HomeMy WebLinkAboutnc0079057_Inspection_20201027ROY COOPER Governor MICHAEL S. REGAN Secretary S. DANIEL SMITH Director James Ayers Town of Manteo PO Box 246 Manteo, NC 27954-0246 NORTH CAROLINA Environmental Quality November 17, 2020 SUBJECT: Compliance Inspection Report Manteo WWTP NPDES WW Permit No. NC0079OS7 Dare County Dear Mr. Ayers: The North Carolina Division of Water Resources conducted an inspection of the Manteo WWTP on 10/27/2020. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0079057. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact Paul Mays with the Water Quality Regional Operations Section in the Washington Regional Office at 252-946-6481 or via email at paul.mays@ncdenr.gov. Sincerely, Pay.(, "S Paul Mays, Environmental Specialist 1 Water Quality Regional Operations Section Washington Regional Office Division of Water Resources Cc: Laserfiche DEQ�` v. , � , -% . r in - z n _,aae sv » se tts 1 V_st.,, . z*sus United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 I 3 I N00079057 I11 121 20/10/27 I17 181r�1 191 1� 201 I 211 I I I I I I I I I I I LJ I I I I I I I I I I I I I I I I I I I I I I I=I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating 81 QA ---------------------- Reserved ------------------- 67I� I 72 1 N I 731 174 75I I I I I I I80 701 LJ I 71I liL J I Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES Dermit Number) 10:30AM 20/10/27 19/07/01 Manteo WWTP Exit Time/Date Permit Expiration Date 710 Bowsertown Rd Manteo NC 27954 11:30AM 20/10/27 23/12/31 Name(s) of Onsite Representative(s)/Ttles(s)/Phone and Fax Number(s) Other Facility Data w Joshua J O'Brien/ORC/252-473-35131 Name, Address of Responsible OfficialMtle/Phone and Fax Number Contacted Nathan Pharr,PO Box 246 Manteo NC 279540246//252-305-3491/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenar E Records/Reports Sludge Handling Dispo: E Facility Site Review Effluent/Receiving Wate Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Paul M Mays DWRANARO WQ/252-948-3940/ Signature of Management QA Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES NCO079057 yr/mo/day Inspection Type 1 12I 20/10/27 17 18 C, (Cont.) Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On 10:30 am on 10/27/2020 Paul Mays from the Division of Water Resources with the Division of Water Resources conducted a compliance evaluation of Manteo WWTP. The facility was fount to be compliant with NPDES permit #NC0079057 and below are the findings of the compliance evaluation: The facility and grounds were well maintained and clean. The facility has a contract lab onsite (Envirochem Services, Inc). Influent sampler was at 5 degrees Celsius and a 350ml sample was obtained every hour. Effluent sampler was at 4 degrees Celsius and a 600ml sample was obtained every hour. DO was kept between 1.5mg/I to 1.8mg/I in the oxidation ditch, in the final train according to the ORC at the time of the visit. Where DO was observed during the inspection it was 1.98mg/I. MLSS in oxidation ditch was currently at 3200 according to ORC. They have abundant spare parts for many critical parts of the plant onsite. The sludge blanket was only 1 ft in each clarifier. The effluent meter was calibrated on 10/06/2020 by Delta Systems. Outfall line is offshore and has a marker about 300-400 yards offshore. Effluent looks great and completely clear. The facility uses 12.5% Sodium Hypochlorite. The Facility uses Sodium Bisulfite for de -chlorination. The July 2020 DMR was spot checked with corresponding lab data. No discrepancies were found. All records that were requested for the inspection were readily available, organized and maintained as required by permit. Page# Permit: NCO079057 Owner -Facility: Manteo WWTP Inspection Date: 10/27/2020 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? M ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The facility and grounds were well maintained and clean. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? M ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? M ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? M ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? M ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatic ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification' M ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? M ❑ ❑ ❑ Page# 3 Permit: NCO079057 Inspection Date: 10/27/2020 Record Keeping Owner -Facility: Manteo WWTP Inspection Type: Compliance Evaluation Facility has copy of previous year's Annual Report on file for review? Yes No NA NE ■ ❑ ❑ ❑ Comment: The July 2020 DMR was soot checked with corresponding lab data. No discrepancies were found. All records that were requested for the inspection were readily available, organized and maintained as required by permit. Bar Screens Yes No NA NE Type of bar screen a. Manual b.Mechanical Are the bars adequately screening debris? ■ ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screening in compliance? M ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: screeningsgo to a lined landfill. Grit Removal Yes No NA NE Type of grit removal a.Manual ❑ b.Mechanical Is the grit free of excessive organic matter? 