HomeMy WebLinkAboutWQ0040005_NOV-2020-PC-0507_20201204ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
NORTH CAROLINA
Environmental Quality
December 4, 2020
CERTIFIED MAIL # 70181130 0000 1608 2453
RETURN RECEIPT REQUESTED
Shane Fox, Town Manager
Town of Blowing Rock
PO Box 47
Blowing Rock, NC 28605
Subject: NOTICE OF VIOLATION — (NOV-2020-PC-0507)
Permit No. WQ0040005
Town of Blowing Rock
Townes of Blowing Rock
Wastewater Collection System Extension Permit Watauga County
Dear Mr. Fox:
The Final Engineer Certification for the subject project was received by our office on August 10,
2020 and reflects non-compliance with the subject permit, 15A NCAC 02T regulations, and the
Division's Minimum Design Criteria. The violations are described below and require your
attention and action:
1) 6-inch gravity sewer was installed between MH-1 and MH-2 (Shown of Sheet C-1 of the as -
built drawings) as opposed to the 8-inch gravity sewer authorized by the permit. This finding
also represents non-compliance with 15A NCAC .0305 (i) (1), which requires public sewers
be equipped with a minimum of 8-inch diameter pipe, and 15A NCAC 02T .0116 (a) which
states: Prior to the operation of any sewer system, treatment works, utilization system, or
disposal system for which an individual permit has been issued in accordance with this
Subchapter and the application prepared by licensed professional, a certification shall be
received by the Division from a professional certifying that the sewer system, treatment works,
utilization system, or disposal system has been installed in accordance with the rules, all
minimum design criteria except as noted, and approved plans and specifications.
Please be aware, in accordance with the subject permit, it shall be the responsibility of the
Permittee to ensure that the as -constructed project meets the appropriate design criteria and rules.
Failure to comply may result in penalties in accordance with North Carolina General Statute § 143-
215.6A through § 143-215.6C, construction of additional or replacement wastewater collection
D � North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office [ 450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
NOh �HCARO UHA
^^ •^ �ku^m I u�•i` r 336.776.9800
facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing
board.
Please submit a written response that provides a description of the proposed corrective action(s)
to be implemented to address the violation(s) described herein. Your written response should
include an anticipated schedule for the implementation of the corrective action(s) proposed and
shall be received within 10 days of receipt of this Notice. The corrective action(s) proposed to
reconcile the described violation(s) shall be installed and certified within 120-days of receiving
Division approval of the proposed corrective measures.
In accordance with North Carolina General Statute 143-215.1, flow shall remain non -tributary
to the subject sewer extension, until a certification is received by the Division from a professional
certifying that the sewer system authorized by the subject permit has been installed in accordance
with the rules, all minimum design criteria except as noted, and approved plans and specifications.
If you have questions regarding this correspondence, please contact Justin Henderson or me at
(336) 776-9800.
Sincerely,
Docu Siiggned by:
LOti l 15.Agt-
145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
NCDEQ-DWR
cc: Michael Trew, P.E.-Municipal Engineering Services Co.- trewmescokbellsouth.net
PERCS
Laserfiche Files — (electronic copy)
Permit: WQ0040005
SOC:
County: Watauga
Region: Winston-Salem
Compliance Inspection Report
Effective: 05/16/18 Expiration: Owner: Town of Blowing Rock
Effective: Expiration: Facility: Townes of Blowing Rock
Contact Person: Shane Fox
Directions to Facility:
System Classifications:
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Title:
Certification:
Phone: 828-295-5200
Phone:
Inspection Date: 08/11/2020 Entry Time 11:OOAM Exit Time: 12:OOPM
Primary Inspector: Justin L Henderson Phone: 336-776-9701
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Gravity Sewer Extension, Pump Stations, & Pressure Sewer Extensions
Facility Status: ❑ Compliant Not Compliant
Question Areas:
Miscellaneous Questions Misc
(See attachment summary)
Page 1 of 3
Permit: WQ0040005 Owner - Facility: Town of Blowing Rock
Inspection Date: 08/11/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
The Final Engineer Certification, received on August 10, 2020, for the subject project reflects non-compliance with the
subject permit, 15A NCAC 02T regulations, and the Division's Minimum Design Criteria. The violation(s) described below
requires your attention and action:
1) 6-inch gravity sewer was installed between MH-1 and MH-2 (Shown of Sheet C-1 of the as -built drawings), as opposed
to that authorized by the permit of 8-inch gravity sewer. This finding also represents non-compliance with 154 NCAC .0305
(i) (1), which requires public sewers be equipped with a minimum of 8-inch diameter pipe, and 15A NCAC 02T .0116 (a)
which states: Prior to the operation of any sewer system, treatment works, utilization system, or disposal system for which
an individual permit has been issued in accordance with this Subchapter and the application prepared by licensed
professional, a certification shall be received by the Division from a professional certifying that the sewer system, treatment
works, utilization system, or disposal system has been installed in accordance with the rules, all minimum design criteria
except as noted, and approved plans and specifications.
Page 2 of 3
Permit: WQ0040005
Inspection Date: 08/11/2020
Misc
Is the facility compliant?
Comment:
Owner - Facility: Town of Blowing Rock
Inspection Type: Compliance Evaluation Reason for Visit: Routine
Yes No NA NE
❑ ❑ ❑ ❑
Page 3 of 3