HomeMy WebLinkAboutSW3201002_7-Eleven Long Ferry Road SIA - 201020_20201022 7-ELEVEN LONG FERRY ROAD Stormwater Impact Analysis and Final Design of Stormwater Management Facility STORMWATER IMPACT ANALYSIS creating experiences through experience 3430 Toringdon Way, Suite 110, Charlotte, NC 28277 / 704. 527. 0800 GENERAL DESCRIPTION Located in Rowan County at the south-west corner of the intersection of Long Ferry Road and Front Creek Road, is a proposed 7-Eleven convenience store and fuel station. The existing site consists of grass and existing impervious area. Proposed development on this site will consist of a 7-Eleven convenience store and fuel station, along with the associated parking lot, sidewalks, utility improvements, and one stormwater control measure. The proposed development is located within the Yadkin River basin with stormwater runoff from the proposed development draining into Town Creek (Class C – index number 12-115-3). This development is located within Rowan County and as a result the proposed stormwater management on this site shall meet the minimum design criteria of NCDEQ: NCDEQ Design Standards A. Development Standards For High Density Projects (per 15A NCAC 02H .1003) (a) SCMs shall be designed, constructed, and maintained so that the project achieves either “runoff treatments” or “runoff volume match”. (b) When new built-upon area is added to existing development or existing development is replaced with new built-upon area, only the area of the next increase shall be subject to this Section. (c) SCMs shall meet the relevant MDC. 1. Storm Water Quality Treatment and Volume Match Sand filters are designed to treat 0.75 times the design volume (discounted volume). 2. Storm Water Quality Treatment All structural storm water treatment systems used to meet these requirements shall be designed to have minimum of 85% average annual removal for Total Suspended Solids. 3. Storm Water Treatment System Design General engineering design for the proposed sand filter is based on the MDC set forth in the NCDEQ Stormwater Design Manual. 4. Storm Water Peak Control Peak control is not required. To meet the above requirements, one sand filter is proposed to treat the net increase of impervious area for the proposed development. Please refer to the appropriate section of this report for additional information. STORMWATER IMPACT ANALYSIS creating experiences through experience 2 of 2 CALCULATION METHODOLOGY > Rainfall data for the analysis was taken from the most current data available from the National Oceanic and Atmospheric (NOAA) Precipitation Frequency Data Server website. > Using maps contained within the Rowan County Soil Survey, the on-site soils were determined to be hydrologic soil group (HSG) ‘B’. > A composite SCS Curve Number was calculated for both the pre- and post-development condition for each sub-basin using SCS curve numbers and land cover conditions. Land cover conditions for the pre-development condition were taken from available survey and GIS information. Land cover conditions for the post-development condition were taken from the proposed development plan. > The time of concentration was calculated using SCS TR-55 (Segmental Approach, 1986). The Tc flow path was divided into three segments: overland flow, concentrated flow, and channel flow. The travel time was then computed for each segment, from which the overall time of concentration was determine by taking the sum of each segmental time. > PondPack Version V8i was used in determined the post-development peak flow rate for the 100- year storm event to check for overtopping, as well as routing calculations for the proposed stormwater control measure. > The proposed stormwater control measure was designed in accordance with the Minimum Design Criteria (MDC) standards set forth in the NCDEQ Stormwater Design Manual. DISCUSSION OF RESULTS Water Quality Requirements: The proposed facility has been designed in accordance with the Minimum Design Criteria (MDC) standards set forth in the NCDEQ Stormwater Design Manual. The proposed facility will provide the required 85% TSS removal. CONCLUSION If the development on this tract is built as proposed within this report, then the requirements set forth in NCDEQ’s Post-Construction Stormwater Ordinance will be met. However, modifications to the proposed development may require that this analysis be revised. Some modifications that would require this analysis to be revised include: > The proposed site impervious surface exceeds the amount accounted for in this report. > The post-development watershed breaks change significantly from those used to prepare this report. The above modifications may result in the assumptions within this report becoming invalid. The computations within this report will need to be revisited if any of the above conditions become apparent as development of the proposed site moves forward. 