HomeMy WebLinkAboutNC0034959_Cover LTR_20201020ROY COOPER
Coverwr
MICHAEL S. REGAN
secretary
S. DANIEL SMITH
Director
Anthony Vann, Assistant Superintendent
Rowan -Salisbury Schools
PO Box 2349
Salisbury, NC 28145
Dear Mr. Vann:
NORTH CAROLINA
En viraninen tat Quality
October 27, 2020
SUBJECT: Compliance Evaluation Inspection
East Rowan High School WWTP
NPDES Permit NCO034959
Rowan County, NC
On October 20, 2020, Roberto Scheller of this Office conducted a compliance inspection at the subject facility. This
inspection was conducted as a Compliance Evaluation Inspection (CEI) to insure compliance with permit requirements
and conditions. The subject facility appeared to be well operated and we wish to thank the operating staff at
Envirolink for assistance regarding this inspection.
The enclosed report should be self-explanatory; however, should you have any questions, please do not hesitate to
contact myself or Roberto Scheller at (704)235-2204 or roberto.scheller(a�ncdenr.gov.
Sincerely,
DocuSigned by:
A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: CEI Report
No rth Caroiina Department of E nvuon menu! Quairty I Dimsoo of Water Resources
ME Mooresville Regbfm! Office 1610 Es3 Center Avenue, Suite 301 I Mooresvlie, North Garoiina 28115
�L f •'— 7fA-6 3-168f}
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO034959 111 121 20/10/20 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701� I 711 L
LJ L -1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09:07AM 20/10/20
20/02/01
West Rowan High School
8050 NC Hwy 801
Exit Time/Date
Permit Expiration Date
Mount Ulla NC 28125
09:53AM 20/10/20
24/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Todd Franklin Robinson/ORC/704-881-4598/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
J. H. Bivens,515 N Clay St Salisbury NC 28144/Maintenance Director/704-639-3016/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Roberto Scheller DWR/MRO WQ/252-946-6481/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
10/27/2020
aiaccsainFvazs... Page#
NPDES yr/mo/day Inspection Type
NCO034959 I11 12I 20/10/20 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Facility compliance history was reviewed from August 2019 through July 2020. Facility reported one
daily and one monthly permit limit violations for BOD during September 2019. The facility is a 0.010
MGD wastewater treatment system that consist of septic tank, dosing tank, alternating dual surface
sand filter, and in -ground effluent holding tank. Facility discharges into Withrow Creek which is Class C
waters in the Yadkin Pee -Dee River Basin. At time of inspection facility appeared to be well maintained
and operated. Treatment unit did not discharge during compliance inspection.
Page#
Permit: NCO034959
Inspection Date: 10/20/2020
Owner -Facility: west Rowan High School
Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Current permit was issued on February 1, 2020 and expires on March 31,
2024.
Record Keeping
Yes
No
NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
❑
❑
0
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
0
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment:
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? M ❑ ❑ ❑
Page# 3
Permit: NCO034959
Inspection Date: 10/20/2020
Laboratory
Owner -Facility: west Rowan High School
Inspection Type: Compliance Evaluation
Yes No NA NE
# Is the facility using a contract lab?
0
❑
❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0 ❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0 ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0 ❑
Comment: All samples collected at this facility are grab samples and appear to be collected in
accordance with permit requirements. Field measurements are done under Field
Certification #5212. Statesville Lab pereforms all other analysis.
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment:
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ■ ❑
Yes No NA NE
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: Once through sand filter appeared to be in good condition and well maintained.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Page# 4