HomeMy WebLinkAboutWQ0042171_Application (FTSE)_20210105Central Files: APS _ SWP
12/17/2020
Permit Number W00042171
Program Category
Non -discharge
Permit Type
Gravity Sewer Extension, Pump Stations, & Pressure Sewer Extensions
Primary Reviewer
dean.hunkele
Coastal 5WRule
Permitted Flow
Facility
Permit Tracking Slip
Status
Project Type
In review
New Project
Version
Permit Classification
A
Individual
Permit Contact Affiliation
Facility Name MajorfMinor Region
Fuller Buildings Site 1 Private Pump Station Minor Wilmington
Location Address County
3240 US Hwy 421 New Hanover
Wilmington NC 28401
Owner
Owner Name
Thornberry Ventures LLC
Facility Contact Affiliation
Owner Type
Non -Government
Owner Affiliation
William B. Fuller
2715 Ashton Or
Dates/Events Wilmington NC 28412
Scheduled
Ong Issue App Received Draft Initiated Issuance Public Notice Issue Effective Expiration
12/11/2020SS
MOMS & TUNSTALL
CONSULTING ENGINEERS P.C.
2602 Iron Gate Drive, Suite 102
Wilmington, NC 28412
(910) 343-9653
(910) 343-9604 Fax
John S. Tunstall, P.E.
T. Jason Clark, P.E.
December 10, 2020
NC DEQ
Division of Water Resources
Water Quality Regional Operations Section
Wilmington Regional Office
127 Cardinal Drive Extension
Wilmington, NC 28405
RECEIVED
DEC 11 2020
NCDEQ
WILMINGTON RO
Re: Gravity Sewer Extension Fast -Track Permit Application
US 421 Fuller Buildings (#1)
3240, 3246, & 3252 US Hwy. 421 N
New Hanover County
N&T Project No. 20071
Dear Sir or Madam:
1429 Ash -Little River Road
Ash, NC 28420
(910) 287-5900
(910) 287-5902 Fax
J. Phillip Norris, P.E.
Joseph K. Bland, P.E.
Thomas J. Scheeti, E.I.
Enclosed is one (1) original application form, one (1) copy of the Sewer Calculations, one (1)
copy of the Sewer Narrative, one (1) original Flow Tracking / Acceptance Form (FTSE 10-18)
with flow letter from the Cape Fear Public Utility Authority, one (1) 8 '/2 x 11 color USGS
Topographic Map, one (1) site plan (ledger size) and a $480.00 check for the processing fee.
Please review this information for approval and contact us with any questions or comments you
may have. Thank you for your assistance on this project.
Sincerely,
NORRIS & TUNSTALL
CONSULTING ENGINEERS, P.C.
S . 'Lt . ➢ WJ
Jo n S. Tunstall, P.E.
JST/asn
20071 12-10-20-s-swr-Itr (#1)
Enclosures
cc: William Fuller, Jr. (by E-Mail Only)
William Fuller (by E-Mail Only)
NCHELS License C-3641
SEWER NARRATIVE
US 421 FULLER BUILDINGS
3240, 3246, & 3252 US Hwy. 421 North
Wilmington, North Carolina
For
Thornberry Ventures, LLC
2715 Ashton Drive, Suite 100
Wilmington, NC 28412
(910) 763-0380
kv
-SEAL
1985
September 2020
Prepared by:
NORRIS & TUNSTALL CONSULTING ENGINEERS, P.C.