4 SITE PRECIPITATION DATA 1 SUMMARY OF RESULTS 2 MISCELLANEOUS SITE INFORMATION 3 WATERSHED SOILS INFORMATION 5 PRE-DEVELOPMENT HYDROLOGIC CALCULATIONS 6 POST-DEVELOPMENT HYDROLOGIC CALCULATIONS 7 STORMWATER CONTROL MEASURE A DESIGN CALCULATIONS 7-ELEVEN LONG FERRY ROAD CPR-20000 SUMMARY OF RESULTS Project Name: 7-Eleven - Long Ferry Road Date: 10/20/2020 Project Number:CPR-20000 Calculated By: J. Woodard, PE STORMWATER CONTROL MEASURE A SUMMARY Design Drainage Area =0.90 acres Design Impervious Area =0.70 acres % Impervious =77.7% Water Quality Volume dis =1,667 cf Top of Dam =706.50 ft Riser =4'x4'(internal dimensions) Riser Elevation =705.00 ft Barrel Diameter =15 in Invert In =699.15 ft Invert Out =697.25 ft Length =76 ft % Slope =2.49% STORMWATER CONTROL MEASURE A ROUTING RESULTS Inflow Outflow Max WSE Freeboard Return Period [cfs][cfs][ft][ft] WQV 1.03 0.03 703.66 2.84 100-Year 6.78 6.24 705.22 1.28 SUMMARY OF RESULTS 7-ELEVEN LONG FERRY ROAD CPR-20000 MISCELLANEOUS SITE INFORMATION Esri, HERE, Garmin, (c) OpenStreetMap contributors, NC Center forGeographic Information & Analysis 0 2,000 4,0001,000 Feet1 inch = 2,000 feet ¯7-ELEVEN LONG FERRY ROAD SITE AERIAL MAPPROJECT #: CPR-2000ROWAN COUNTY, NORTH CAROLINA Copyright:© 2013 National Geographic Society, i-cubed 0 2,000 4,0001,000 Feet1 inch = 2,000 feet ¯7-ELEVEN LONG FERRY ROAD USGS TOPO MAPPROJECT #: CPR-20000ROWAN COUNTY, NORTH CAROLINA 2012 North Carolina Integrated Report 10-digit Watershed 0304010303 High Rock LakeYadkin-Pee Dee River Basin AU Number Name Description Length or Area Units Classification Category Category Rating Use Reason for Rating Parameter Year > 12-117-(3)Second Creek Arm of High Rock Lake From a point 1.7 miles downstream of Rowan County SR 1004 to High Rock Lake 894.9 FW Acres WS-IV,B 5> Not Rated Aquatic Life Potential Standards Viol High Water Temperature3a Impaired Aquatic Life Standard Violation Chlorophyll a5 2008 Not Rated Aquatic Life Potential Standards Viol Turbidity3a Impaired Aquatic Life Standard Violation High pH5 2008 12-117-2 Second Creek From source to Second Creek Arm of of High Rock Lake, Yadkin River 13.5 FW Miles C 2> Supporting Aquatic Life Good-Fair Bioclassificati Ecological/biological Integrity FishCom1 Supporting Aquatic Life Good Bioclassification Ecological/biological Integrity Benthos1 12-117-2ut10 UT SECOND CR Source to SECOND CR 2.8 FW Miles 2> Supporting Aquatic Life Not Impaired Bioclassific Ecological/biological Integrity Benthos1 12-117-2ut33 UT SECOND CR Source to SECOND CR 3.7 FW Miles 3> Not Rated Aquatic Life Not Rated Bioclassificati Ecological/biological Integrity Benthos3a 12-digit Subwatershed 030401030301 Town of Spencer-Headwaters Crane Creek 12-115-3 Town Creek From source to Crane Creek 15.4 FW Miles C 5> Impaired Aquatic Life Fair Bioclassification Ecological/biological Integrity FishCom5 1998 Impaired Aquatic Life Fair Bioclassification Ecological/biological Integrity Benthos5 1998 Supporting Recreation No Criteria Exceeded Fecal Coliform (recreation)1 12-digit Subwatershed 030401030305 Yadkin River-High Rock Lake Monday, March 25, 2013 Page 525 of 554Category 5 Assessments Approved by EPA August 10, 2012 USGS The National Map: Orthoimagery. Data refreshed October, 2020. National Flood Hazard Layer FIRMette 0 500 1,000 1,500 2,000250 Feet Ü SEE FIS REPORT FOR DETAILED LEGEND AND INDEX MAP FOR FIRM PANEL LAYOUT SPECIAL FLOOD HAZARD AREAS Without Base Flood Elevation (BFE) Zone A, V, A99 With BFE or DepthZone AE, AO, AH, VE, AR Regulatory Floodway 0.2% Annual Chance Flood Hazard, Areas of 1% annual chance flood with average depth less than one foot or with drainage areas of less than one square mileZone X Future Conditions 1% Annual Chance Flood HazardZone X Area with Reduced Flood Risk due to Levee. See Notes.Zone X Area with Flood Risk due to LeveeZone D NO SCREEN Area of Minimal Flood Hazard Zone X Area of Undetermined Flood HazardZone D Channel, Culvert, or Storm Sewer Levee, Dike, or Floodwall Cross Sections with 1% Annual Chance 17.5 Water Surface Elevation Coastal Transect Coastal Transect Baseline Profile Baseline Hydrographic Feature Base Flood Elevation Line (BFE) Effective LOMRs Limit of Study Jurisdiction Boundary Digital Data Available No Digital Data Available Unmapped This map complies with FEMA's standards for the use of digital flood maps if it is not void as described below. The basemap shown complies with FEMA's basemap accuracy standards The flood hazard information is derived directly from the authoritative NFHL web services provided by FEMA. This map was exported on 10/19/2020 at 2:25 PM and does not reflect changes or amendments subsequent to this date and time. The NFHL and effective information may change or become superseded by new data over time. This map image is void if the one or more of the following map elements do not appear: basemap imagery, flood zone labels, legend, scale bar, map creation date, community identifiers, FIRM panel number, and FIRM effective date. Map images for unmapped and unmodernized areas cannot be used for regulatory purposes. Legend OTHER AREAS OF FLOOD HAZARD OTHER AREAS GENERAL STRUCTURES OTHER FEATURES MAP PANELS 8 B 20.2 The pin displayed on the map is an approximate point selected by the user and does not represent an authoritative property location. 1:6,000 80°24'8"W 35°41'58"N 80°23'31"W 35°41'29"N 7-ELEVEN LONG FERRY ROAD CPR-20000 WATERSHED SOILS INFORMATION Hydrologic Soil Group—Rowan County, North Carolina (PreDev DA) Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 9/22/2020 Page 1 of 439500803950110395014039501703950200395023039502603950080395011039501403950170395020039502303950260554330554360554390554420554450554480554510554540554570554600 554330 554360 554390 554420 554450 554480 554510 554540 554570 554600 35° 41' 41'' N 80° 23' 58'' W35° 41' 41'' N80° 23' 46'' W35° 41' 35'' N 80° 23' 58'' W35° 41' 35'' N 80° 23' 46'' WN Map projection: Web Mercator Corner coordinates: WGS84 Edge tics: UTM Zone 17N WGS84 0 50 100 200 300 Feet 0 20 40 80 120 Meters Map Scale: 1:1,370 if printed on A landscape (11" x 8.5") sheet. Soil Map may not be valid at this scale. MAP LEGEND MAP INFORMATION Area of Interest (AOI) Area of Interest (AOI) Soils Soil Rating Polygons A A/D B B/D C C/D D Not rated or not available Soil Rating Lines A A/D B B/D C C/D D Not rated or not available Soil Rating Points A A/D B B/D C C/D D Not rated or not