Subject: Compliance Evaluation Inspection
Belmont WWTP
NPDES Permit No. NCO021181
Gaston County
Dear Mr. Webb:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at
the subject facility on January 19i 2017, by Ori Tuvia. Sandra Craft's cooperation during the site visit
was much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a
copy of the enclosed repot.
The main area of concern is that at the time of the inspection the facility did not have a copy
of the 2016 Annual Report. Once the Annual report please send me a copy for review via email.
If you any questions, please contact Ori Tuvia at (704) 235-2190, or via email at
ori.tuvia(a ncdenr.gov.
Cc: NPDES
MRO Files
Sincerely,
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, DEQ
Mooresville Regional Office
Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115
Phone: (704) 663.16991 Fax: (704) 663.60401 Customer Service:1-877-623-6748
Internet: www.ncwaterqual'4.org
United States Environmental Protection Agency
Forth Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES, yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 15 1 3 1 NCW21181 111 12 17/01/19 17 18 ICI 19 I g I 20 LJ
21111111 1111111 11 11 111 1111 1 1 11111 1111111 11 126
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67
1.0 70 J�j 71 L 72 LNJ 73LLJ74 75 LJ_U80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry rime/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:05AM 17/01/19
06/02/01
Belmont WWTP
298 Parkdale Rd
Exit Time/Date
Permit Expiration Date
Belmont NC 28012
12:25PM 17/01/19
10/06/30
Name(s) of Onsite Representative(s)/T'dEes(s)/Phone and Fax Number(s)
Other Facility Data
111
Sandra Marie Craft/ORCJ704-825-3791/
Name, Address of Responsible OffidaUT'dle/Phone and Fax Number
Contacted
Barry L Webb,PO Box 431 Belmont NC 280120431/City
Manager/704-825-5588/7048250514 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & MaintenancE Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checdists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phons and Fax Numbers Date
Od A Tuvia MRO WQ/1704-663-1699/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
I1�C-08rJQ • ev►R-' NR�
Page#
NPDES
31 NCO021181 I11
yr/mo/day Inspection Type
12 17/01/19 17 18 1 C 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO021181 Owner - Facility: Belmont WWTP
Inspection Date: 01/1912017 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires In 6 months or less). Has the permittee submitted a new
❑
❑
M
❑
application?
Is the facility as described in the permit?
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The subject permit expired on 6/30/2010: however. the Division received the permit renewal
application package on 1/5/2010. The facility continues to adhere to the requirements of this
permit until a new permit is reissued.
The'City implements an approved industrial pretreatment program.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
M
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. rag. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
❑
Are DMRs complete: do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
0
❑
❑
Comment: The records reviewed during the inspection were organized and well maintained. DMRs.
COC. ORC logs and process control data were reviewed for the period January
2016
through October 2016. At the time of the inspection the facility did not have a cop,
of f the
2016 Annual Report.
Page# 3
Permit: NC0021181 Owner -Facility:
Belmont wWTP
Inspection Date: 01/19/2017 Inspection Type: Compliance Evaluation
Record Keeping -
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters( excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees?
Yes No NA NE
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ M ❑
❑ ❑ ■ ❑
Comment: Influent and effluent analyses (including field) are performed by Shealy
Environmental
Services, Inc. (Certification #329). ETT Environmental, Inc. (toxicity) has also been
contracted to provide analytical support.
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
M
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
M
❑
❑
❑
Is the tubing clean?
N
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
❑
❑
❑
Comment: The sub)ect permit requires composite BOD and TSS influent samples. Aliquot sampling
collected was 152 ml.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
❑
Is sample collected below all treatment units?
❑
❑
❑
Is proper volume collected?
M
❑
❑
❑
Is the tubing clean?
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: The subject permit reauires composite and grab effluent samples. Aliquot sampling_
collected was 149 mi.
Weekly aliauot verfications are performed and documented on both samplers (influent_ and
effluent).
Page# 4
Permit: NCO021181 Owner - Facility: Belmont WWrP
Inspection Date: 01/19/2017 Inspection Type: Compliance Evaluation
Effluent Sampling `' Yes No NA NE
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and 0 ❑ ❑ ❑
sampling location)?
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? N ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable N ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Thelacility appeared to be properly operated and well maintained. The ORC and staff
incorporate a comprehensive process control program with all measurements being
Properly documented and maintained on -site.
