Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on
November 4, 2020, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible Charge (ORC) of our
findings by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this report, please do
not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bellkncdenr.gov.
Sincerely,
DocuSigned by:
A14CC681 AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, DEQ
Enclosure:
Inspection Report
D-;� North Carolina Department of Environmental Quality I Division of Water Resources
EMooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR7H ORROLINA i
kmrl l m EnNromi W uwi` /`� 704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO022187 I11 121 20/11/04 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70LJ 71 I„ I 72 L71 74 79
I I I I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09:10AM 20/11/04
15/09/01
Paw Creek Terminal
410 Tom Sadler Rd
Exit Time/Date
Permit Expiration Date
Paw Creek NC 28130
11:00AM 20/11/04
20/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Bobby Regans/Operator Terminal//
Justin Chad Baker/ORC/704-399-3301/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Scott Dilling,410 Tom Sadler Rd Charlotte NC 28214/Complex Manager/704-399-3301)
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell Signed by: DWR/MRO WQ/704-663-1699 Ext.2192/ 11/12/2020
Be&
E�Docu`,�,'96D90=437-
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by: 11/17/2020
A14CC681 AF27425... Page#
NPDES yr/mo/day Inspection Type
NCO022187 I11 12I 20/11/04 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO022187 Owner -Facility: Paw Creek Terminal
Inspection Date: 11/04/2020 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The Division received the facility's permit renewal application on 12/11/19.
The last compliance evaluation inspection at this facility was performed by
Mecklenburg
Countv Stormwater Services staff on 7/11/18.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
Page# 3
Permit: NCO022187 Owner -Facility: Paw Creek Terminal
Inspection Date: 11/04/2020 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed during the inspection were organized and well maintained. Discharge
Monitoring Reports (eDMRs) were reviewed for the period October 2019 through Septembel
2020. No effluent limit violations were reported and all monitoring frequencies were correct.
The Terminal Manager is currently certifying and submitting the eDMRs; however, the ORC
should initiate certifying all future eDMRs. In addition, the ORC must ensure to document
the weekly NPDES visitations on all future eDMRs. Any operation & maintenance activities
associated with the on -site NPDES facilities should also be documented in a log book
maintained on -site.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑
# Is the facility using a contract lab? 0 ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑
Comment: The facilitv has contracted Eurofins TestAmerica (Certification #434) to Derform effluent
analyses.
Effluent samples are temporarily stored in a refrigerator prior to pick-up and shipment to the
contracted laboratory. The ORC and staff must ensure that the refrigerator's temperature is
measured and documented for every day the unit is used for sample storage to verify the
samples were being properly preserved at less than or equal to six degrees Celsius
(Reference: 40 CFR 136.3 Table II).
Effluent Sampling
Yes
No
NA NE
Is composite sampling flow proportional?
❑
❑
0 ❑
Is sample collected below all treatment units?
0
❑
❑ ❑
Is proper volume collected?
0
❑
❑ ❑
Is the tubing clean?
❑
❑
0 ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0 ❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑ ❑
representative)?
Comment: The subject permit requires effluent grab samples.
The ORC and staff must ensure that all effluent samples are preserved
(chemically
and
refrigerated) within fifteen minutes of sample collection (Reference: 40 CFR 136.3 Table II).
In addition, effluent oil & grease samples must be collected directly into the laboratory's
sample bottle (Reference: EPA Method 1664). No intermediate sample containers can be
used.
Page# 4
Permit: NCO022187 Owner -Facility: Paw Creek Terminal
Inspection Date: 11/04/2020 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: NPDES facilities appeared to be properly operated and well maintained. The secondary
containment dikes and valves are inspected daily and the product recovery in the oil/water
separator (SPCC tank) is checked twice per week. The recovered petroleum (oil/water
separator) is either reused on -site or removed by Hepaco and disposed at the
Heritage -Crystal Clean facility located in Concord, N.C. Groundwater is pumped through
two carbon tanks (operated in series) for the reduction of manganese prior to discharging
into the dike structure. The accumulated water in the dike is conveyed into a retention pond
prior to being discharged (via manually operated valve) through the discharge outfall.
Flow Measurement - Effluent
Yes
No
NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
M
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The calibrated in -line flow meter was placed into operation on 6/16/2020. The facili
contracts Sparling Instruments, LLC. to calibrate the flow meters annually.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
❑
❑
0
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The facility was not discharging at the time of the inspection. The manually operated
discharge valve was secured with lock and chain. The accumulated water inside the dike
appeared clear with no petroleum sheens.
Page# 5