HomeMy WebLinkAboutNC0034860_Regional Office Historical File Pre 2018 (25)UEOOPER Governor MICHAEL. S. REGAN . Secretary . Water Resources ENVIRONMENTAL QUALITY November 15, 2017 Mr. Chip Swinnie, Plant Manager Schneider Mills, Inc. P.O. Box 519 Taylorsville, NC 28681 Subject: Compliance Inspection Schneider Mills WWTP NPDES Permit No. NCO034860 Alexander County Dear Mr. Swinnie: LINDA CULPEPPER Interim Director r Enclosed is a copy of the Compliance Inspection for the inspection conducted at the subject facility on November 3, 2016, by Ori Tuvia.. Darren Webb's cooperation during the site visit was much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a copy of,the enclosed report. The following areas of concern were observed during the inspection: 1) ORC Must Record the beginning and end time of composite sampling. 2) At the time of the inspection the flow meter values did not match the calculated value, ORC will need to farther investigate. The report should be self-explanatory; however, should you have any questions, concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia@ncdenr.gov. Cc: NPDES Unit MRO Files Sincerely, Ori Tuvia, Environmental Engineer Mooresville Regional Office Division of Water Resources,__DEQ Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-16991 Fax: (704) 663.60401 Customer Service:1.877-623-6748 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20480 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fee Type 1 IN I 2 15 I 3 I NCO034860 I11 12 17/11/14 17 18 I,• I 19 I s l 20I I 211;I I I, I I I l l l l i, I I I I I I I I I I I I I I I I I I I I I I I I I I I I I r6 I Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved 67 1.0 70IQ I 71 IN I 72 IJ N 72i I I74 75. IJ I_1 I I 80 Section B: FacilityData Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include - Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09:30AM 17/11/14 15/11/03 Schneider Mills WWTP 1170 NC Hwy 16 N Exit Time/Date Permit Expiration Date Taylorsville NC 28681 11:30AM 17/11/14 20/07/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Darren David Webb/ORC/828-632-8181/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Chip Swinnie,PO Box 519 Taylorsville NC 286810519/Plant Manager/828-632-8181/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports N.Self-Monitoring Program N Sludge Handling Disposal Facility Site Review Effluent/Receiving-Waters, Laboratory Section D: Summary of Finding/Comments (Attach, additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Od A Tuvia MRO WO//704-663-1699/ wer Agency/Office/Phone and Fax Numbers Date Signature of ManagemNMV Andrew Pitner Cl WQ//704-663-1699 Ext.21 (S 1 `7 EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# r Page# 2 0 Permit: NCO034860 Owner -Facility: Schneider Mills WWTP Inspection Date: 11/14/2017 Inspection Type; Compliance Evaluation Permit (If the present permit expires in 6 months or less). Has the permittee submitted a new application? Is the facility as described in the permit? # Are there any special conditions for the permit? Is access to the plant site restricted to the general public? Is the inspector granted access to all areas for inspection? Comment: The subject permit expires on 7/31/2020. Record Keeoina Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records,maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis - Name of person performing analyses Yes No NA 'NE ❑ ❑ N-❑ ■ ❑ ❑ ❑ ❑11 ❑ ❑ ■ ❑ ❑ ❑ 0 ❑ ❑ ❑ Yes No .NA NE ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 0 ❑ ❑ ❑ ■ ..❑ ❑ ❑ Transported COCs Are DMRs complete: do they include all permit parameters? .❑ ❑ ❑ Has the facility submitted its annuai compliance report to users and DWQ? ❑ ❑ -0 ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log. available and current? . ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? N ❑ Cl 11 Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ Comment: sampling. Page# 3 I Permit: NCO034860 Owner -Facility: Schneider Mills WWTP Inspection Date: 11/14/2017 Inspection Type: Compliance Evaluation Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? ❑ ❑ ❑ # Is the facility using a contract lab? E ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees N ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees? ❑ ❑ ❑ Comment: On -site field analvses (dissolved oxvgen, pH, temperature, total residual chlorine) are performed under the Company's field laboratory certification #5012. Water Tech Labs (BOD, TSS, ammonia, nutrients) and R & A Laboratories, Inc. (toxicity and metals) .have also been contracted to provide analytical support Effluent Sampling Yes No NA NE Is composite sampling flow proportional? . ❑ ❑ ❑ Is sample collected, below all treatment units? E ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tutting clean?