NPDES STAFF REPORT AND RECOMMENDATION
County: Alexander
Permit No. NCO026271 (A to C)
PART I - GENERAL INFORMATION
1. Facility and Address: Taylorsville WWTP
204 Main Avenue Drive S. E.
Taylorsville, NC 28681
2. ' Date of Investigation: July 25, 1995
3. Report Prepared By: Todd St. John
4. Persons Contacted and Telephone Number: Mr. Bob Duncan (704) 632-5280
5. Directions to Site: Travel on Hwy 16 North to Taylorsville. Turn left on Main Avenue. Turn
left on 7th Street S.W. Turn left on Happy Plains Road. Turn left on Minnington Road. The
WWTP is at the end of the road.
6. Discharge Point(s). List for all discharge :points:
Latitude: 350 53' 02," Longitude: 810 11' 44"
Attach a U.S.G.S. map extract and indicate treatment facility site and discharge point on
map.
U.S.G.S. Quad No.: D14NW U.S.G.S, Name: Taylorsville, NC
7. Site size and expansion are consistent with application?
Yes X No_ If No, explain:
8. Topography (relationship to flood plain included): The area in which the drying beds are
located may be prone to flooding. Precautions should be taken to protect New Clarifier 1,
New Recycle Pumping Station 1, the new chlorine contact chamber and the dechiorination
chamber/room from flooding.
9. Location of nearest dwelling: approximately 500 feet
10. Receiving stream or affected surface waters: Lower Little River
a. Classification: C
b. River Basin and Subbasin No.: 030832
C. Describe receiving stream features and pertinent downstream uses: The stream is
approximately 80 feet wide, has considerable flow, and has a bed that consists of
sand, mud, and rock. The stream has typical class "C" usage downstream.
PART II - DESCRIPTION OF DISCHARGE AND TREATMENT WORKS
1. a. What is the current permitted capacity of the wastewater treatment facility? 0.43
MGD
b. Actual treatment capacity of the current facility (current design capacity)? 0.43
MGD
C. Date(s) and construction activities allowed by previous Authorizations to Construct
issued in the previous two years: N/A
d. Please provide a description of existing or substantially constructed wastewater
treatment facilities: Facility consists of a bar screen, a flow splitting box, two Imhoff
tanks (in series), two trickling filters in series, an aeration basin, a secondary clarifier,
an aerobic digester, and chlorination. This facility also has sludge drying beds (not
currently in use). '
2. a. Please provide a description of proposed wastewater treatment facilities: The
proposed facilities will consist of a manual bar screen, a manual grit chamber, a flow
splitting box, dual aeration basins, dual final clarifiers, dual chlorine contact
chambers, one dechlorination tank, and four aerobic digesters.
b. Possible toxic impacts to surface waters: This facility is apparently handling
industrial wastewater from various sources including textile and furniture.
C. Pretreatment Program (POTWs only): None at this time. However, this facility
currently treats and will treat industrial wastewater in the future. The Town of
Page 2
Taylorsville is in the process of establishing a pretreatment program.
3. Residuals handling and utilization/disposal scheme:
a. If residuals are being land applied, please specify DEM Permit No.: WQ0006906
Residuals Contractor: Wheelabrator Clean Water Systems, Inc., Biogrow Division
Telephone No.: (410) 224 0022
b. Residuals stabilization: PSRP: X
RFRP:
Other:
C. Landfill: N/A
d. Other disposal/utilization scheme (specify): This facility has been burying the solids,
collected from the bar screen and the Imhoff tanks on site. This facility does not
have a permit to dispose of these solids in this manner.
Treatment plant classification (attach completed rating sheet): This facility will be class II
as currently proposed.
5. SIC Code(s): 4952
Wastewater Code(s) of actual wastewater, not particular facilities, i.e., non -contact cooling
water discharge from a metal plating company would be 14, not 56.
Primary: 01 Secondary: 02
Main Treatment Unit Code: 02 0 0 3
6. Important SOC, JOC or Compliance Schedule dates: (please indicate) N/A
PART III EVALUATION AND RECOMMENDATIONS
The Town of Taylorsville is applying for an Authorization to Construct to increase the
capacity of the wastewater;treatmerit facilities from 0.43 MGD to 0.83 MGD.
Staff from this Office and'tl e'Asheville Regional Office recently visited this site in response
to a request from the Town for technical assistance. The ORC did not attend this meeting and the
other representatives from the Town left during the visit and did not return. These actions seem to
indicate that some of the problems that the this subject facility is experiencing may be a result of
Page 3
inadequate motivation to properly run the facility. As a result it is not certain that the requested
improvements will achieve.the desired results. Nevertheless, the facility does need to expand its
treatment capabilities in order to meet the expected increase in wastewater volume.
The Town is proposing to convert the existing trickling filters into aeration basins. The Town
proposes installing 50 HP floating surface aerators in file aeration basins. It is not clear why the
Town is proposing to use this method of aeration when it would be possible to add blowers and
diffusers as will be done with the aerobic sludge digesters. The walls of the existing trickling filters
will be raised approximately-4 feet. The resultant water depth in the proposed aeration basins will
be 10 feet. The shape of these basins will be cylindrical (vertical sides that meet a horizontal wall),
and the diameter of each basin will be 80 feet. The aerator will be located in the center of the basin.
The shallow and wide configuration of the basins and the central location of the aerators may
produce "dead spots". Considering the Town's apparent lack of initiative to properly maintain and
operate this facility, this Office would prefer a more reliable method of aeration for the aeration
basins such as diffused air. Also, because this facility will not be using diffused air in the aeration
basins, it will be reclassified from a Class III to a Class II WWTP.
Signature o Report Preparer
D. j64C,-"-t,
Water Quality k egional Supervisor
Date
Page 4
./ . , �j "- asintsy, r
,/ . ---- - rf " -- ), "
0
tit'
I N\
f
Q.
A
\r z V f
Ti"
BM 11 90 j
lorsy 0o
12
qem I
rid
JI,
;(10
Ilbspit'ar
t- IR'
Cje n
IL
4,
N
A/.
ICb
0
0.
INAI;
.Z, CP
46
Co se t i �Ra o'Tower,
Golf
IYO LK) I
106
e
SY
g 160 05 6
_J/4
QT C' nal Onit
C re tio
N
CP
At
1180
I'm Cqrrn
u
%
D )sal
00 L.41
00
a LI
169
00
Liledq,
/00 N
L
A
A
�v
-,-WIWT
k.,
biscedoni.)c
1`1075
Coun
ty
39�
)i Fairgro
p 1100
un
'q, -
A
\�q
hrm)