September 20, 2017
Mr. David Odom, Town Manager
Town of Taylorsville
344 Minnigan Lane
Taylorsville, NC 28681
� ' �RO'Y COOPER
I; Governor
MICHAEL S. REGAN
Secretary
S. JAY ZIMMERMAN
Director
Subject: Compliance Evaluation Inspection
Taylorsville WWTP
NPDES Permit No. NCO026271
Alexander County
Dear Mr. Odom:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at
the subject facility on September 19, 2017, by Ori Tuvia, Ed Watson and Ousmane Sidibe..Brian
Eades cooperation during the site visit was much appreciated. Please advise the staff involved with
this. NPDES Permit by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning
this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Cc: NPDES Unit
MRO Files
Sincerely,
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, DEQ
Mooresville Regional Office
Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115
Phone: (704) 663-16991 Fax: (704) 663.60401 Customer Service:1-877-623-6748
United States Environmental Protection Agency
Form Approved..
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires a-31-98
Section A: National Data System Coding (i.e., PCS) -
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 1 3 I NCO026271 I11 12 17/09/19 17 18 ICI 19 1 c I 20 LI
_1
16
211 I I I 1 11I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1. I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1 I 1
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67
1.0 70 71 IN 72 LI 73 174 75 1 1 1 1 1
80
Section B: FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number) .
09:25AM 17/09/19
15/07/01
Taylorsville WWTP
Minnigan Ln
Exit Time/Date
Permit Expiration Date
Taylorsville NC 28681 .
11:15AM 17/09/19
20/03/31
Name(s) of Onsite Representative(s)Ttles(s)/Phone and Fax Number(s)
Other Facility Data
Steve Brian Eades/ORC/828-632-5280/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
David Matthew Robinette,204 Main Ave Dr Taylorsville NC 28681/Public Works
No
Director/828-632-2218/
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) _ Agency/Office/Phone and Fax Numbers Date
Ousmane Sidibe Department Environmental Assistance a
Edward Watson MRO GW/// �� B
Od A Tuvia MRO W0//704-663-1699/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. AA�p� t �i�/
• s
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC0026271 I11 12 17/09/19 17 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
:, Page# 2 ,
i
Permit: NCO026271 Owner -Facility: TaylorsvilleWWiP
Inspection Date: 09/19/2017 Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment: The current permit expires on March 31, 2020.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Yes No NA NE
❑ ❑ E ❑
❑ ■ ❑ ❑
M. ❑ ❑ ❑
❑ ❑ ❑
Yes No NA NE
"❑
❑
❑
■
❑
❑
❑
❑
.❑
❑
❑
❑
❑
❑
❑.
❑
❑;
❑
❑
❑
❑
❑
■
❑
❑
❑
,Is the ORC certified at grade equal to or higher than the facility classification? M ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑
Is a copy of the current NPDES permit, available on. site? M ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? M ❑ ❑ ❑
Comment: The permittee's records were organized and well maintained and records requested during
the inspection were readily available. DMRs COCs. calibration logs. ORC visitation logs
and process control data were reviewed for the period September 2016 through July1017.
Laboratory
Yes No - NA NE
Page#
3
0
I
Permit: NCO026271 Owner - Facility: Taylorsville VWVrP
Inspection Date: 09/19/2017 Inspection Type: Compliance Evaluation.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
-0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
E
❑
❑
❑
# Is the facility using a contract lab?
M•
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)? .
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
M
❑
Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees?
❑
❑
M
❑
Comment: On -site analyses (pH and TRC) are performed under field laboratory certification #5062
(Town of Taylorsville). Water Tech Labs, Inc. (Certification #501performs all remaining
permit -required effluent analyses The field instrumentation used on site appeared to be
properly calibrated and documented: daily calibration/verification data is entered in the ORC
log book. The field instrumentation is calibrated annually by Water Tech labs. Inc.
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
N
❑
❑
❑
Is sample collected above side streams?
E
❑
❑
❑
Is proper volume collected?
E
- ❑.
❑
Is the tubing clean?
0
❑
❑
11.
# Is proper temperature set for sample storage (kept at less than or equal to 6.6 degrees
0
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
0
❑
El
❑
Comment: The influent composite sampler was collecting 170 mL per aliquot at the time of the
inspection.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
.❑
Is sample collected below all treatment units?
❑
❑
❑
Is proper.volume collected?
0
❑
❑
❑
Is the tubing. clean?