2602 Iron Gate Drive, Suite 102
Wilmington, North Carolina 28412
(910) 343-9653
(910) 343-9604 (Fax)
License # C-3641
N&T Project #20071 (#1)
NARRATIVE
US 421 FULLER BUILDINGS
3240, 3246, & 3252 US Hwy. 421 North
SEWER SYSTEM:
The private duplex grinder pump station and forcemain system is designed to service
existing office / warehouse buildings each with 15 employees and dock doors. A total of
40 LF of 2" sewer line will be needed to complete the system. The private pump station
will serve the 3 existing buildings plus 2 future buildings. It will connect to the recently
completed 8" forcemain owned by the CFPUA. The average daily design flow of the
station is 3,675 GPD. The pump station reliability of the station is per 15A NCAC 02T
.0305 (h)(1)(C). A portable pump power source shall be dedicated to backup this
station. A letter will be provided that the portable source of power is owned or
contracted for by the permittee and is compatible with the station. Telemetry is provided
at the station with remote notification if a power outage or problem occurs. A high-water
audio and visual alarm are provided.
There are 2 separate conditions that occur at the connection point to the CFPUA
forcemain. The design condition is where the upstream pumps that connect to the
forcemain are off. This results in a very low head condition to pump into the 8"
forcemain. This condition will result in a condition of approximately 15 GPM at 36' TDH.
The second condition is with upstream pump on. The CFPUA can give us little
confidence in the pressure to overcome. Our maximum pump operating will be
approximately 9.5 GPM at 119' TDH.
The MDC requires if practical, a minimum of 2 cycles per hour. Due to the ADF and the
duplex pump / wet well requirements, it is not practical to meet the 2 cycles per hour
requirement.
Also, the MDC requires a minimum of 2 FPS in all forcemain design. Due to the
extreme conditions that the pump station must overcome, we cannot provide 2 FPS in
the desired 2" forcemain. The length of the forcemains is 40 LF. We do not
recommend downsizing the forcemain to less than 2".
A portion of the 2" forcemain in the right-of-way from the CFPUA forcemain to the gate
valve at the right-of-way shall be maintained by the CFPUA.
This system will be served by the Cape Fear Public Utility Authority
State of North Carolina
Department of Environmental Quality
I j Division of Water Resources
15A NCAC 02T .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
Division of Water Resources FTA 04-16 & SUPPORTING DOCUMENTATION
Application Number: (to be wmpleted by DWR)
All items must be completed or the application will be returned
I. APPLICANT INFORMATION:
1. Applicant's name: Thombeny Ventures. LLC (company, municipality, HOA, utility, etc.)
2. Applicant type: ❑ Individual ® Corporation ❑ General Partnership ❑ Privately -Owned Public Utility
❑ Federal ❑ State/County ❑ Municipal ❑ Other
3. Signature authority's name: William B. Fuller per 15A NCAC 02T .0106(b)
Title: Member / Manager
4. Applicant's mailing address: 2715 Ashton Drive, Suite 100
City: Wilmington State: NC Zip: 28412
5. Applicant's contact information:
Phone number: (910) 763-0380 Email Address: wbfuller@aol.com
II. PROJECT INFORMATION:
1. Project name: US 421 Fuller Buildings (3240, 3246, & 3252 US Hwy 421 N)
2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project
If a modification, provide the existing permit number: W000 and issued date:
If new construction but part of a master plan, provide the existing permit number: W000
3. County where project is located: New Hanover
4. Approximate Coordinates (Decimal Degrees): Latitude: 34.28734' Longitude:-77,96614'
5. Parcel ID (if applicable): R03200-002-008-000
(or Parcel ID to closest downstream sewer)
III. CONSULTANT INFORMATION:
1. Professional Engineer: John S. Tunstall, P.E.License Number: 19851
Firm: Norris & Tunstall Consulting Engineers, P.C.
Mailing address: 2602 Iron Gate Drive, Suite 102
City: Wilmington State: NC Zip: 28412-
Phone number: (910) 343-9653 Email Address: jtunstall(a ntengineers.com & anorris@nteneineers.com
IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION:
L Facility Name: James A. Loughlin (Northside W WTP) Permit Number: NC 0023965
Owner Name: Cape Fear Public Utility Authority
V. RECEIVING DOWNSTREAM SEWER INFORMATION (if different than WWTF):
1. Permit Number(s): W00039283
System Wide Collection System Permit Number(s) (if applicable): WQCS
Owner Name(s): Cape Fear Public Utility Authority
FORM: FTA 04-16 Page 1 of 5
yi. GENERAL REQUIREMENTS
1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached?
