HomeMy WebLinkAboutWQ0039181_Compliance Evaluation Inspection_20201218ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANI£L SMITH
Director
Mr. Aaron Goss, President (via email)
Carolina Malt House, Inc.
12969 Statesville Boulevard
Cleveland, North Carolina 27013
Dear Mr. Goss:
NORTH CAROLINA
Environmental Quality
December 18, 2020
Subject: Compliance Evaluation Inspection
Carolina Malt House, Inc.
Permit No. WQ0039181
Rowan County
The MRO would like to extend our thanks to yourself, Mr. Lynn Aldridge and Mr. Mark Van Wagenburg
for the time and assistance provided during the November 23, 2020, inspection. Enclosed you will find
the report for the compliance inspection, which should be self-explanatory.
We have received the documents requested in the additional information request associated with your
permit modification. These documents are being reviewed by Central Office and MRO staff. The draft
permit for the modification will be sent to you as soon as the review has been completed.
Should you have further questions or concerns regarding the report, please contact Edward Watson at
704-235-2198 or edward.watsonkncdenr.gov.
Sincerely,
EDocuSigned by:
�4t W H P44ft
F161FB69A2D84A3...
Andrew H. Pitner, Assistant Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
Attachment: Compliance Inspection Report
CC: Laserfiche file
Lynn Aldridge (via email)
D Q
�, _ North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR fH CA�in!.INA
14'tore'wm—ta�a"1 704,663.1699
Compliance Inspection Report
Permit: WQ0039181 Effective: 07/14/17 Expiration: 06/30/22 Owner : Carolina Malt House Inc
SOC: Effective: Expiration: Facility: Carolina Malt House WWTF
County: Rowan 12969 Statesville Blvd
Region: Mooresville
Cleveland NC 27013
Contact Person: Aaron F Goss Title: President Phone: 704-412-9962
Directions to Facility:
System Classifications: SI,
Primary ORC: A Lynn Aldridge
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 11/23/2020 Entry Time 01:OOPM
Primary Inspector: Edward Watson
Secondary Inspector(s):
Certification: 993778 Phone:704-431-5266
Exit Time: 02:30PM
Phone:
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Record Keeping Treatment Lagoons
Use Records
End Use -Irrigation Treatment Influent Pump Station Treatment Flow Measurement
(See attachment summary)
Page 1 of 5
Permit: WQ0039181 Owner - Facility: Carolina Malt House Inc
Inspection Date: 11/23/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
On November 23, 2020, MRO staff performed a Compliance Evaluation Inspection for Carolina Malt House under permit
WQ0039181. A permit modification has been submitted for increasing the Spray Irrigation application amount This request
is currently under review. The permit modification also includes doubling the flow to the lagoon. The permittee is planning
on installing an influent flow meter to aid with monitoring the volume of flow entering the lagoon.
The permittee needs to increase flow to the lagoon and increase the application volume to the dedicated application fields.
The MRO is suggesting the permittee consider adding more acreage for spray irrigation. It is not unusual to have spray
irrigation in wooded areas. The additional application fields should provide relief for the permittee to keep the lagoon volume
to a level that will accept additional inflow.
Page 2 of 5
Permit: WQ0039181 Owner - Facility: Carolina Malt House Inc
Inspection Date: 11/23/2020 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Activated Sludge Spray, HR
❑
Infiltration System
❑
Recycle/Reuse
❑
Activated Sludge Spray, LR
❑
Activated Sludge Drip, LR
❑
Single Family Drip
❑
Single Family Spray, LR
❑
Lagoon Spray, LR
Treatment Influent Pump Station
Yes No NA NE
Is the pump station free of bypass lines or structures?
❑ ❑ ❑
Is the general housekeeping acceptable?
❑ ❑ ❑
Are all pumps present?
❑ ❑ ❑
Are all pumps operable?
❑ ❑ ❑
Are floats/controls operable?
❑ ❑ ❑
Are audio and visual alarms available?
❑
❑ ❑
Are audio and visual alarms operational?
❑
❑ ❑
# Are SCADA/Telemetry alarms required?
❑
❑ ❑
Are SCADA/Telemetry available?
❑
❑ ❑
Are SCADA/Telemetry operational?
❑
❑ 0 ❑
Comment: The alarms were not reviewed during the site visit.
Treatment Flow Measurement -Influent Yes No NA NE
Is flowmeter calibrated annually? ❑ ❑ 0❑
Is flowmeter operating properly? ❑ ❑ 0❑
Does flowmeter monitor continuously? ❑ ❑ 0 ❑
Does flowmeter record flow? ❑ ❑ 0 ❑
Does flowmeter appear to monitor accurately? ❑ ❑ 0 ❑
Comment: The permittee is planning on adding a flow meter to the discharge into the lagoon. The permitteE
is in the process of a permit modification and will be requesting the allowance of additional flow
to the treamtent lagoon as part of the modification request.
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment: Metering is not required for this permit.
Page 3 of 5
Permit: WQ0039181 Owner - Facility: Carolina Malt House Inc
Inspection Date: 11/23/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Treatment Flow Measurement -Effluent Yes No NA NE
Is flowmeter calibrated annually? ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ 0 ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment: O&M records indicate the flow meter has been replaced within the past year. Calibration
records appear to be accurate and up-to-date. Please keep O&M records in a dedicated book.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑ ❑ ❑
NDAR?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑
❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑
❑ ❑
Are all samples analyzed for all required parameters?
❑
❑ ❑
Are there any 2L GW quality violations?
❑
❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑
❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑ ❑ ❑
# Are PAN records required?
❑ ❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑ ❑ ❑
Is a copy of the SOC readily available?
❑
❑ ❑
No treatment units bypassed since last inspection?
❑
❑ ❑
Page 4 of 5
Permit: WQ0039181 Owner - Facility: Carolina Malt House Inc
Inspection Date: 11/23/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Comment: Groundwater monitoring is not required for this permit. The current application rates are being
exceeded. The application limits are being reviewed by MRO and CO as part of a permit
modification. Current application rates do not exceed the soil scientist or engineering
recommendations.
End Use -Irrigation
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
Comment: The closest supply well is over 500 ft. from the application fields.
The spray application equipment was viewed to be operational during the site visit.
Yes No NA NE
■❑❑❑
■❑❑❑
■❑❑❑
■❑❑❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑■❑❑
❑■❑❑
■❑❑❑
❑■❑❑
❑■❑❑
❑❑■❑
❑❑■❑
❑❑■❑
Page 5 of 5