available Water Features Streams and Canals Transportation Rails Interstate Highways US Routes Major Roads Local Roads Background Aerial Photography The soil surveys that comprise your AOI were mapped at 1:24,000. Warning: Soil Map may not be valid at this scale. Enlargement of maps beyond the scale of mapping can cause misunderstanding of the detail of mapping and accuracy of soil line placement. The maps do not show the small areas of contrasting soils that could have been shown at a more detailed scale. Please rely on the bar scale on each map sheet for map measurements. Source of Map: Natural Resources Conservation Service Web Soil Survey URL: Coordinate System: Web Mercator (EPSG:3857) Maps from the Web Soil Survey are based on the Web Mercator projection, which preserves direction and shape but distorts distance and area. A projection that preserves area, such as the Albers equal-area conic projection, should be used if more accurate calculations of distance or area are required. This product is generated from the USDA-NRCS certified data as of the version date(s) listed below. Soil Survey Area: Rowan County, North Carolina Survey Area Data: Version 17, Jun 3, 2020 Soil map units are labeled (as space allows) for map scales 1:50,000 or larger. Date(s) aerial images were photographed: Oct 28, 2018—Oct 30, 2018 The orthophoto or other base map on which the soil lines were compiled and digitized probably differs from the background imagery displayed on these maps. As a result, some minor shifting of map unit boundaries may be evident. Hydrologic Soil Group—Rowan County, North Carolina (PreDev DA) Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 9/22/2020 Page 2 of 4 Hydrologic Soil Group Map unit symbol Map unit name Rating Acres in AOI Percent of AOI EnC Enon fine sandy loam, 8 to 15 percent slopes C 0.1 2.2% LdB2 Lloyd clay loam, 2 to 8 percent slopes, moderately eroded B 4.8 97.8% Totals for Area of Interest 4.9 100.0% Description Hydrologic soil groups are based on estimates of runoff potential. Soils are assigned to one of four groups according to the rate of water infiltration when the soils are not protected by vegetation, are thoroughly wet, and receive precipitation from long-duration storms. The soils in the United States are assigned to four groups (A, B, C, and D) and three dual classes (A/D, B/D, and C/D). The groups are defined as follows: Group A. Soils having a high infiltration rate (low runoff potential) when thoroughly wet. These consist mainly of deep, well drained to excessively drained sands or gravelly sands. These soils have a high rate of water transmission. Group B. Soils having a moderate infiltration rate when thoroughly wet. These consist chiefly of moderately deep or deep, moderately well drained or well drained soils that have moderately fine texture to moderately coarse texture. These soils have a moderate rate of water transmission. Group C. Soils having a slow infiltration rate when thoroughly wet. These consist chiefly of soils having a layer that impedes the downward movement of water or soils of moderately fine texture or fine texture. These soils have a slow rate of water transmission. Group D. Soils having a very slow infiltration rate (high runoff potential) when thoroughly wet. These consist chiefly of clays that have a high shrink-swell potential, soils that have a high water table, soils that have a claypan or clay layer at or near the surface, and soils that are shallow over nearly impervious material. These soils have a very slow rate of water transmission. If a soil is assigned to a dual hydrologic group (A/D, B/D, or C/D), the first letter is for drained areas and the second is for undrained areas. Only the soils that in their natural condition are in group D are assigned to dual classes. Hydrologic Soil Group—Rowan County, North Carolina PreDev DA Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 9/22/2020 Page 3 of 4 Rating Options Aggregation Method: Dominant Condition Component Percent Cutoff: None Specified Tie-break Rule: Higher Hydrologic Soil Group—Rowan County, North Carolina PreDev DA Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 9/22/2020 Page 4 of 4 7-ELEVEN LONG FERRY ROAD CPR-20000 PRECIPITATION DATA Project Name: 7-Eleven Long Ferry Road Date: 10/20/2020 Project Number: CPR-20000 Calculated By:J. Woodard, PE INPUT DATA (REF: NOAA Atlas 14). Copy input data from NOAA Atlas 14. Paste Special...Values and Transpose ARI 5 10 15 30 60 120 3 6 12 24 48 3 4 7 10 20 30 45 60 [years] [min] [min] [min] [min] [min] [min] [hrs] [hrs] [hrs] [hrs] [hrs] [days] [days] [days] [days] [days] [days] [days] [days] 1 0.384 0.614 0.767 1.05 1.31 1.51 1.61 1.95 2.29 2.73 3.17 3.37 3.58 4.13 4.71 6.34 7.84 9.87 11.7 2 0.455 0.727 0.914 1.26 1.58 1.83 1.94 2.35 2.76 3.3 3.82 4.05 4.29 4.93 5.6 7.48 9.22 11.5 13.7 5 0.53 0.849 1.07 1.53 1.96 2.28 2.43 2.93 3.46 4.14 4.75 5.02 5.29 6 6.73 8.83 10.7 13.2 15.4 10 0.583 0.933 1.18 1.71 2.23 2.61 2.79 3.38 4.01 4.8 5.48 5.78 6.08 6.84 7.61 9.89 11.9 14.4 16.8 25 0.642 1.02 1.3 1.92 2.56 3.04 3.28 3.98 4.76 5.7 6.47 6.81 7.15 7.99 8.79 11.3 13.4 16.1 18.5 50 0.681 1.09 1.37 2.07 2.8 3.36 3.65 4.45 5.35 6.41 7.25 7.62 8 8.91 9.71 12.4 14.5 17.3 19.8 100 0.716 1.14 1.44 2.2 3.04 3.67 4.01 4.93 5.96 7.13 8.04 8.45 8.86 9.84 10.6 13.6 15.7 18.5 21.1 200 0.745 1.18 1.49 2.32 3.26 3.98 4.38 5.4 6.59 7.88 8.85 9.3 9.75 10.8 11.6 14.7 16.8 19.6 22.3 500 0.777 1.23 1.55 2.46 3.53 4.37 4.86 6.05 7.44 8.89 9.94 10.4 11 12.1 12.9 16.3 18.3 21.2 23.8 1000 0.798 1.26 1.58 2.55 3.73 4.66 5.22 6.53 8.09 9.69 10.8 11.3 11.9 13.1 13.8 17.4 19.4 22.3 25 RAINFALL CALCULATIONS 7-ELEVEN LONG FERRY ROAD