❑ Yes ❑No NN/A
2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached?
[:]Yes (—]No NN/A
3. If the Applicant is a Home/Property Owners' Association has an Operational Agreement (FORM: HOA) been attached?
❑ Yes ❑No NN/A
4. Origin of wastewater: (check all that apply):
❑ Residential Owned ❑ Retail (stores, centers, malls) ❑ Car Wash
❑ Residential Leased ❑ Retail with food preparation/service ❑ Hotel and/or Motels
❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool /Clubhouse
❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash
N Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment)
5. Nature of wastewater : 100 % Domestic/Commercial 100 % Commercial
_ % Industrial (See 15A NCAC 02T .0103(20))
"Is there a Pretreatment Program in effect? ❑ Yes ❑ No
6. Hasa flow reduction been approved under 15A NCAC 02T .0114(f)? ❑ Yes N No
➢ hes, provide a copv of flow reduction approval letter
7. Summarize wastewater generated by project:
Establishment Type (see 02T.0114(t)1
Daily Design Flow a,s
No. of Units
Flow
3240: Business General / Warehouse
25 gaV Day / Employee
15 Emp
375 GPD
3246: Business General / Warehouse
25 gal/ Day / Employee
15 Emp
375 GPD
3252: Business General / Warehouse
25 gal/ Day / Employee
15 Emp
375 GPD
3240: Business General / Warehouse
100 gal/Dock
2
200 GPD
3246: Business General / Warehouse
100 gal/Dock
4
400 GPD
3252: Business General / Warehouse
100 gal/Dock
4
400 GPD
1) 550 U p
IJ
Total
3,675 GPD
a See 15A NCAC 02T .0114(b), (d). (c)(1) and (ee)(2) for caveats to wastewater design flow rates (i.e., minimum flow per
dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas;
and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined
in G.S. 42A-4).
b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.0114) shall be
determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data.
8. Wastewater generated by project: 3 675 GPD (per 15A NCAC 02T 0114)
➢ Do not include future flows or previously permitted allocations
If permitted flow is zero, indicate why:
❑ Pump Station or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line
❑ Flow has already been allocated in Permit Number:
❑ Rehabilitation or replacement of existing sewer with no new flow expected
❑ Other (Explain):
FORM: FTA 04-16 Page 2 of 5
VII. GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T .0305 & MDC (Gravity Sewers):
1. Summarize gravity sewer to be permitted:
Size (inches) Length (feet) Material
➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria
➢ Section III contains information related to minimum slopes for gravity sewer(s)
➢ Oversizing lines to meet minimum slope requirement is not allowed and a violation of the MDC
VIII. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains):
COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
1. Pump station number or name: 3240, 3246, & 3252 US Hwy. 421 North
2. Approximate Coordinates (Decimal Degrees): Latitude: 34.28734' Longitude:-77.96614°
3. Design flow of the pump station: 7 stiiiieas-gallons per day (firm capacity)
4. Operational point(s) of the pump(s): 9.5 & 15.4 gallons per minute at 119 & 36 feet total dynamic head (TDH)
5. Summarize the force main to be permitted (for this Pump Station):
Size (inches)
Length (feet)
Material
2"
40
PVC
6. Power reliability in accordance with 15A NCAC 02T .0305(h)(1):
❑ Standby power source or pump with automatic activation and telemetry - 15A NCAC 02T .0305(h)(1)(B):
➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
➢ Must be permanent to facility
Or if the pump station has an average daily flow less than 15,000 gallons per day:
® Portable power source with manual activation, quick -connection receptacle and telemetry - 15A NCAC 02T
.0305(h)(1)(C)
or
❑ Portable pumping unit with plugged emergency pump connection and telemetry - 15A NCAC 02T .0305(h)(1)(C):
➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant (draft agreement)
and is compatible with the station.
➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage
capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided
in the case of a multiple station power outage.
FORM: FTA 04-16 Page 3 of 5
IX. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T.0305(f)):
1. Does the project comply with all separations found in 15A NCAC 02T.0305(f) & (g)
➢ 15A NCAC 02T.0305 contains minimum separations that shall be provided for sewers stems:
Setback Parameter*
Separation Required
Storm sewers and other utilities not listed below vertical
24 inches
Water mains vertical -water over sewer including in benched trenches
18 inches
Water mains horizontal
10 feet
Reclaimed water lines vertical - reclaimed over sewer
18 inches
Reclaimed water lines(horizontal - reclaimed over sewer
2 feet
**Any private or public water supply source, including any wells, WS-I waters of Class I or
Class II impounded reservoirs used as a source of drinking water
100 feet
"Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal
high water or tide elevation and wetlands see item IX.2
50 feet
**Any other stream, lake, impoundment, or ground water lowering and surface drainage
ditches
10 feet
Any building foundation
5 feet
Any basement
10 feet
Top slope of embankment or cuts of 2 feet or more vertical height
10 feet
Drainage systems and interceptor drains
5 feet
Any swimming pools
10 feet
Final earth grade vertical
36 inches
➢ 15A NCAC 02T.0305(4) contains alternatives where separations in 02T.0305(f) cannot be achieved.
➢ **Stream classifications can be identified using the Division's NC Surface Water Classifications weboage
➢ If noncompliance with 02T.0305(f) or (a), see Section X of this application
2. Does the project comply with separation requirements for wetlands? (50 feet of separation) ® Yes [—]No
➢ See the Division's draft separation requirements for situations where separation cannot be meet
➢ No variance is required if the alternative design criteria specified is utilized in design and construction
➢ As built documents should reference the location of areas effected
3. Does the project comply with all setbacks found in the river basin rules per 15A NCAC 02B .0200? ® Yes ❑ No
➢ This would include Trout Buffered Streams per 15A NCAC 213.0202
4. Does the project comply with an individual 404 Permit or any 401 Certifications? ® Yes ❑ No
➢ Wetland -related permits shall be requested, obtained, and adhered to for projects that impact wetlands or surface waters
➢ Information can be obtained from the 401 & Buffer Permittine Branch
5. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permits/certifications)?
// 0 M
Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications are being prepared, have
been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and
sedimentation control plans, stormwater management plans, etc.).
6. Does this project include any sewer collection lines that are deemed "high -priority?"
Per 15A NCAC 02T.0402, "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer
positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer.
❑ Yes ® No
➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location).
High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections
documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System -Wide Collection permit.
FORM: FTA 04-16 Page 4 of 5
.X. CERTIFICATIONS:
1. Does the submitted system comply with 15A NCAC 02T, the Minimum Design Criteria for the Pertnittine of Pump Stations
and Force Mains (latest version), and the Gravity Sewer Minimum Design Criteria latest version as applicable? _
® Yes ❑ No See, , TIl1.c�lVJli ham
If No, complete and submit the Variance/Alternative Design Request application (VADt 1 b 14)'and''su6PoitiTg documentsfor
review. Approval of the request is required prior to submittal of the Fast Track Application and supporting documents
2. Professional Engineer's Certification:
that this application for
Engineer's name from Application Item III.
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications,
engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best
of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer
Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting
of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this
submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and
have judged it to be consistent with the proposed design.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation.
North Carolina Professional Engineer's seal, signature, and date:
3. Applicant's Certification per 15A NCAC 02T .0106(b):
I,
s name & title from Application Item I.3.)
that this application for
has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of
this application are not completed and that if all required supporting documentation and attachments are not included, this
application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non -
discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties,
injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water Resources should a condition
of this permit be violated. I also understand that if all required parts of this application package are not completed and that if
all required supporting information and attachments are not included, this application package will be returned to me as
incomplete.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation.
