HomeMy WebLinkAboutNC0036277_Compliance Evaluation Inspection_20201013 (2)Division of Water Resources
October 9, 2020
MEMORANDUM
To: Corey Basinger
Water Quality Regional Opera 'ans, MRO
Through: Cindy A. Moore
Supervisor, Aquatic Toxicology Branch (ATB)
From: Lorimar S. Henning
Environmental Specialist Il, Aquatic Toxicology Branch (ATB)
Subject: Whole effluent toxicity test results
McDowell Creek WWTP
NPDES Permit # NC0036277/001
Mecklenburg County
The aquatic toxicity test using flow -proportional composite samples of effluent discharged from
the McDowell Creek WWTP has been completed. McDowell Creek WWTP has a permitted
effluent discharge of 12.0 million gallons per day (MGD) entering McDowell Creek (7Q10 of 1.8
CFS). Whole effluent samples were collected on September 29 and October 1 by Wes Bell and
facility representatives Craig Coleman and Daniel Matias for use in a chronic Ceriodaphnia dubia
pass -fail toxicity test. The test passed. Toxicity test information follows.
Test Type 3-Brood Ceriodaphnia dubia chronic pass -fail
Test Result
Pass
Test Concentrations
90%
Control Survival
100%
Control Mean Reproduction
18.5 neonates
Test Treatment Survival
91.7%
Treatment Mean Reproduction
26.7 neonates
First Sample pH
7.97 SU
First Sample Conductivity
531 micromhos/cm
First Sample Total Residual Chlorine
0.03 mg/L
Second Sample pH
7.66 SU
Second Sample Conductivity
582 micromhos/cm
Second Sample Total Residual Chlorine
0.04 mg/L
Test results for the above samples indicate that the effluent would not be predicted to have
water quality impacts. These samples were split and tested by ETT Environmental, Inc. The
chronic Ceriodaphnio dubia pass/fail test run by ETT resulted in a pass. Please contact us if you
have any questions or if further effluent toxicity monitoring is desired. We may be reached at
(919) 743-8401.
Basin: Catawba
cc: Wes Bell (MRO)
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
Ms. Jacqueline A. Jarrell, P.E.
Operations Chief
Environmental Management Division
Charlotte Water
5100 Brookshire Blvd.
Charlotte, North Carolina 28216
Dear Ms. Jarrell:
NORTH CAROLINA
Environmental Quality
October 13, 2020
Subject: Chronic Toxicity Test Results
McDowell Creek WWTP
NPDES Permit No. NCO036277
Mecklenburg County
Enclosed is a copy of the toxicity test results relative to the samples collected (split) at the subject facility on September 29
and October 1, 2020, by Charlotte Water staff and Mr. Wes Bell of this Office. Effluent samples were collected for use in a
chronic Ceriodaphnia dubia pass -fail toxicity test. The test Passed utilizing these samples. Please inform the facility's
Operator -in -Responsible Charge (ORC) of our findings by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this report, please do
not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bell(a ncdenr.gov.
Sincerely,
DocuSigned by:
A14CC681 AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, DEQ
Enclosure:
Toxicity Test Results
�� Office
Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR7H ORROLINA i
kmrlaam m EnNromi Wuwi\ /`� 704.663.1699
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
Ms. Jacqueline A. Jarrell, P.E.
Operations Chief
Environmental Management Division
Charlotte Water
5100 Brookshire Blvd.
Charlotte, North Carolina 28216
Dear Ms. Jarrell:
NORTH CAROLINA
Environmental Quality
October 8, 2020
Subject: Compliance Bio-monitoring Inspection
McDowell Creek WWTP
NPDES Permit No. NCO036277
Mecklenburg County
Enclosed is a copy of the Compliance Bio-monitoring Inspection Report for the inspection conducted at the subject facility
on September 29, 2020, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible Charge (ORC)
of our findings by forwarding a copy of the enclosed report. The results of the effluent chronic toxicity tests performed by the
Division's Aquatic Toxicity Unit will be forwarded under separate cover.
The report should be self-explanatory; however, should you have any questions concerning this report, please do
not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bell@ncdenr.gov.