CPR-20000 PRE-DEVELOPMENT HYDROLOGIC CALCULATIONS PRE PRE DEVELOPMENT GRAPHIC SCALE 0 15 30 60 1 inch = 30 ft. CONTRACTOR SHALL NOTIFY "NC811" (811) OR (1-800-632-4949) AT LEAST 3 FULL BUSINESS DAYS PRIOR TO BEGINNING CONSTRUCTION OR EXCAVATION TO HAVE EXISTING UTILITIES LOCATED. CONTRACTOR SHALL CONTACT ANY LOCAL UTILITIES THAT PROVIDE THEIR OWN LOCATOR SERVICES INDEPENDENT OF "NC811". REPORT ANY DISCREPANCIES TO THE ENGINEER IMMEDIATELY. R EXISTING FRONT CREEK ROAD (VARIABLE WIDTH PUBLIC R/W) EXISTING LONG FERRY ROAD (SR 2120) (VARIABLE WIDTH PUBLIC R/W) 1"=30' EXISTING CONDITIONS LEGEND CLIENT REVISIONS PROJECT NO.CPR-20000 FILENAME CHECKED BY JBW DRAWN BY LSE SCALE DATE 09.24.2020 N0.DATE M:\Projects\CroslandSE\CPR-20000\04-Production\Engineering\Construction Drawings\Current Drawings\CPR20000-Pre Development DA.dwg, 10/20/2020 10:21:13 AM, Woodard, JonathanThe John R. McAdams Company, Inc. www.mcadamsco.com 3430 Toringdon Way Suite 110 phone 704. 527. 0800 fax 919. 361. 2269 license number: C-0293, C-187 Charlotte, NC 28277 7-ELEVEN - LONG FERRY ROADSTORE NUMBER: 1047760CONSTRUCTION DRAWINGS1215 LONG FERRY ROADSALISBURY, NORTH CAROLINA 28146SHEET PLAN INFORMATION C4 STORE HOLDINGS II, LLC 121 WEST TRADE STREET, SUITE 2550 CHARLOTTE, NORTH CAROLINA 28202 PHONE: 704.414.7472 CPR20000-Pre Development DA FINAL DRAWING - RELEASED FOR CONSTRUCTION N/F LARRY R. BARNETTE PID: 052 095 DB. 1295, PG. 611 ZONING: IB JAMES EDWARD EPTING HIERS PID: 052 213 DB. 1280, PG. 358 ZONING: CBI 176,466 S.F.= 4.051 AC VICINITY MAP N.T.S. SITE FOR REFERENCE ONLYCOVER CONDITIONS POINT OF ANALYSIS EXISTING DRAINAGE DIVIDE IMPERVIOUS AREA = 91,023 SF EXISTING IMPERVIOUS AREA DRAINS TO POINT OF ANALYSIS #2 THAT WAS NOT ANALYZED POINT OF ANALYSIS #2 OFF-SITE AREA IS NOT INCLUDED IN EXISTING IMPERVIOUS TAKEOFF Project Name:7-Eleven - Long Ferry Road Date:10/20/2020 Project Number:CPR-20000 Calculated By:J. Woodard, PE Subbasin ID:1 SCS CURVE NUMBER (REF: TR-55 and NRCS Web Soil Survey). HSG Impervious Open Wooded Pond A 98 39 30 100 B 98 61 55 100 C 98 74 70 100 D 98 80 77 100 HSG 'A' =0% HSG 'B' =100% HSG 'C' =0% HSG 'D' =0% Cover Composite Condition SCS CN Impervious 98 Open 61 Wooded 55 Pond 100 WATERSHED BREAKDOWN Composite Area Area SCS CN [sf][acres] 98 91,023 2.09 61 50,928 1.17 55 0 0.00 100 0 0.00 98 34,380 0.79 61 35,371 0.81 55 0 0.00 100 0 0.00 Total Area =211,702 sf =4.86 acres Composite SCS CN =83 % Impervious =59.24% TIME OF CONCENTRATION (REF: SCS Segmental Approach, TR-55). Time of concentration is 5 minutes due to existing impervious area across the site and public ROW. Offsite Pond - PRE DEVELOPMENT HYDROLOGIC CALCULATIONS Offsite Impervious - Offsite Open Assume good condition Offsite Wooded Assume good condition Comments - Assume good condition Assume good condition - Contributing Area Onsite Impervious Onsite Open Onsite Wooded Onsite Pond Comments - Assume good condition Assume good condition - 7-ELEVEN LONG FERRY ROAD CPR-20000 POST-DEVELOPMENT HYDROLOGIC CALCULATIONS CAT SCALEGRAPHIC SCALE 0 15 30 60 1 inch = 30 ft. CONTRACTOR SHALL NOTIFY "NC811" (811) OR (1-800-632-4949) AT LEAST 3 FULL BUSINESS DAYS PRIOR TO BEGINNING CONSTRUCTION OR EXCAVATION TO HAVE EXISTING UTILITIES LOCATED. CONTRACTOR SHALL CONTACT ANY LOCAL UTILITIES THAT PROVIDE THEIR OWN LOCATOR SERVICES INDEPENDENT OF "NC811". REPORT ANY DISCREPANCIES TO THE ENGINEER IMMEDIATELY. R EXISTING FRONT CREEK ROAD (VARIABLE WIDTH PUBLIC R/W) EXISTING LONG FERRY ROAD (SR 2120) (VARIABLE WIDTH PUBLIC R/W) 1"=30' VICINITY MAP N.T.S. CLIENT REVISIONS PROJECT NO.CPR-20000 FILENAME CHECKED BY JBW DRAWN BY LSE SCALE DATE 09.24.2020 N0.DATE M:\Projects\CroslandSE\CPR-20000\04-Production\Engineering\Construction Drawings\Current Drawings\CPR20000-Post Development DA.dwg, 10/20/2020 10:23:41 AM, Woodard, JonathanThe John R. McAdams Company, Inc. www.mcadamsco.com 3430 Toringdon Way Suite 110 phone 704. 527. 0800 fax 919. 361. 2269 license number: C-0293, C-187 Charlotte, NC 28277 7-ELEVEN - LONG FERRY ROADSTORE NUMBER: 1047760CONSTRUCTION DRAWINGS1215 LONG FERRY ROADSALISBURY, NORTH CAROLINA 28146SHEET PLAN INFORMATION C4 STORE HOLDINGS II, LLC 121 WEST TRADE STREET, SUITE 2550 CHARLOTTE, NORTH CAROLINA 28202 PHONE: 704.414.7472 CPR20000-Post Development DA FINAL DRAWING - RELEASED FOR CONSTRUCTION STORMWATER CONTROL MEASURE CONTRACTOR SHALL NOTIFY "SC811" (811) OR (1-800-721-7877) AT LEAST 3 FULL BUSINESS DAYS PRIOR TO BEGINNING CONSTRUCTION OR EXCAVATION TO HAVE EXISTING UTILITIES LOCATED. CONTRACTOR SHALL CONTACT ANY LOCAL UTILITIES THAT PROVIDE THEIR OWN LOCATOR SERVICES INDEPENDENT OF "SC811". REPORT ANY DISCREPANCIES TO THE ENGINEER IMMEDIATELY. R EXISTING CONDITIONS LEGEND POST POST DEVELOPMENT COVER CONDITIONS GRADING LEGEND POINT OF ANALYSIS IMPERVIOUS AREA DRAINS TO SCM = 30,438 SF IMPERVIOUS AREA DRAINS TO POA = 52,619 SF IMPERVIOUS AREA DRAINS TO POA = 38,724 SF TOTAL ON-SITE IMPERVIOUS AREA DRAINING TO POA = 120,986 SF EX. ON-SITE IMPERVIOUS AREA DRAINING TO POA = 91,023 SF DIFFERENCE IN IMPERVIOUS AREA REQUIRED TO BE TREATED = 29,945 SF PROPOSED IMPERVIOUS AREA TO BE TREATED = 30,438 SF FOR REFERENCE ONLY Project Name:7-Eleven - Long Ferry Road Date:10/20/2020 Project Number:CPR-20000 Calculated By:J. Woodard, PE Subbasin ID:1-To SCM A SCS CURVE NUMBER (REF: TR-55 and NRCS Web Soil Survey). HSG Impervious Open Wooded Pond A 98 39 30 100 B 98 61 55 100 C 98 74 70 100 D 98 80 77 100 HSG 'A' =0% HSG 'B' =100% HSG 'C' =0% HSG 'D' =0% Cover Composite Condition SCS CN Impervious 98 Open 61 Wooded 55 Pond 100 WATERSHED BREAKDOWN Composite Area Area SCS CN [sf][acres] 98 30,438 0.70 61 5,850 0.13 55 0 0.00 100 2,910 0.07 98 