December 15, 2020
John F Zachwieja
Slash Creek Condominium Homeowners Association
PO Box 1465
Kitty Hawk, NC 27949
SUBJECT: Compliance Inspection Report
Slash Creek WWTP
Non -discharge Permit No. WQ0022725
Dare County
Dear Mr. Zachwieja:
The North Carolina Division of Water Resources conducted an inspection of the Slash Creek WWTP on
11/19/2020. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non -discharge Permit No. WQ0022725. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Paul Mays with the Water Quality
Regional Operations Section in the Washington Regional Office at 252-948-3940 or via email at
paul.mays@ncdenr.gov.
ATTACHMENTS
Cc: Laserfiche
Sincerely,
P hails
Paul Mays, Environmental Specialist 1
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
ID ra pans t t Erre r orm.,t q, - I D arsua aa Waterrsaso.
Was^. rgt 5 8:ea Off., 194., heat rgn .ars Na 1 Was:Was^ rgtc.:. hxa Zara a Be.P&
E4E1
Compliance Inspection Report
Permit: WQ0022725 Effective: 11/07/17
SOC:
County: Dare
Region: Washington
Effective:
Expiration: 10/31/22 Owner : Slash Creek Condominium Homeowners
Association
Expiration: Facility: Slash Creek WWTP
57440 NC 12
Hatteras NC 27943
Contact Person: John F Zachwieja Title: Board President Phone: 252-261-1200
Directions to Facility:
on the outer banks, take NC Highway 12 south of Buxton and Frisco and Slash Condos will be located on the right (sound side) of
NC 12 as you enter the town of Hatteras
System Classifications: SI, WW3.,
Primary ORC: David Pharr Certification: 21101 Phone: 252-473-3461
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 11/19/2020
Primary Inspector: Paul M Mays
Secondary Inspector(s):
Entry Time 11:OOAM
Reason for Inspection: Follow-up
Permit Inspection Type: Reclaimed Water
Facility Status: Compliant 0 Not Compliant
Question Areas:
▪ Treatment Flow Measurement -Effluent
▪ Treatment Flow Measurement -Water
Use Records
N I Treatment Filters
▪ Treatment Sludge Storage/Treatment
▪ Treatment Disinfection
▪ Storage
(See attachment summary)
Exit Time: 12:30PM
Phone: 252-948-3940
Inspection Type: Compliance Evaluation
▪ Treatment Flow Measurement -Influent
1111 Treatment
▪ Record Keeping
▪ End Use -Irrigation
▪ Treatment Flow Measurement
Standby Power
• Miscellaneous Questions
▪ Treatment Barscreen
▪ Treatment Activated Sludge
▪ Treatment Clarifiers
1111 Treatment Return pumps
▪ Coastal Requirements
Page 1 of 7
Permit: WQ0022725 Owner - Facility: Slash Creek Condominium Homeowners Association
Inspection Date: 11/19/2020
Inspection Type : Compliance Evaluation Reason for Visit: Follow-up
Inspection Summary:
On 11/19/2020 from 11:00am to 12:30pm, Paul Mays and Robert Tankard with the Division of Water Resources from the
Washington Regional Office conducted an inspection of Slash Creek WWTP operating under permit#WQ0022725. The
facility was found to be non -compliant with permit #WQ0022725. Below are the findings during the inspection:
The backwash function via air scouring for the tertiary filter was not operational during the inspection. The backup generator
was not operational and the "warning light" was on for the turbidity meter during the inspection. When the generator was
further inspected the display on the generator pointed to an ignition fault. ORC David Phar stated the battery died the
morning of the inspection. Michelle Pharr followed up with photo evidence that the generator, the turbidity meter, and
backwash function of the tertiary filter are now fully operational. These photos are included in the report and docemented.
The Turbidity meter was calibrated on 05/16/2020
Effluent flowmeter was calibrated on 05/01/2020
The 10' x 12' x 13' aeration basin appeared to be fully operation. However, the entire basin was covered with a thick foam. It
was unknown what caused the foam layer to form on the basin.
All records and reports requested for the inspection were available. Operation and maintenance records were available for
review. Upon review of the 07/2020 NDMR discrepancies for total phosphorous, PH, TSS and DO were found between the
report and the lab data. On 07/15/2020 PH was 7.46 for the NDMR and 7.46 from lab data, total phosphorous was 0.73mg/I
and not found in lab data, TSS was 3.4mg/I in NDMR and 4.55mg/I from lab data and lastly, DO was 3.4mg/I in NDMR and
4.55mg/I in lab data. The 06/2020 NDMR was spot checked with no discrepancies. Michelle Pharr will be followed up with an
amended 07/2020 NDMR and corresponding lab data. No discrepancies were found within the amended report.