Signature: , Date: e4 Jo
FORM: FTA 04-16 Page 5 of 5
N-T AV- InI l ( W4)
State of North Carolina
Department of Environmental Quality
-FJWRDivision of Water Resources
Division of Water Resources Flow Tracking for Sewer Extension Applications
(FTSE 10-18)
Entity Requesting Allocation: Thomberry Ventures, LLC
Project Name for which flow is being requested: US 421 Fuller Buildings (3240, 3245, & 3252 US Hwy 421 N)
More titan one FTSE may be required for a single project if the owner of the WWTP is not responsible for all pump
stations along the route of the proposed wastewater flow.
Complete this section only if you are the owner of the wastewater treatment plant
a. WWTP Facility Name: James A. Loughlin (Northside) WWTP
b. WWTP Facility Permit #: NPDES NC 0023965
c. WWTP facility's permitted flow
d. Estimated obligated flow not yet tributary to the WWTP
e. WWTP facility's actual avg. flow
f. Total flow for this specific request
g. Total actual and obligated flows to the facility
h. Percent of permitted flow used
All flows are in MGD
16.000
3.509
10.661
0.003675
14.173
88.6
Il. Complete this section for each pump station you are responsible for along the route of this proposed
wastewater flow.
List pump stations located between the project connection point and the WWTP:
(A) (B) (C) (D)—(B+C)
(E)=(A-D)
Design
Average Approx. Obligated,
Pump Pump Daily Current Not Yet Total Current
Station Station Finn Flow** Avg. Daily Tributary Flow Plus
(Name or Permit Capacity, * (Firm / pf), Flow, Daily Flow, Obligated
Available
Number) No. MGD MGD MGD MGD Flow
Capacity***
10 WQ0039922 22.090 7.363 3.472 0.611 4.083
3.280
12 WQ0039517 4.920 1.970 0.672 0.234 0.906
1.064
* The Firm Capacity (design flow) of any pump station is defined as the maximum pumped flow
that can be achieved with the largest pump taken out of service.
** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking factor
(pf) not less than 2.5, per Section 2.02(A)(4)(c) of the Minimum Design Criteria.
*** A Planning Assessment Addendum shall be attached for each pump station located
between the project connection point and the WWTP where the Available Capacity is < 0.
Downstream Facility Name (Sewer): _Cape Fear Public Utility Authority
Downstream Permit Number:
Page 1 of 6
FTSE 10-18
III. Certification Statement:
I Jeff Theberge, CFPUA Eng. Mgr certify to the best of my knowledge that the addition of
the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving
wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity
related sanitary sewer overflows or overburden any downstream pump station en route to the receiving
treatment plant under normal circumstances, given the implementation of the planned improvements
identified in the planning assessment where applicable. This analysis has been performed in accordance
with local established policies and procedures using the best available data. This certification applies to
those items listed above in Sections I and II plus all attached planning assessment addendums for which I
am the responsible party. Signature of this form certifies that the receiving collection system or treatment
works has adequate capacity to transport and treat the proposed new wastewater.
10/14/2020
Official Signature Date
Engineering Manager
Title of Signing Official
Page 2 of 6
FTSE 10-18
12/17/2020
34"17'14.4"N 77°57'58.1 "W - Google Maps
Google Maps 34'1714.4"N 77°57'58.1 V
9Alsco
J B Lawn Sprinklers, Inc
Q
Live Wire
Powder Coating
afo "'cy
0
d Southern Industrial
9
Constructors
yc Oc
Q a; j Z
Wash On Wheels
BFPE International
V
QLinder Industrial
Machinery
n, V q1
QFleetPride
MCO Transport Q
J,
Fear Habitat 'Q
Old Dominion ;! /�� /for Humanity.
Freight Line
Google
Map data @2020 200 It r
https://www.google.com/maps/place/34' 17' 14.4"N+77'57'58+1 "W/@34.2878006,-77.9682169,17zldata='4m5l3m4l1 sOx0:OxO!8m2!3d34.28734!4d-77.96614?hl=en 1 /2