0 0.00 61 0 0.00 55 0 0.00 100 0 0.00 Total Area =39,198 sf =0.90 acres Composite SCS CN =93 % Impervious =77.65% TIME OF CONCENTRATION Time of Concentration =5.00 minutes SCS Lag Time =3.00 minutes Offsite Open Assume good condition Offsite Wooded Assume good condition Offsite Pond - Onsite Wooded Assume good condition Onsite Pond - Offsite Impervious - Contributing Area Comments Onsite Impervious - Onsite Open Assume good condition - POST DEVELOPMENT HYDROLOGIC CALCULATIONS Comments - Assume good condition Assume good condition 7-ELEVEN LONG FERRY ROAD CPR-20000 DESIGN OF STORMWATER CONTROL MEASURE A Project Name:7-Eleven - Long Ferry Road Date:10/20/2020 Project Number:CPR-20000 Calculated By:J. Woodard, PE Facility ID:SCM A SAND FILTER Average Incremental Accumulated Calculated Contour Stage Contour Area Contour Area Contour Vol Contour Vol Stage LN Storage [ft][ft][sf][sf][cf][cf][ft] 703.00 0.00 580 703.50 0.50 727 654 327 327 0.51 5.79 704.00 1.00 857 792 396 723 0.98 6.58 705.00 2.00 1,184 1,021 1,021 1,743 2.02 7.46 b =1.2078 Ks =744 STAGE-STORAGE FUNCTION - SAND FILTER 'A' y = 1329.2x1.2173 R² = 0.9997 0 500 1000 1500 2000 2500 3000 3500 0 0.5 1 1.5 2 2.5Storage (CF)Stage (feet) Storage vs. Stage Project Name:7-Eleven - Long Ferry Road Date:10/20/2020 Project Number:CPR-20000 Calculated By:J. Woodard, PE Facility ID:SCM A PRE-TREATMENT Average Incremental Accumulated Calculated Contour Stage Contour Area Contour Area Contour Vol Contour Vol Stage LN Storage [ft][ft][sf][sf][cf][cf][ft] 703.00 0.00 940 703.50 0.50 1,125 1,033 516 516 0.51 6.25 704.00 1.00 1,290 1,208 604 1,120 0.98 7.02 705.00 2.00 1,687 1,489 1,489 2,609 2.02 7.87 b =1.1685 Ks =1147 STAGE-STORAGE FUNCTION - PRE-TREATMENT 'A' y = 2122.2x1.8492 R² = 0.9997 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 0 0.5 1 1.5 2 2.5Storage (CF)Stage (feet) Storage vs. Stage Project Name:7-Eleven - Long Ferry Road Date:10/20/2020 Project Number:CPR-20000 Calculated By:J. Woodard, PE Facility ID:SCM A TOTAL STORAGE ABOVE SAND FILTER Average Incremental Accumulated Calculated Contour Stage Contour Area Contour Area Contour Vol Contour Vol Stage LN Storage [ft][ft][sf][sf][cf][cf][ft] 703.00 0.00 1,520 704.00 1.00 2,147 1,834 1,834 1,834 1.01 7.51 705.00 2.00 2,871 2,509 2,509 4,343 1.96 8.38 705.50 2.50 3,329 3,100 1,550 5,893 2.49 8.68 706.00 3.00 3,668 3,499 1,749 7,642 3.04 8.94 706.50 3.50 4,021 3,845 1,922 9,564 3.62 9.17 b =1.2904 Ks =1816 ASSOCIATED DEPTH IN POND WQv =1667 cf Stage/Storage Data: Ks =1816 b = 1.2904 Zo =703.00 Volume of 1" =1667 cf Calculated Values: 0.94 ft (Depth used to set depth of ponding in calculations) =11.23 inches Elevation =703.94 STAGE-STORAGE FUNCTION - TOTAL 'A' Depth of WQv in Basin = y = 3522.6x1.5663 R² = 0.9996 0 5000 10000 15000 20000 25000 30000 35000 40000 0 1 2 3 4 5Storage (CF)Stage (feet) Storage vs. Stage Project Name:7-Eleven - Long Ferry Road Date:10/20/2020 Project Number:CPR-20000 Calculated By:J. Woodard, PE Facility ID:SCM A DETERMINATION OF WATER QUALITY VOLUME (REF: Simple Method, Schueler, 1987). WQV = P x Rv x A / 12 where, WQV = Water Quality Volume (acre-ft) Rv = 0.05 + 0.009 x I, where I is % Impervious Cover A = Area (acres) P = Rainfall (inches) Total Drainage Area, A =0.90 acres Net Increase in Imp.Area =0.63 acres % Impervious, I =70.1% Rainfall, P =1.00 inches Rv =0.68 WQV =0.05 acre-ft 2,223 cf Sizing is based upon the discounted water quality volume, WQVdis (75% of the total WQV) per MDC standards WQVdis =1667 cf SAND FILTER SIZING AF = WQVdis / D where, AF = surface area of filter bed (sf) WQVdis= discounted water quality volume (cf) D = ponding depth WQVdis =1,667 cf D =2.00 ft AF = 834 sf (minimum sand filter surface area required) AP = 1,520 sf (sand filter area provided) Design Summary WATER QUALITY VOLUME CALCULATION (REF: MDC). Asf > 834 sf (min. total sand and sedimentation chamber surface area) Asf > 1,520 sf (total sand and sedimentation chamber surface area provided) Asand >417 sf (min. sand chamber area required) Asand >580 sf (min. sand chamber area provided) Ased >417 sf (min. sedimentation chamber area required) Ased >940 sf (min. sedimentation chamber area provided) D =2.00 ft (max. WQVdis ponding depth in facility) UNDERDRAIN SIZING (REF: Charlotte-Mecklenburg BMP Design Manual). Compute drawdown through filter bed Q = A(k)(hF+dF)/(dF) where, A = provided surface area of filter bed (sf) k = coefficient of permeability of filter media (ft/day) hF = height of water above filter bed (feet) dF = filter bed depth (feet) A =580 sf k =3.50 ft/day hF = 2.00 ft dF = 2.00 ft Q =4,060 cf/day =0.047 cfs Compute minimum drawdown discharge WQV =2,223 cf t =1.667 days Minimum drawdown, Q =0.015 cfs Compute underdrain pipe capacity Number of rows, n = 2 Diameter of underdrains, d = 6 inches Area, A =0.196 sf Wetted perimeter, P =1.571 ft Slope, S = 0.005 ft/ft Capacity of one pipe = 0.395 cfs Total capacity = 0.790 cfs Assume 50% clogging =0.395 cfs DESIGN ACCEPTABLE Compute underdrain preforation capacity 3/8-inch perforations spaced 3 inches on center, along 4 longitudinal rows spaced 90 o apart Number of rows, n = 2 Diameter of underdrains, d = 6 inches Length of underdrains, L = 18 ft Number of perforations =576 holes Capacity of one hole = 0.008 cfs Total capacity = 4.757 cfs Assume 50% clogging =2.378 cfs DESIGN ACCEPTABLE STAGE-DISCHARGE FOR SAND MEDIA (REF: Charlotte-Mecklenburg BMP Design Manual). AF = [(WQV)(dF)]/[(k)(hA+ dF)(t)] WQV / t = QO = AF (k)(hF+ dF)/(dF) A =580 sf dF = 2.00 ft Surface of sand media = 703.00 ft k =3.50 ft/day Elevation Height hF Discharge Qo [ft][ft][sf] 703.00 0.00 0.000 703.50 0.50 0.029 704.00 1.00 0.035 