Bar Screens
Yes No NA NE
Type of bar screen,
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
N
❑
❑
❑
Comment:
Grit Removal
Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
N
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment: Screenings and grit are disposed at the County Landfill
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting? ❑ N ❑ ❑
Page# 5
Permit: NCO021181 Owner - Facility: Belmont VUwTP
Inspection Date: 01/19/2017 Inspection Type: Compliance Evaluation
Flow Measurement - Influent
Yes No NA NE
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑ME].
Comment: The influent flow meter is calibrated quarterly and was last calibrated on 11/3/2016 by
Ken
Nash Company. Inc
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Yes No NA NE
Ext. Air
Surface
0❑ ❑❑
■ ❑ Cl ❑
❑ ❑ M ❑
■ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ M ❑
Comment: The facility is equipped with two aeration basins (inactive aertion basin need minor repairs):
however, only one aeration basin is used due to low influent flows. Sodium hydroxide is
added to the influent prior to the aeration basin to maintain appropriate alkalinity/aH levels._
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
N
❑
110
Is the site free of excessive buildup of solids in center well of circular clarifier?
M
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
M
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
M
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
0
❑
❑
❑
Comment: Both secondaries were operational and in service.
Page# 6
N
Permit: NCO021181
Inspection Date: 01/19/2017
Owner - Facility: Belmont WWTP
Inspection Type: Compliance Evaluation
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
❑
❑
❑
Are pumps operational?
❑
❑
❑
Are there adequate,spare parts and supplies on site?
0
❑
❑
❑
Comment:
Disinfection -Gas
Yes No NA NE
Are cylinders secured adequately?
0
❑
❑
❑
Are cylinders protected from direct sunlight?
0
❑
❑
❑
Is there adequate reserve supply of disinfectant?
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
1111
Is the contact chamber free of growth, or sludge buildup?
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Does the Stationary, Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)?
0
❑
❑
❑
If yes, then is there,a Risk Management Plan on site? N ❑ . ❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000- -. 1000-0000-7244
If yes, then when was the RMP last updated? 03/01/2014
Comment: The chlorination and dechlorination systems are serviced annually by a contracted
company.
De -chlorination Yes No NA NE
Type of system.? Gas
Is the feed ratio proportional to chlorine amount (1 to 1)? N ❑ ❑ ❑
Is storage appropriate for cylinders? 0 ❑ 0 ❑
# Is de -chlorination substance stoned away from chlorine containers? E ❑ ❑ ❑
Comment:
Are the tablets the proper size and type? ❑ ❑ 0 ❑
Are tablet de-chloriI nators operational? ❑ ❑ N ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? 0 ❑ ❑ ❑
Is flow meter calibrated annually? ❑ ❑ ❑
Page# 7
Permit: NCO021181 Owner -Facility: Belmont WWTP
Inspection Hate: 01/19/2017 Inspection Type: Compliance Evaluation
Flow Measurement - Effluent- Yes No NA NE
Is the flow meter operational? 0 ❑ ❑ ❑
(If units are separated) Does the chart recorder match the flow meter? ❑ ❑ M ❑
Comment: The effluent flow meter is calibrated auarterly and was last calibrated on 11/3/2016 by Ken
Nash Company, Inc
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? 0 ❑ ❑ - ❑
Are the receiving water free of foam other than trace amounts and other debris? N ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ N ❑
Comment: The effluent appeared clear with no floatable solids or foam.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
❑
❑
❑
Is the site free of excessive foaming in the tank?
M
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: The facility is equipped with two aerobic digestors and a sludge holding
tank. The drving
beds have been taken out of service for several years. Digested bio-solids are land applied
by a contract company under the authority of Permit No. WQ0003281.
Standby Power
Yes No NA NE
Is automatically activated standby power available?
M
❑
❑
❑
Is the generator tested by interrupting primary power source?
0
❑
❑
❑
Is the generator tested under load?
0
❑
❑
❑
Was generator tested & operational during the inspection?
0
❑
❑
❑
Do the generator(s) have adequate capacity to operate the entire,wastewater site?
0
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
0
❑
❑
❑
Is the generator fuel level monitored?
M
❑
❑
❑
Comment: The facility is equipped with one standby generator that is tested weekly and
put under load
_
monthly. The City also participates in the load management program. Generator last
maintenance check was on 7/25/2016.
Page# 8