0 ❑ ❑ ❑ Is the grit free of excessive odor? 0 ❑ ❑ ❑ # Is disposal of grit in compliance? M ❑ ❑ ❑ Comment: grit goes to a lined landfill Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ❑ Comment: The facility has a contract lab onsite (Envirochem Services Inc). Influent sampler was at 5 degrees Celsius and a 350ml sample was obtained every hour. Effluent sampler was at 4 degrees Celsius and a 600ml sample was obtained every hour. Page# 4 Permit NCO079057 Inspection Date: 10/27/2020 Oxidation Ditches Are the aerators operational? Are the aerators free of excessive solids build up? # Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Owner -Facility: Manteo WWTP Inspection Type: Compliance Evaluation Are settleometer results acceptable (> 30 minutes)? Is the DO level acceptable?(1.0 to 3.0 mg/1) Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes) Yes No NA NE ■ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ Comment: DO was kept between 1.5mg/I to 1.8mg/I in the final train according to the ORC at the time of the visit. Where DO was observed during the inspection it was 1.98mg/I. MLSS in oxidation ditch was currently at 3200 according to ORC. Pumin-RASMAS Yes No NA NE Are pumps in place? 0 ❑ ❑ ❑ Are pumps operational? 0 ❑ ❑ ❑ Are there adequate spare parts and supplies on site? 0 ❑ ❑ ❑ Comment: They have abundant spare parts for many critical parts of the plant onsite. Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately Y<of the sidewall depth) Comment: The sludge blanket was only 1 ft in each clarifier. Flow Measurement - Effluent # Is flow meter used for reporting? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE ■ ❑ ❑ ❑ Page# 5 Permit: NCO079057 Owner -Facility: Manteo WWTP Inspection Date: 10/27/2020 Inspection Type: Compliance Evaluation Flow Measurement - Effluent Yes No NA NE Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: The effluent meter was calibrated on 10/06/2020 by Delta Systems. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? M ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ❑ Comment: Outfall line is offshore and has a marker about 300-400 yards offshore. Sand Filters (Low ratel Yes No NA NE (If pumps are used) Is an audible and visible alarm Present and operational? 0 ❑ ❑ ❑ Is the distribution box level and watertight? 0 ❑ ❑ ❑ Is sand filter free of ponding? ❑ ❑ M ❑ Is the sand filter effluent re -circulated at a valid ratio? ❑ ❑ M ❑ # Is the sand filter surface free of algae or excessive vegetation? M ❑ ❑ ❑ # Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1) ❑ ❑ ❑ Comment: Effluent looks great and completely clear Disinfection -Liquid Yes No NA NE Is there adequate reserve supply of disinfectant? 0 ❑ ❑ ❑ (Sodium Hypochlorite) Is pump feed system operational? N ❑ ❑ ❑ Is bulk storage tank containment area adequate? (free of leaks/open drains) 0 ❑ ❑ ❑ Is the level of chlorine residual acceptable? 0 ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? N ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? 0 ❑ ❑ ❑ Comment: The facility uses 12.5% Sodium Hypochlorite. De -chlorination Yes No NA NE Type of system ? Liquid Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? ❑ ❑ N ❑ Page# 6 Permit: NC0079057 Inspection Date: 10/27/2020 Owner - Facility: Manteo WWTP Inspection Type: compliance Evaluation De -chlorination # Is de -chlorination substance stored away from chlorine containers? Are the tablets the proper size and type? Comment: The Facility uses Sodium Biosulfite for de -chlorination. Are tablet de -chlorinators operational? Number of tubes in use? Comment: Aerobic Digester Is the capacity adequate? Is the mixing adequate? Is the site free of excessive foaming in the tank? # Is the odor acceptable? # Is tankage available for properly waste sludge? Comment: Yes No NA NE ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ■ ■ Yes No NA NE ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ • ❑ ❑ ❑ • ❑ ❑ ❑ Page# 7