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
N
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: he efluent composite sampler was collecting 155 mL per aliquot when tested:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Page# 4
1
Permit: NCO026271 Owner -Facility: TaylorsvilleWWrP
Inspection Date: 09/19/2017 Inspection Type: Compliance Evaluation
Operations & Maintenance
Yes No NA NE
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
M
❑
❑
❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: �At the time of the inspection the facility appeared to be properly operated and well
maintained. The facility is equipped with a SCADA'system and dissolved oxygen and DH
PLC controllers are installed in the aeration basins for process control.
Pump Station —Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
El
❑.
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑ :
Are float controls operable?
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment:
Bar Screens
Yes No NA NE
Type of bar screen
i
a.Manual
❑
. b.Mechanical
Are the bars adequately screening debris?
❑
El
❑
Is the screen free of excessive debris?
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
❑
❑
❑
Comment:
Grit Removal
Yes No NA NE
i Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?.
M
❑
❑
❑
Is the grit free. of excessive odor?
❑
❑"
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment:
_
Page#
5
Permit: NCO026271 - Owner - Facility: Taylorsville WWTP
Inspection Date: 09/19/2017 Inspection Type: Compliance Evaluation
Grit Removal
Yes No NA NE
Flow Measurement - Influent
Yes. No NA NE
# Is flow meter used for reporting?
❑
.
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
. ❑
❑
Comment: The flow meter is calibrated/verified once per year.
Aeration Basins
'
Yes No NA NE
Mode of operation
I
Ext. Air
Type of aeration system
Diffused
Is the basin free of deed spots?.
E❑
❑
❑
Are surface aerators,and mixers operational?
E
❑.
❑
❑
Are the diffusers operational?
E
❑
❑
❑
Is the foam the proper color for the treatment process?
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
E
❑
❑
- ❑
Is the DO level acceptable?
E
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/I)
0
❑
❑
❑
Comment:
Secondary Clarifier
Yes No. NA NE
Is the clarifier free of black and odorous wastewater?
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
N
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
.Is the drive unit operational?
N
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑ .
Is the sludge blanketlevel acceptable? (Approximately % of the sidewall depth)
0
❑
❑
❑
Comment:
Page# 6
Permit: NCO026271 Owner - Facility: Taylorsvllle vvwrP
Inspection Date: 09/19/2017 Inspection Type: Compliance Evaluation
Disinfection -Gas
Yes No NA NE
Are cylinders secured adequately?
0
❑
❑
❑
Are cylinders protected from direct sunlight?
N
❑
❑
❑
Is there adequate reserve supply of disinfectant?
N
❑
❑
0
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
N
❑
❑
❑
Is there chlorine residual prior to de -chlorination? .
N
❑
❑
❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑
❑
If yes, then is there a Risk Management Plan on site?
❑
❑
0
❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment: The chlorination and dechlorination systems are serviced by Piedmont Chlorinator Sales
and Service. Inc
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: ' Sulfer dioxide is used for disinfection
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable? r
# Is tankage available for properly waste sludge?
Yes. No NA NE
Gas
❑
❑
❑
■.❑'❑:❑
❑
❑
❑
❑
❑
❑
Yes No NA NE
■ ❑ ❑- ❑
❑ ❑ ❑-N
❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Residuals awland applied by Southern Soil under permit W00006906. Anew digester, with
a 500,000 gallons capacity is being constructed.
Page# 7
Permit: NC0026271
Owner -Facility: Taylorsville WWTP
-Inspection Date: 09/19/2017
Inspection Type: Compliance Evaluation
Chemical Feed
Yes No NA NE
Is containment adequate?
M
❑
❑
❑
Is storage adequate?
E
❑
❑
❑
Are backup pumps available?
❑
❑
❑
M.
Is the site free of excessive leaking?
❑
❑
❑
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meterused for reporting?
❑
❑
❑
Is flow meter calibrated annually?
M
❑
❑
0
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Comment: The flow meter is calibrated/verified once peryear.
Standby Power
Yes No' NA NE
Is automatically activated standby power available?
N
❑
❑
❑
Is the generator tested by interrupting primary power source?
❑
❑
❑
Is the generator tested under load?
M.
❑
❑
❑
Was generator tested & operational during the inspection?
❑
❑
❑
Do the generator(s). have adequate capacity to operate the entire wastewater site?
N
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
E
❑
,❑
El
Is the generator fuel level monitored?
❑
❑
❑
Comment: The generator powers only the essentials unit for the operation of the UWVIP should power
be interrupted. The -generator is auto cycled once per week and placed under load a few
times per year. The generator is serviced annually and was last serviced by
Carolina CAT.
Page# 8