Sincerely,
DocuSigned by:
44"HPu�- . for
F161 FB69A2D84A3...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, DEQ
Enclosure:
Inspection Report
�� Office
Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR7H ORROLINA i
kmrlaam m EnNromi Wuwi\ /`� 704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO036277 I11 121 20/09/29 I17 18LB] 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 701d I 71 l� I 72 I r., I 71 I 74 79 I I I I I I I80
L—I L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09:15AM 20/09/29
19/12/01
McDowell Creek WWTP
4901 Neck Rd
Exit Time/Date
Permit Expiration Date
Huntersville NC 28078
11:57AM 20/09/29
24/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Darrell Victor Dewitt/ORC/704-361-0611/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Jacqueline A Jarrell,5100 Brookshire Blvd Charlotte NC 28216/Operations
Chief/704-336-4460/7043365081 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell Docusigned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 10/7/2020
Z(Jra Be&
A61696D90CC3437...
Docusigned by: Date
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numb[X-�
Andrew Pitner DWR/MRO WQ/704-663-1699 Ext.2180/ H P44-ft 10.8.2020
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0036277 I11 12I 20/09/29 117 18 IBI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On -site Representatives:
The following Charlotte Water personnel were in attendance during the inspection: Mr. Darrel DeWitt,
Mr. Tony Spinelli and Mr. Doug Wise.
Page#
Permit: NCO036277 Owner -Facility: McDowell Creek WWTP
Inspection Date: 09/29/2020 Inspection Type: Bioassay Compliance
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Charlotte Water implements a Division approved Industrial Pretreatment Program.
The last compliance evaluation inspection at this facility was performed by
DWR staff on
0/11C/.14
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The records reviewed during the inspection were organized and well maintained. Discharge
Monitoring Reports (eDMRs) were reviewed for the period August 2019 through July 2020.
No effluent monitoring violations were reported and all monitoring frequencies were correct.
Page# 3
Permit: NCO036277
Inspection Date: 09/29/2020
Owner -Facility: McDowell Creek WWTP
Inspection Type: Bioassay Compliance
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
Comment: Influent and effluent analyses (including field) are performed under Charlotte Water's
Environmental Services Laboratory (Certification #192). ETT Environmental and R&A Labs
have also been contracted to Derform chronic toxicitv analvses.
Influent Sampling
Yes
No
NA NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
E
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: The subject permit requires influent CBOD and TSS composite samples. Samplers are
checked daily (each shift) and aliquot verifications are performed monthly (at a minimum).
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: The subject permit requires grab and composite effluent samples. Samplers are checked
daily (each shift) and aliquot verifications are performed monthly (at a minimum).
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, an( 0 ❑ ❑ ❑
sampling location)?
Page# 4
Permit: NCO036277
Inspection Date: 09/29/2020
Owner -Facility: McDowell Creek WWTP
Inspection Type: Bioassay Compliance
Upstream / Downstream Sampling
Yes
No
NA
NE
Comment:
Operations & Maintenance
Yes
No
NA
NE
Is the plant generally clean with acceptable housekeeping?
0
❑
❑
❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
0
❑
❑
❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facilitv was beina DroDerIv ODerated and well maintained.
Charlotte Water staff incorporate a commendable process control program with all
measurements being documented and maintained on -site.
In-depth operation and maintenance records were also being maintained on -site. The facilit,
is equipped with a SCADA System that is accessible at nine locations throughout the
wastewater facility.
Odor control systems are connected to the 1.3 MG equalization day tank and influent pump
station.
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
❑
❑
0
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment: The facility is equipped with a 1.3 MG equalization day tank and two additional equalization
basins (7 MG and 6 MG).
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Page# 5
Permit: NCO036277 Owner -Facility: McDowell Creek WWTP
Inspection Date: 09/29/2020 Inspection Type: Bioassay Compliance
Grit Removal Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
0 ❑ ❑ ❑
Is the grit free of excessive odor?
0 ❑ ❑ ❑
# Is disposal of grit in compliance?
0 ❑ ❑ ❑
Comment: Screenings and grit are disposed by a contracted company at the CMS Landfill in Cabarrus
County.
Flow Measurement - Influent
Yes
No
NA
NE
# Is flow meter used for reporting?
❑
0
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The influent flow meter is calibrated twice per year and was last calibrated on 4/18/2020
Charlotte Water's Electrical & Instrumentation Division.