704.50 1.50 0.041 Project Name: 7-Eleven - Long Ferry Road Date: 10/20/2020 Project Number: CPR-20000 Calculated By: J. Woodard, PE Facility ID:SCM A INPUT DATA Inside Length =4.00 ft Inside Width =4.00 ft Wall Thickness =6.00 in Standard Base Length =5.00 ft Standard Base Width =5.00 ft Standard Base Thickness =6.00 in Inside Height of Riser =5.95 ft Concrete Unit Weight =142.00 pcf Unit weight of manhole concrete is 142 pcf per NC Products Outside Diameter of Barrel =30.00 in Drain Pipe (if present) =0.00 in CONCRETE PRESENT IN RISER STRUCTURE Riser Walls =53.550 cf Standard Base of Riser =12.500 cf Less Opening for Barrel =2.454 cf Less Opening for Drain Pipe =0.000 cf Total Concrete Less Openings =63.596 cf Weight of Concrete =9,031 lbs AMOUNT OF WATER DISPLACED BY RISER STRUCTURE Displacement by Concrete =63.596 cf Displacement by Open Air =95.200 cf Total Water Displaced =158.796 cf Weight of Water Displaced =9,909 lbs AMOUNT OF CONCRETE TO ADD TO RISER STRUCTURE Safety Factor =1.15 Recommend 1.15 or higher Add'l Weight for Bouyancy =2,365 lbs Bouyant Weight of Concrete =79.60 pcf Bouyant Weight w/ SF =69.22 pcf Add'l Concrete to Add =34.162 cf Less Standard Base =12.500 cf New Base Design Required =46.662 cf ANTI FLOTATION BLOCK DESIGN CALCULATIONS AF Block Length =7.00 ft AF Block Width =7.00 ft AF Block Thickness =12.00 in AF Block Provided =49.000 cf Total Concrete Present =100.096 cf =14,214 lbs RISER ANTI-FLOTATION CALCULATION Project: Date: 10/20/2020 Project Number: Calculated By: JBW Outlet Number: Outlet flowrate =6.24 cfs Pipe diameter = 15 inches Number of pipes = 1 Pipe separation = 0 feet Outlet Velocity = 5 ft/sec Zone from graph above =1 Outlet pipe diameter 15 in.Length =5.0 ft. Outlet flowrate 6.2 cfs Width =3.3 ft. Outlet velocity 5.0 ft/sec Stone diameter =3 in. Material =Class A Thickness =12 in. Zone Material Diameter Thickness Length Width 1 Class A 3 12 4 x D(o) 3 x D(o) 2 Class B 6 18 6 x D(o) 3 x D(o) 3 Class I 13 24 8 x D(o) 3 x D(o) 4 Class I 13 24 8 x D(o) 3 x D(o) 5 Class II 23 36 10 x D(o) 3 x D(o) 6 Class II 23 36 10 x D(o) 3 x D(o) 7 1. Calculations based on Pages 8.06.05 through 8.06.06 in NC Erosion Control Manual 2. Outlet velocity based on full-flow velocity Special study required DESIGN OF RIPRAP OUTLET PROTECTION WORKSHEET 7-Eleven - Long Ferry Road CPR-20000 SCM-A 5.0 ft/sec 0 5 10 15 20 25 0 1 2 3 4 5 6 7 8 9 10Velocity (ft/sec)Pipe diameter (ft) Figure 8.06.b.1 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Scenario Calculation Summary Scenario Summary 95ID Post WQVLabel Notes <I> Post Active TopologyActive Topology Hydrology Alternative - WQVHydrology WQVRainfall Runoff <I> Post PhysicalPhysical <I> Post Initial ConditionInitial Condition <I> Post Boundary ConditionBoundary Condition <I> Post Infiltration and InflowInfiltration and Inflow <I> Post OutputOutput <I> Post User Data ExtensionsUser Data Extensions 1 year 24 hour Calculation OptionsPondPack Engine Calculation Options Output Summary min1.00Output Increment min7,200.00Duration Rainfall Summary 0Return Event Tag Time-Depth CurveRainfall Type in1.0Total Depth 1 inchStorm Event Executive Summary (Nodes) Maximum Pond Storage (ft³) Maximum Water Surface Elevation (ft) Peak Flow (ft³/s) Time to Peak (min) Hydrograph Volume (ft³) TruncationReturn Event (years) ScenarioLabel (N/A)(N/A)0.031338.001,464.000None0Post WQVPOA-1 (N/A)(N/A)1.027186.001,464.000None0Post WQVSCM-A (IN) 1,129.000703.660.031338.001,464.000None0Post WQVSCM-A (OUT) (N/A)(N/A)1.027186.001,464.000None0Post WQVSub-1-to- SCM-A Executive Summary (Links) Node Flow Direction End PointPeak Flow (ft³/s) Peak Time (min) Hydrograph Volume (ft³) LocationTypeLabel Pond InflowSCM-A1.027186.001,464.000Upstream Pond Outflow SCM-A0.031338.001,464.000Outflow 0.031338.001,464.000Link POA-10.031338.001,464.000Downstream Messages 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Scenario Calculation Summary Messages WarningSource Kr (reverse flow entrance loss coefficient) was not specified. Kr was set to same value as Ke= 0.50 . Message (N/A)Time SCM-ALabel 143Element Id Composite Outlet StructureElement Type Post WQVScenario 15Message Id WarningSource Charged riser flow adjusted to weir flow rate to maintain convergence. If adjustments are desired, substitute a user defined outlet rating table for level pool routing. Or, store rating curve (s) in E-Q-TW table, edit, then route with ICPM option. Message (N/A)Time SCM-ALabel 143Element Id Composite Outlet StructureElement Type Post WQVScenario 19Message Id 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road J. Woodard, PE7-Eleven Long Ferry Road Scenario Calculation Summary Scenario Summary 79ID Post 100 yearLabel Notes <I> Post Active TopologyActive Topology <I> Post HydrologyHydrology 100 yearRainfall Runoff <I> Post PhysicalPhysical <I> Post Initial ConditionInitial Condition <I> Post Boundary ConditionBoundary Condition <I> Post Infiltration and InflowInfiltration and Inflow <I> Post OutputOutput <I> Post User Data ExtensionsUser Data Extensions Base Calculation OptionsPondPack Engine Calculation Options Output Summary min1.00Output Increment min1,440.00Duration Rainfall Summary 100Return Event Tag Time-Depth CurveRainfall Type in7.1Total Depth 100 yearStorm Event Executive Summary (Nodes) Maximum Pond Storage (ft³) Maximum Water Surface Elevation (ft) Peak Flow (ft³/s) Time to Peak (min) Hydrograph Volume (ft³) TruncationReturn Event (years) ScenarioLabel (N/A)(N/A)6.244723.0016,230.000None100Post 100 year POA-1 (N/A)(N/A)6.782721.0020,559.000None100Post 100 year SCM-A (IN) 4,965.000705.226.244723.0016,230.000None100Post 100 year SCM-A (OUT) (N/A)(N/A)6.782721.0020,559.000None100Post 100 year Sub-1-to- SCM-A Executive Summary (Links) Node Flow Direction End PointPeak Flow (ft³/s) Peak Time (min) Hydrograph Volume (ft³) LocationTypeLabel Pond InflowSCM-A6.782721.0020,559.000Upstream Pond Outflow SCM-A6.244723.0016,230.000Outflow 6.244723.0016,230.000Link POA-16.244723.0016,230.000Downstream Messages Scenario Calculation Summary Messages WarningSource Kr (reverse flow entrance loss coefficient) was not specified. Kr was set to same value as Ke= 0.50 . Message (N/A)Time SCM-ALabel 143Element Id Composite Outlet StructureElement Type Post 100 yearScenario 15Message Id WarningSource Charged riser flow adjusted to weir flow rate to maintain convergence. If adjustments are desired, substitute a user defined outlet rating table for level pool routing. Or, store rating curve (s) in E-Q-TW table, edit, then route with ICPM option. Message (N/A)Time SCM-ALabel 143Element Id Composite Outlet StructureElement Type Post 100 yearScenario 19Message Id 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A Element Details SCM-ALabel Notes Headwater Range Use Pond for Headwater Range Headwater Type ft706.50Maximum (Headwater) SCM-APond ft0.50Increment (Headwater) ft703.00Minimum (Headwater) SpotElevation (ft) Tailwater Setup Free OutfallTailwater Type Tailwater Tolerances 30Maximum Iterations ft0.50Tailwater Tolerance (Maximum) ft0.01Headwater Tolerance (Minimum) ft³/s0.001Flow Tolerance (Minimum) ft0.50Headwater Tolerance (Maximum) ft³/s10.000Flow Tolerance (Maximum) ft0.01Tailwater Tolerance (Minimum) Outlet Structure CulvertOutlet Structure Type CircularCulvert Type Outlet Structure (IDs and Direction) CulvertOutlet ID TailwaterDownstream ID Forward Flow OnlyFlow Direction Notes Outlet Structure (Advanced) ft0.00Elevation (On) ft0.00Elevation (Off) Culvert Data 1Number of Barrels ft697.25Downstream Invert ft76.25Length in15.000Diameter ft699.15Upstream Invert Unsubmerged->Submerged FalseSpecify Transitions FalseCompute Inlet Control Only Culvert Coefficients 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A Culvert Coefficients Concrete - Square edge w/headwall Inlet Description 0.0398C Chart 1Chart 0.6700Y Nomograph 1Nomograph 0.013Manning's n Form 1Equation Form 0.50Ke 0.0098K 0.00Kr 2.0000M -0.50Slope Correction Factor Culvert (Advanced) ft0.00Convergence Tolerance FalseSpecify Number of Backwater Sections Pond Water Surface Elevation (ft)676.25 675.63 675.00 674.38 673.75 673.13 672.50 671.88 671.25 670.63 670.00 Flow (ft³/s) 12.00010.0008.0006.0004.0002.000 RATING TABLE FOR ONE OUTLET TYPE Structure ID = Culvert (Culvert-Circular) --------------------------------------- Mannings open channel maximum capacity: 5.364 ft³/s Upstream ID = Riser, Media Downstream ID = Tailwater (Pond Outfall) Next Downstream Hydraulic Grade Line (ft) Converge Downstream Hydraulic Grade Line (ft) (into) Headwater Hydraulic Grade Line (ft) Device Flow (ft³/s) Water Surface Elevation (ft) 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A RATING TABLE FOR ONE OUTLET TYPE Structure ID = Culvert (Culvert-Circular) --------------------------------------- Mannings open channel maximum capacity: 5.364 ft³/s Upstream ID = Riser, Media Downstream ID = Tailwater (Pond Outfall) Next Downstream Hydraulic Grade Line (ft) Converge Downstream Hydraulic Grade Line (ft) (into) Headwater Hydraulic Grade Line (ft) Device Flow (ft³/s) Water Surface Elevation (ft) Free OutfallFree Outfall666.920.048670.50 Free OutfallFree Outfall666.940.057671.00 Free OutfallFree Outfall666.950.065671.50 Free OutfallFree Outfall666.960.080672.00 Free OutfallFree Outfall666.970.084672.50 Free OutfallFree Outfall666.980.091672.90 Free OutfallFree Outfall666.980.094673.00 Free OutfallFree Outfall666.990.103673.50 Free OutfallFree Outfall666.990.114674.00 Free OutfallFree Outfall667.000.121674.50 Free OutfallFree Outfall667.010.135675.00 Free OutfallFree Outfall667.020.136675.30 Free OutfallFree Outfall668.214.439675.50 Free OutfallFree Outfall676.0013.093676.00 Tailwater Error (ft) Downstream Channel Tailwater (ft) Convergence Error (ft³/s) Downstream Hydraulic Grade Line Error (ft) 0.00(N/A)0.0010.00 0.00(N/A)0.0010.00 0.00(N/A)0.0000.00 0.00(N/A)0.0050.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0010.00 0.00(N/A)0.0000.00 0.00(N/A)0.0020.00 0.00(N/A)0.0000.00 0.00(N/A)0.0040.00 0.00(N/A)0.0010.00 0.00(N/A)0.0000.00 0.00(N/A)15.1690.00 Message BACKWATER CONTROL.. Vh= .025ft hwDi= .087ft H.JUMP IN PIPE Hev= .00ft BACKWATER CONTROL.. Vh= .029ft hwDi= .095ft Lbw= 151.0ft Hev= .00ft 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A RATING TABLE FOR ONE OUTLET TYPE Structure ID = Culvert (Culvert-Circular) --------------------------------------- Mannings open channel maximum capacity: 5.364 ft³/s Upstream ID = Riser, Media Downstream ID = Tailwater (Pond Outfall) Message CRIT.DEPTH CONTROL Vh= .033ft Dcr= .098ft H.JUMP IN PIPE Hev= .00ft CRIT.DEPTH CONTROL Vh= .037ft Dcr= .109ft H.JUMP IN PIPE Hev= .00ft CRIT.DEPTH CONTROL Vh= .038ft Dcr= .111ft H.JUMP IN PIPE Hev= .00ft CRIT.DEPTH CONTROL Vh= .039ft Dcr= .116ft H.JUMP IN PIPE Hev= .00ft CRIT.DEPTH CONTROL Vh= .040ft Dcr= .117ft H.JUMP IN PIPE Hev= .00ft CRIT.DEPTH CONTROL Vh= .042ft Dcr= .123ft H.JUMP IN PIPE Hev= .00ft CRIT.DEPTH CONTROL Vh= .044ft Dcr= .129ft H.JUMP IN PIPE Hev= .00ft BACKWATER CONTROL.. Vh= .045ft hwDi= .135ft Lbw= 151.0ft Hev= .00ft CRIT.DEPTH CONTROL Vh= .048ft Dcr= .142ft CRIT.DEPTH Hev= .00ft CRIT.DEPTH CONTROL Vh= .048ft Dcr= .142ft H.JUMP IN PIPE Hev= .00ft BACKWATER CONTROL.. Vh= .326ft hwDi= .921ft Lbw= 151.0ft Hev= .00ft FULL FLOW...Lfull=150.78ft Vh=1.769ft HL=8.849ft Hev= .00ft Outlet Structure User