HomeMy WebLinkAboutWQ0002376_BIMS Inspection Report_20201120Compliance Inspection Report
Permit: WQ0002376 Effective: 06/04/20 Expiration: 12/31/26 Owner : City of Reidsville
SOC: Effective: Expiration: Facility: City of Reidsville RLAP
County: Rockingham 230 W Morehead St
Region: Winston-Salem
Contact Person: Steven L Routh
Directions to Facility:
System Classifications: LA,
Primary ORC: Brent M Collins
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Reidsville NC 27320
Title: Director of Public Works Phone: 336-349-1070
Certification: 27651 Phone: 336-751-1441
NC0024881 City of Reidsville - Reidsville WWTP
Inspection Date: 11/05/2020
Entry Time 10:25AM Exit Time: 12:10PM
Primary Inspector: Jim J Gonsiewski Phone: 336-776-9704
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Land Application of Residual Solids (503)
Facility Status: Compliant ❑ Not Compliant
Question Areas:
▪ Miscellaneous Questions
II Sampling
▪ Transport
(See attachment summary)
▪ Record Keeping Treatment
▪ Land Application Site Pathogen and Vector Attraction
Page 1 of 5
Permit: WQ0002376 Owner - Facility: City of Reidsville
Inspection Date: 11/05/2020 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Inspection Summary:
On November 5, 2020 staff of the North Carolina Division of Water Resources Winston-Salem Regional Office (DWR)
performed an announced routine compliance inspection of the City of Reidsville's residuals land application program. This
inspection was conducted by DWR staff member Jim Gonsiewski. Mr. Brent Collins of EMA Resources was present during
this inspection. The inspection reflects compliance with the permit.
The inspection strated at the WWTP. Three 7.200-gallon tankers were used to transport residuals Observed one tanker
loading up residuals from the two 1,000,000-gallon concrete digesters. No spillage. No staining of the asphalt or tracking of
sludge out of the WWTP was observed.
Arrived at application field (NC-RC-005-1). A rain gauge was observed in the field. The terrain was slightly hilly with the
slopes ranging from 3% to 6%. The solids content in the residuals was 0.98%. The field was properly flagged. No runoff or
ponding of residuals from previous spreading was observed. Two 4,200 gallon tractor pulled spreaders were applying
residuals. The O&M plan and the permit were present. The O&M plan was adequate. Each truck also had an O&M plan and
maps.
The residual spreading was good. No additional run off or ponding was observed. Proper buffers were
maintained. No problems noted with the transfer of residuals from tankers to spreaders.
Page 2 of 5
Permit: WQ0002376 Owner - Facility: City of Reidsville
Inspection Date: 11/05/2020 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Distribution and Marketing
Land Application
Record Keeping
Is GW monitoring being conducted, if required?
Are GW samples from all MWs sampled for all required parameters?
Are there any GW quality violations?
Is GW-59A certification form completed for facility?
Is a copy of current permit on -site?
Are current metals and nutrient analysis available?
Are nutrient and metal loading calculating most limiting parameters?
a. TCLP analysis?
b. SSFA (Standard Soil Fertility Analysis)?
Are PAN balances being maintained?
Are PAN balances within permit limits?
Has land application equipment been calibrated?
Are there pH records for alkaline stabilization?
Are there pH records for the land application site?
Are nutrient/crop removal practices in place?
Do lab sheets support data reported on Residual Analysis Summary?
Are hauling records available?
Are hauling records maintained and up-to-date?
# Has permittee been free of public complaints in last 12 months?
Has application occurred during Seasonal Restriction window?
Comment:
Pathogen and Vector Attraction
a. Fecal coliform SM 9221 E (Class A or B)
Class A, all test must be <1000 MPN/dry gram
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
Fecal coliform SM 9222 D (Class B only)
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
b. pH records for alkaline stabilization (Class A)
c. pH records for alkaline stabilization (Class B)
Temperature corrected
d. Salmonella (Class A, all test must be < 3MPN/4 gram day)
Yes No NA NE
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
•
❑ ❑ ❑
❑ ❑ • ❑
▪ ❑ ❑ ❑
•
❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
Yes No NA NE
O 000
O 000
O 000
O 000
O 000
Page 3 of 5
Permit: WQ0002376 Owner - Facility: City of Reidsville
Inspection Date: 11/05/2020 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
e. Time/Temp on:
Digester (MCRT)
Compost
Class A lime stabilization
f. Volatile Solids Calculations
g. Bench -top Aerobic/Anaerobic digestion results
Comment:
Treatment
Check all that apply
Aerobic Digestion
Anaerobic Digestion
Alkaline Pasteurization (Class A)
Alkaline Stabilization (Class B)
Compost
Drying Beds
Other
Comment:
Sampling
Describe sampling:
Is sampling adequate?
Is sampling representative?
Comment:
Yes No NA NE
•
•
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Transport
Yes No NA NE
Is a copy of the permit in the transport vehicle? • ❑ ❑ ❑
Is a copy of the spill control plan in the vehicle? • ❑ ❑ ❑
Is the spill control plan satisfactory? • ❑ ❑ ❑
Does transport vehicle appear to be maintained? • ❑ ❑ ❑
Comment:
Land Application Site
Is a copy of the permit on -site during application events?
Is the application site in overall good condition?
Is the site free of runoff/ponding?
If present, is the application equipment in good operating condition?
Are buffers being maintained?
Are limiting slopes buffered?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 4 of 5
Permit: WQ0002376 Owner - Facility: City of Reidsville
Inspection Date: 11/05/2020 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
10% for surface application
18% for subsurface application
Are there access restrictions and/or signs?
Is the application site free of odors or vectors?
Have performance requirements for application method been met?
For injection?
For incorporation?
Does permit require monitoring wells?
Have required MWs been installed?
Are MWs properly located w/ respect to RB and CB?
Are MWs properly constructed (including screened interval)?
Is the surrounding area served by public water?
If Annual Report indicates overapplication of PAN, are wells nearby that may be impacted?
Are soil types consistent w/ Soil Scientist report/evaluation?
Is the water table greater than 173' bls.
Is application occurring at the time of the inspection?
Comment: See comments.
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ • ❑ ❑
❑ ❑ • ❑
❑ ❑ ❑ •
❑ • ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 5 of 5