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Primary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 6
Permit: NCO036277
Inspection Date: 09/29/2020
Primary Clarifier
Is the site free of excessive floating sludge?
Owner -Facility: McDowell Creek WWTP
Inspection Type: Bioassay Compliance
Is the drive unit operational?
Is the sludge blanket level acceptable?
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
Comment: Two of the five primaries were in service.
Nutrient Removal
# Is total nitrogen removal required?
# Is total phosphorous removal required?
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
Type Biological
# Is chemical feed required to sustain process? ❑ ❑ 0 ❑
Is nutrient removal process operating properly? 0 ❑ ❑ ❑
Comment: The facility has two five (5) stage BNR treatment trains (parallel) currently in service.
Acetic acid and/or cola syrup is added as a carbon supplement.
Chemical Feed
Yes
No
NA
NE
Is containment adequate?
0
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Are backup pumps available?
0
❑
❑
❑
Is the site free of excessive leaking?
E
❑
❑
❑
Comment:
Aeration Basins
Yes
No
NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0
❑
❑
❑
Comment: Lime slurry is added to maintain appropriate alkalinity/pH levels.
Page# 7
Permit: NCO036277
Inspection Date: 09/29/2020
Owner -Facility: McDowell Creek WWTP
Inspection Type: Bioassay Compliance
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: Two of four secondaries were in service. One of the secondaries was currently bein
rehabbed.
Pumps-RAS-WAS
Yes
No
NA NE
Are pumps in place?
E
❑
❑ ❑
Are pumps operational?
0
❑
❑ ❑
Are there adequate spare parts and supplies on site?
0
❑
❑ ❑
Comment:
Filtration (High Rate Tertiary)
Yes
No
NA
NE
Type of operation:
Down flow
Is the filter media present?
0
❑
❑
❑
Is the filter surface free of clogging?
0
❑
❑
❑
Is the filter free of growth?
0
❑
❑
❑
Is the air scour operational?
0
❑
❑
❑
Is the scouring acceptable?
0
❑
❑
❑
Is the clear well free of excessive solids and filter media?
0
❑
❑
❑
Disinfection - UV
Yes
No
NA
NE
Are extra UV bulbs available on site?
0
❑
❑
❑
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
0
❑
❑
❑
Page# 8
Permit: NCO036277 Owner -Facility: McDowell Creek WWTP
Inspection Date: 09/29/2020 Inspection Type: Bioassay Compliance
Disinfection - UV Yes No NA NE
Is transmittance at or above designed level?
0
❑
❑
❑
Is there a backup system on site?
0
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment:
Flow Measurement - Effluent
Yes
No
NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The effluent flow meter is calibrated twice per year and was last calibrated on 4/18/2020 by
Charlotte Water's Electrical & Instrumentation Division.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: The effluent aDDeared clear with no floatable solids or foam. The receivina stream did not
appear to be negatively impacted.
DWR and Charlotte Water staff split effluent chronic toxicity samples on 9/29/2020 and
10/1/2020. The results of the effluent chronic toxicity tests performed by DWR's Aquatic
Toxicity Unit will be forward under separate cover.
Anaerobic Digester
Type of operation:
Is the capacity adequate?
# Is gas stored on site?
Is the digester(s) free of tilting covers?
Is the gas burner operational?
Is the digester heated?
Is the temperature maintained constantly?
Is tankage available for properly waste sludge?
Yes No NA NE
Fixed cover
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
Comment: The facility is equipped with five digesters (4 — primary/fixed cover and 1 — storage/floating
cover).
Page# 9
Permit: NCO036277
Inspection Date: 09/29/2020
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Owner -Facility: McDowell Creek WWTP
Inspection Type: Bioassay Compliance
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: The facility is equipped with two gravity belt thickeners and two belt presses (all operational)
One thickener and belt press was in service at the time of the inspection.
Dewated bio-solids are land applied by a contracted company (Synagro) under the authority
of Permit No. WQ0000057.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: The facility is equipped with two backup generators. Generators are placed under load
monthly and serviced by a contracted company (Cummings) quarterly. The facility also
activates the generator(s) prior to thunder storms (storm avoidance).
Page# 10