- 0 ❑ ❑ ❑ # Is proper temperature -set for sample storage (kept at less than or equal to 6.0 degrees E ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type E ❑ ❑ ❑ representative)? Comment: The subiect Dermit'reauires both composite and Arab effluent samples. The Division improved a variance'to collect time -based composite samples on 5/26/1998 provided that the flows do not vary by more than 30%. The samgler was collecting 300 nil. aliquot every twenty minutes with an internal temperature of less than four degrees Celsius. Upstream % Downstream Sampling Yes No. NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, and ❑ ❑ - ❑ sampling location)? Comment: Operations & Maintenance Yes No NA NE ` Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable N ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The wastewater facility appeared to be properly operated and well maintained. The ORC incorporates a comprehensive process control Program with all measurements being properly documented and maintained on -site. Page# 4 F Permit: NCO034860 Owner - Facility: Schneider Mills WWTP Inspection Date: 11/14/2017 Inspection Type: Compliance Evaluation Bar Screens Yes "No NA NE Type_ of bar screen a.Manual b.Mechanical ❑ Are the bars adequately screening debris? E ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ 0- Is disposal of screening in compliance? N❑ ❑ ❑ Is the unit in good condition? ❑ 0 ❑ Comment: Bar screenings are disposed at the Alexander County Landfill. Flow Measurement - Influent Yes No NA NE # Inflow meter used for reporting? A ❑ '❑ 11, Is flow meter calibrated annually? . ❑ ❑ ❑, .." Is.the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ N ❑ Comment: The influent flow meter (Outfall 001) is calibrated twice Der year and was last calibrated by the number of backwash events per day. ,Aeration Basins Mode of operation Type of aeration system Is the basin free of dead spots? Are surface aerators and mixers operational? Are the diffusers operational? Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Is the DO level acceptable?(1.0 to 3.0 mg/1) Yes No NA NE_ Ext. Air Surface ■ ❑ ❑ ❑ . ❑ ❑ ■ ❑• N. ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ Comment: Aqueous lime and soda ash' are added to maintain appropriate pH/alkalinity levels. The ORC al§o adds food (BOD)/nutrient (nitrogen and phosphorus) supplements and selective microrganisms to maintain the biological treatment process. Secondary Clarifier Yes No NA NE Page# 5 I Permit: NC0034860 Owner - Facility: Schneider Mills WWiP Inspection Date: 11/14/2017.: Inspection Type: Compliance Evaluation Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ E13 ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? E. ❑ 11 ❑ Are weirs level? 0. , ❑ ❑ Is the site free of weir blockage? N. ❑ 0 .❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ -is scum removal adequate? ❑ .0 . ❑ Is. the site free of excessive floating sludge? N , ❑ ❑ ❑ Is the drive unit operational? 0 ❑ ❑ ❑ Is the return rate acceptable (low turbulence)? ❑ ❑ ❑ Is the overflow, clear of excessive. solids/pin floc? . ❑ ❑ . E] Is the sludge blanket level acceptable? (Approximately %.of the sidewall depth) 0 ❑ ❑ 0 Comment: Polymer is added to the clarifier influent to enhance settling. Pumps-RAS-WAS Yes No NA NE Are pumps in place? ❑ ❑ ❑ Are pumps operational .. > ❑ ❑ Are there adequate spare parts and supplies on site? E] ❑ ❑ Comment: Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: At the time of the inspection the -effluent appeared to be clear. Aerobic Digester Is the capacity adequate? 1, Is the mixing ,adequate? Is the site free of excessive foaming in the tank? #. Is the odor acceptable? # Is tankage available for properly waste "sludge? Comment: Yes No NA NE ■ '❑ ❑ -❑ 0,❑--❑ El El ❑ ❑ Yes No NA NE • ❑ ❑ ❑ ❑' ❑ ❑ El El ❑ ❑ ■,❑ ❑ 0 ❑ ❑ ❑ Page# 6 Permit: NC0034860 Inspection Date: 11/14/2017 Owner -Facility: Schneider Mills WWTP Inspection Type: Compliance Evaluation Drying Beds Is there adequate drying bed space? Is the sludge distribution on drying beds appropriate? Are the drying beds free of vegetation? # Is the site free of dry sludge remaining in beds? Is the site free of stockpiled sludge? Is the filtrate from sludge drying beds returned to the front of the plant? # Is the sludge disposed of through county landfill? # Is the sludge land applied? (Vacuum filters) Is polymer mixing adequate? Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑. ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ El. '� ❑ Comment: The dewatered sludge& from the wastewater treatment system (drying beds) and water treatment -system are transported to the Alexander County Landfill for disposal. Page# 7