At the time of inspection many of the irrigation nozzles were not fully functional and did not irrigate properly. Due to this the
specified acreage in the permit was not being irrigated. The irrigation nozzles require maintenance or fixing in order to
correct this issue. Documentation has been provided showing that the irrigation system was fully functional after the
inspection by Michelle Pharr. This documentation is included at the end of the report and documented.
Page 2 of 7
Permit: WO0022725 Owner • Facility: Slash Creek Condominium Homeowners Association
Inspection Date: 11/19/2020
Inspection Type : Compliance Evaluation Reason for Visit: Follow-up
Type
Yes No NA NE
Lagoon Spray, LR ❑
Activated Sludge Spray, LR ❑
Single Family Drip ❑
Recycle/Reuse ❑
Infiltration System ❑
Single Family Spray, LR ❑
Activated Sludge Spray, HR ❑
Activated Sludge Drip, LR ❑
Reuse (Quality)
Treatment
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑ ❑
Comment: The backwash function for the tertian/ filter was not operational during the inspection. The
backup generator was not operational and the "warning light" was on for the turbidity meter
during the inspection.
Treatment Flow Measurement -Influent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment:
Treatment Flow Measurement -Water Use Records
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement -Effluent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Yes No NA NE
❑ ❑• ❑
❑ ❑ ❑
❑ ❑•❑
❑ ❑•❑
❑ ❑•❑
Yes No NA NE
❑ ❑•❑
❑ ❑•❑
Yes No NA NE
• ❑ ❑ ❑
■ ❑❑❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 3 of 7
Permit: WQ0022725 Owner - Facility:Slash Creek Condominium Homeowners Association
Inspection Date: 11/19/2020 Inspection Type : Compliance Evaluation
Reason for Visit: Follow-up
Comment: The Turbidity meter was calibrated on 05/16/2020
Effluent flowmeter was calibrated on 05/01/2020
Standby Power
Is automatically activated standby power available?
Is generator tested weekly by interrupting primary power source?
Is generator operable?
Does generator have adequate fuel?
Yes No NA NE
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The generator was not functional during inspection. When the generator was further inspected
the display on the generator pointed to an ignition fault. ORC David Phar stated the battery died
the morning of the inspection.
Treatment Barscreen
Is it free of excessive debris?
Is disposal of screenings in compliance?
Are the bars spaced properly?
Is the unit in good condition?
Comment:
Treatment Activated Sludge
Is the aeration mechanism operable?
Is the aeration basin thoroughly mixed?
Is the aeration equipment easily accessed?
Is Dissolved Oxygen adequate?
Are Settleometer results acceptable?
Is activated sludge an acceptable color?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑•
• ❑ ❑ ❑
❑ ❑ ❑•
Comment: The 10' x 12' x 13' aeration basin appeared to be fully operation. However, the entire basin was
covered with a thick foam. It was unknown what caused the foam laver to form on the basin.
Treatment Clarifiers Yes No NA NE
Are the weirs level? ❑ ❑ ❑
Are the weirs free of solids and algae? •000
Is the scum removal system operational? • ❑ ❑ ❑
Is the scum removal system accessible? MEMO
Is the sludge blanket at an acceptable level? ❑ ❑ ❑•
Is the effluent from the clarifier free of excessive solids? • 000
Comment:
Treatment Return pumps
Are they in place?
•
Yes No NA NE
❑ ❑ ❑
Page 4 of 7
Permit: WO0022725 Owner - Facility: Slash Creek Condominium Homeowners Association
Inspection Date: 11/19/2020 Inspection Type : Compliance Evaluation
Reason for Visit: Follow-up
Are they operational?
Comment:
Treatment Filters
Is the filter media present?
Is the filter media the correct size and type?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids?
Is the mud well free of excessive solids and filter media?
Does backwashing frequency appear adequate?
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑•
❑ • ❑ ❑
❑•❑ ❑
❑ ❑ ❑•
❑ ❑ ❑•
❑•❑ ❑
Comment: The backwash function via air scouring for the tertiary filter was not operational during the
inspection.
