HomeMy WebLinkAboutNC0041181_Compliance Evaluation Inspection_20130116 United States Environmental Protection Agency Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 INI 2 15I 31 NCO041181 111 121 13/01/16 117 18I S I 19I S I 201
I
Remarks
211 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 116
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ---------------------------Reserved----------------------
67 I 169 70121 711 I 721 N I 73I I 174 751 I I I I I I 1 80
Section B: Facility Data I_I_I
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number)
10:45 AM 13/01/16 08/11/01
Happy Valley Elementary School
1350 Yadkin River Rd Exit Time/Date Permit Expiration Date
Lenoir NC 28645 11:10 AM 13/01/16 13/10/31
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Jeff Church,1914 Hickory Blvd Lenoir NC 28645//828-728-8407/8287280012 Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations&Maintenance 0 Records/Reports
Self-Monitoring Program 0 Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Linda S Wiggs ARO WQ//828-296-4500 Ext.4653/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type (cant.
1
3 I NC0041181 111 12I 13/01/16 117
18I S 1
Section D: Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
The treatment units (sand filter beds and pipes) appear to need work. The distribution pipes do not appear
to be functioning optimally.
The sand filter bed needs work. Only portions of the beds are treating the wastewater. The ponding
occurring at the time of the inspection was not acceptable.
These treatment units should be evaluated and repaired as needed.
Effluent Sampling Results: BOD 12 mg/I, TSS 6.3 mg/1
Fortunately the effluent samples were compliant. However, the maintenance work noted above will likely be
needed soon to avoid effluent violations.
The septic tank is pumped annually which appears to be a good maintenance practice and is assisting in
keeping the sand filter beds from failing.
Page# 2
Permit: NCO041181 Owner-Facility: Happy Valley Elementary School
Inspection Date: 01/16/2013 Inspection Type: Compliance Sampling
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ 0 0 0
Does the facility analyze process control parameters,for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■
Judge, and other that are applicable?
Comment: The facility housekeeping is not an issue. However, O&M needs attention.
See summary.
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application? rl ❑ ■ ❑
Is the facility as described in the permit? ■ rl El 0
#Are there any special conditions for the permit? rl ■ El ❑
Is access to the plant site restricted to the general public? ■ 0 0 0
Is the inspector granted access to all areas for inspection? ■
Comment: Permit expires in October. The permittee should keep an eye out for
renewal notice early this year.
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational? fl rl ■ rl
Is septic tank pumped on a schedule? ■ ❑ fl ❑
Are pumps or syphons operating properly?
nn ■ n
Are high and low water alarms operating properly? I] ❑ ■ 11
Comment: See summary.
Sand Filters (Low rate) Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational? 0 0 ■ 0
Is the distribution box level and watertight? I] ❑ ❑ ■
Is sand filter free of ponding? ❑ ■ ❑ ❑
Is the sand filter effluent re-circulated at a valid ratio? El 0 ■ 0
#Is the sand filter surface free of algae or excessive vegetation? ❑ ■ ❑ ❑
#Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1) 0 ❑ ■ ❑
Comment: The sand filter beds are in need of attention. There is too much ponding,
the pipes may not be properly laid. Work needs to be performed on these treatment
units.
Page# 3