Defined Rating TableOutlet Structure Type Outlet Structure (IDs and Direction) MediaOutlet ID CulvertDownstream ID Forward Flow OnlyFlow Direction Notes 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A Outlet Structure (Advanced) ft0.00Elevation (On) ft0.00Elevation (Off) Outlet Structure (Common) ft703.00Elevation User Defined Rating Curve Flow (ft³/s) Elevation (ft) 0.0000.00 0.0290.50 0.0351.00 0.0411.50 0.0472.00 0.0532.50 0.0593.00 0.0653.50 Pond Water Surface Elevation (ft)676.25 675.63 675.00 674.38 673.75 673.13 672.50 671.88 671.25 670.63 670.00 Flow (ft³/s) 0.1400.1300.1200.1100.1000.0900.0800.0700.0600.050 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A RATING TABLE FOR ONE OUTLET TYPE Structure ID = Media (User Defined Table) --------------------------------------- Upstream ID = (Pond Water Surface) Downstream ID = Culvert (Culvert-Circular) Next Downstream Hydraulic Grade Line (ft) Converge Downstream Hydraulic Grade Line (ft) (into) Headwater Hydraulic Grade Line (ft) Device Flow (ft³/s) Water Surface Elevation (ft) 666.92666.92670.500.047670.50 666.94666.93671.000.056671.00 666.95666.95671.500.065671.50 666.96666.96672.000.075672.00 666.97666.97672.500.084672.50 666.98666.98672.900.091672.90 666.98666.98673.000.093673.00 666.99666.99673.500.103673.50 666.99666.99674.000.112674.00 667.00667.00674.500.121674.50 667.01667.01675.000.131675.00 667.02667.02675.300.136675.30 668.21668.21675.500.140675.50 676.00676.00676.000.150676.00 Tailwater Error (ft) Downstream Channel Tailwater (ft) Convergence Error (ft³/s) Downstream Hydraulic Grade Line Error (ft) 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 Message Interpolated from input table Interpolated from input table FLOW PRECEDENCE SET TO DOWNSTREAM CONTROLLING STRUCTURE Outlet Structure 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A Outlet Structure RiserOutlet Structure Type Outlet Structure (IDs and Direction) RiserOutlet ID CulvertDownstream ID Forward Flow OnlyFlow Direction Notes Outlet Structure (Advanced) ft0.00Elevation (On) ft0.00Elevation (Off) Outlet Structure (Riser) Inlet BoxRiser ft²16.000Orifice Area ft16.00Weir Length ft0.00Transition Elevation (ft^0.5)/s3.00Weir Coefficient ft0.00Transition Height 0.60Orifice Coefficient 1.00K Reverse Outlet Structure (Common) ft705.00Elevation Outlet Structure (Riser, Advanced) TrueUse Orifice Depth to Crest?FalseUse Submerged Weir Equation?Pond Water Surface Elevation (ft)676.25 675.63 675.00 674.38 673.75 673.13 672.50 671.88 671.25 670.63 670.00 Flow (ft³/s) 27.00024.00021.00018.00015.00012.0009.0006.0003.0000.000 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A RATING TABLE FOR ONE OUTLET TYPE Structure ID = Riser (Inlet Box) --------------------------------------- Upstream ID = (Pond Water Surface) Downstream ID = Culvert (Culvert-Circular) Next Downstream Hydraulic Grade Line (ft) Converge Downstream Hydraulic Grade Line (ft) (into) Headwater Hydraulic Grade Line (ft) Device Flow (ft³/s) Water Surface Elevation (ft) 666.920.000.000.000670.50 666.940.000.000.000671.00 666.950.000.000.000671.50 666.960.000.000.000672.00 666.970.000.000.000672.50 666.980.000.000.000672.90 666.980.000.000.000673.00 666.990.000.000.000673.50 666.990.000.000.000674.00 667.000.000.000.000674.50 667.010.000.000.000675.00 667.020.000.000.000675.30 668.21Free Outfall675.504.293675.50 676.00676.00676.0028.112676.00 Tailwater Error (ft) Downstream Channel Tailwater (ft) Convergence Error (ft³/s) Downstream Hydraulic Grade Line Error (ft) 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 0.00(N/A)0.0000.00 Message WS below an invert; no flow. WS below an invert; no flow. WS below an invert; no flow. WS below an invert; no flow. WS below an invert; no flow. WS below an invert; no flow. WS below an invert; no flow. 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A RATING TABLE FOR ONE OUTLET TYPE Structure ID = Riser (Inlet Box) --------------------------------------- Upstream ID = (Pond Water Surface) Downstream ID = Culvert (Culvert-Circular) Message WS below an invert; no flow. WS below an invert; no flow. WS below an invert; no flow. WS below an invert; no flow. WS below an invert; no flow. Weir: H =0.2ft FULLY CHARGED RISER, DOWNSTREAM CONTROL: Kev=0. Hev=0.000 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A Composite Rating Table Tailwater Elevation = Free Outfall (SCM-A) Convergence Error (ft) Tailwater Elevation (ft) Flow (ft³/s) Water Surface Elevation (ft) 0.00(N/A)0.048670.50 0.00(N/A)0.057671.00 0.00(N/A)0.065671.50 0.00(N/A)0.080672.00 0.00(N/A)0.084672.50 0.00(N/A)0.091672.90 0.00(N/A)0.110673.00 0.00(N/A)0.292673.50 0.00(N/A)0.386674.00 0.00(N/A)0.456674.50 0.00(N/A)0.523675.00 0.00(N/A)0.553675.30 0.00(N/A)4.869675.50 0.00(N/A)13.571676.00 Contributing Structures Media,Culvert (no Q: Riser,Orifice - 1) Media,Culvert (no Q: Riser,Orifice - 1) Media,Culvert (no Q: Riser,Orifice - 1) Media,Culvert (no Q: Riser,Orifice - 1) Media,Culvert (no Q: Riser,Orifice - 1) Media,Culvert (no Q: Riser,Orifice - 1) Media,Culvert,Orifice - 1 (no Q: Riser) Media,Culvert,Orifice - 1 (no Q: Riser) Media,Culvert,Orifice - 1 (no Q: Riser) Media,Culvert,Orifice - 1 (no Q: Riser) Media,Culvert,Orifice - 1 (no Q: Riser) Media,Culvert,Orifice - 1 (no Q: Riser) Riser,Media,Culvert,Orifice - 1 Riser,Media,Culvert,Orifice - 1 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road Composite Outlet Structure Detailed Report: SCM-A Rating Curve Pond Water Surface Elevation (ft)676.25 675.63 675.00 674.38 673.75 673.13 672.50 671.88 671.25 670.63 670.00 Flow (ft³/s) 12.00010.0008.0006.0004.0002.000 10/20/2020CPR20000.ppc J. Woodard, PE7-Eleven Long Ferry Road