Treatment Sludge Storage/Treatment
Is the aeration operational?
Is the aeration pattern even?
If required, are Sanitary "Ts" present in tankage?
Comment:
Treatment Disinfection
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑■❑
• ❑ ❑ ❑
❑ ❑•❑
❑ ❑ • ❑
❑ ❑ ❑
❑ ❑•❑
❑ ❑•❑
• ❑■❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑•❑
❑ ❑•❑
❑ ❑•❑
Page 5 of 7
Permit: WQ0022725 Owner - Facility: Slash Creek Condominium Homeowners Association
Inspection Date: 11/19/2020
Inspection Type : Compliance Evaluation Reason for Visit: Follow-up
Record Keeping
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑❑❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
❑ ❑•❑
❑ ❑•❑
❑ ❑•❑
O 0110
❑ ❑ • ❑
❑ 01E0
❑ ❑•❑
❑ ❑•❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑•❑ ❑
❑ ❑•❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑•❑
• ❑ ❑ ❑
Comment: All records and reports requested for the inspection were available. Operation and maintenance
records were available for review. Upon review of the 07/2020 NDMR discrepancies for total
phosphorous, PH, TSS and DO were found between the report and the lab data. On 07/15/2020
PH was 7.46 for the NDMR and 7.46 from lab data, total phosphorous was 0.73mq/I and not
found in lab data, TSS was 3.4mq/I in NDMR and 4.55mq/I from lab data and lastly, DO was
3.4mq/I in NDMR and 4.55mq/I in lab data. The 06/2020 NDMR was spot checked with no
discrepancies.
End Use -Irrigation
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 6 of 7
Permit: WQ0022725
Inspection Date: 11/19/2020
Owner - Facility:Slash Creek Condominium Homeowners Association
Inspection Type : Compliance Evaluation Reason for Visit: Follow-up
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
■ ❑❑❑
. ❑ ❑ ❑
❑ • ❑ ❑
• ❑ ❑ ❑
❑ ■❑❑
• ❑ ❑ ❑
❑ ❑ ❑•
❑ ❑•❑
❑ ❑•❑
O 0110
• ❑ ❑ ❑
❑ ❑•❑
❑ ❑•❑
O E11110
❑ ❑ • ❑
Comment: At the time of inspection many of the irrigation nozzles were not fully functional and did not
irrigate properly. Due to this the specified acreage was not being irrigated. The irrigation nozzles
require maintenance or fixing in order to correct this issue.
Coastal Requirements
Are essential treatment units provided in duplicate?
Is an adequately sized aerated equalization basin present?
If so, is it operable?
If present, are diffusers cleaned regularly?
Is the equalization capacity adequate?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
111000
❑ ❑•❑
• ❑ ❑ ❑
Page 7 of 7
A �� SCou( t
Scouc
Aic 5ux)(
AIR SCOUR BLOWER
HAND OFF AUTO
AIRSCOUR NO.1
HAND OFF AUTO
NI( Scovc
Uem«k(T 1
G-C (\ec ()Oro( 2
•
3'411
J.1
ALARM
/UARM 2
TO
Tucb-lay
1 vc b-icli-\ 1
(External) Slash Creek Irrigation System
micheltedPob h2otom
In 0 Met; Pau4M
Os mire Ili Now a si min now ms ow naps a auplataammnce towewnIn a was Women
e') Reply 01 Reply Pll -i Seward w.
Tw 124,7020 biiahl
[utmost. blarnelarnalt Co not sect links o open ahacMnemsunlau you verify. fend al aurpkbusamaa as m attachment to Rese.tl w
December 8, 2020
To: Paul Mays
DENR
From: Michelle Pharr
aibemad. Environmental
Reference: Slash Creek Irrigation System
Dear Mr. Mays,
Per your request, as faltow up to the November 19, 2020 Slash Creek impaction, I am providing you with written documentation of the noidng status of the Slash Creek Irrigation System. There are 16 spray irrigation acmes, 1,2,5.6,7,8,9,10,11,12,13,14,15,16,17,18, with B to 10
spray IrrlgaUon nozzles per zone. Post Inspection, all zones ware chocked and ab nozzles are working.
Than have boon 5 spray nozzles Identified, when activated, are not consistent with their spray pattern. The owners have now winterized the Irrigation system. We will work on the nozzles that have Irregular spray performance In the spring when the krigatfon system Is Initialized.
Best regards,
Michelle Pharr