HomeMy WebLinkAboutNCG030070_2020 DMR_20201124J► l! n
M O W
November 24, 2020
NCDEQ - Asheville Regional Office
Division of Energy, Mineral, and Land Resources
2090 U.S. 70 Highway
Swannanoa, NC 28778-8211
ABB Motors and Mechanical
70 Reems Creek Rd
Weaverville, NC 28787
Re: ABB Motors and Mechanical (Formerly Baldor Electric)
General Permit No. NCG030070
Please find enclosed the stormwater discharge monitoring report for October 2020.
This was our second semi-annual sampling.
We currently remain in Tier III status at conveyance point B.
B — Zinc
No significant process sources of zinc have been identified at our facility. We
continue to believe that the major contributors are infrastructure sources. Run off
from metal roofing is the primary culprit for outfall B. We have continued increasing
the cleaning frequency for outside storage areas where forklifts and delivery trucks
travel.
Please contact me with operational or compliance issues.
Sincer ly,
Gary Massey
HSE Manager
ABB Motors and Mechanical
828-645-1718
a .masse us.abb.com
Page 1 of 1
NCDEQ Division of Energy, Mineral and Land Resources
Stormwater Discharge Monitoring Report (DMR) Form for NCG030000
Metal Fabrication
Click here for instructions
Complete, sign, scan and submit the DMR via the Stormwater NPDES Permit Data Monitoring Retort [DMR) Upload form within
30 days of receiving sampling results. Mail the original, signed hard copy of the DMR to the appropriate DEMLR Regional Office.
Certificate of Coverage No. NCG03 0 0 7 0
Facility Name: ABB Motor and Mechanical, Inc.
Person Collecting Samples: Reggie Reeves
Laboratory Name: Pace Analytical
Facility County: Buncombe I Laboratory Cert. No.: 40
Discharge during this period: ❑■ Yes ❑ No (if no, skip to signature and date)
Has your facility implemented mandatory Tier response actions for any benchmark exceedances? ❑■ Yes ❑ No
If so, which Tier (I, II, or III)? III
Analytical Monitoring Requirements for Outfalls with Industrial Activities — Benchmarks in (Red)
Parameter
Code
Parameter
Outfall B
Outfall C
Outfall D
Outfall E
Outfall F
N/A
Receiving Stream Class
Trout
Trout
Trout
Trout
Trout
N/A
Date Sample Collected MM/DD/YYYY
10/28/2020
10/28/2020
10/28/2020
10/28/2020
10/28/2020
46529
24-Hour Rainfall in inches
0.47
0,47
0.47
0.47
0.47
00552
Non -Polar Oil & Grease in mg/L (15)
< 5.0
< 5.0
< 5.0
< 5.0
< 5.0
C0530
TSS in mg/L (100-er 50*)
3.8
15.2
< 2.5
5.3
< 2.5
00400
pH in standard units (6.0-9.0)
7.1
7.5
7.4
7.1
6.7
NCOIL
New Motor/Hydraulic Oil Usage in
N/A
N/A
N/A
N/A
N/A
gal/month
01119
Copper, total recoverable in mg/L
< 0.005
0.0076
< 0.005
0.0165
< 0.005
(0.010 FW, 0T005-5UU)
01051
Lead, total recoverable in mg/ L
< 0.005
0.0096
< 0.005
< 0.005
< 0.005
01094
Zinc, total recoverable in mg/ L (0.126
0.181
0.112
0.0622
0.112 1
0.0221
FW, 049"W)
N/A
N/A
N/A
N/A
78141
Total Toxic Organics (TTO) in mg/L(1)
N/A
* Outfalls to Outstanding Resource Waters (ORW), High Quality Waters (HQW), Trout Waters (Tr) and Primary Nursery Areas (PNA)
have a benchmark TSS limit of SO mg/L. All other water classifications have a benchmark of 100 mg/L.
Notes (optional):
"I certify by my signature below, under penalty of law, that this document and all attachments were prepared under my direction or
supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information
submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for
gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am
aware that there are significant penalties for submitting false information, including the possibility of fines and imprisonment for
knowing violations."
it -)-?sue
Date
NCDEQ Division of Energy, Mineral and Land Resources
Stormwater Discharge Monitoring Report (DMR) Form for NCG030000
Metal Fabrication
Click here for instructions
Complete, sign, scan and submit the DMR via the Stormwater NPDE5 Permit Data Monitoring Report (DMR) Upload form within
30 days of receiving sampling results. Mail the original, signed hard copy of the DMR to the appropriate DEMLR Regional Office.
Certificate of Coverage No. NCG03 0 0 7 fl Person Collecting Samples: Reggie Reeves
Facility Name: ABB Motor and Mechanical, Inc. Laboratory Name: Pace Analytical
Facility County: Buncombe Laboratory Cert. No.: 40
Discharge during this period: U Yes U No (if no, skip to signature and date)
Has your facility implemented mandatory Tier response actions for any benchmark exceedances? ❑ Yes Q No
If so, which Tier (I, 11, or III)?
Analytical Monitoring Requirements for Outfalls with Industrial Activities — Benchmarks in (Red)
Parameter
Parameter
Outfall G
Outfall I
Outfall
Outfall
Outfall
Code
N/A
Receiving Stream Class
Trout
Trout
N/A
Date Sample Collected MM/DD/YYYY
10/28/2020
10/28/2020
46529
24-Hour Rainfall in inches
0.47
0.47
00552
Non -Polar Oil & Grease in mg/L (15)
8.1
< 5.0
C0530
TSS in mg/L (100-or 50*)
44.8
< 2.5
00400
pH in standard units (6.0-9.0)
6.9
6.9
NCOIL
New Motor/Hydraulic Oil Usage in
N/A
N/A
gal/month
01119
Copper, total recoverable in mg/L
0.0094
< 0.005
(0.010 FW, GAKM-M)
01051
Lead, total recoverable in mg/ L
0.006
< 0.005
(0.075 FW, 0.220 51011)
01094
Zinc, total recoverable in mg/ L (0.126
0.076
0.0489
FW, 04954W)
78141
Total Toxic Organics (TTO) in mg/L(1)
N/A
N/A
* Outfalls to Outstanding Resource Waters (ORW), High Quality Waters (HOW), Trout Waters (Tr) and Primary Nursery Areas (PNA)
have a benchmark TSS limit of 50 mg/L. All other water classifications have a benchmark of 100 mg/L.
Notes (optional):
"I certify by my signature below, under penalty of law, that this document and all attachments were prepared under my direction or
supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information
submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for
gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am
aware that there are significant penalties for submitting false information, including the possibility of fines and imprisonment for
knowing violations."
Signature of Permittee or D41egated Authorized Individual
I _
Date