HomeMy WebLinkAboutWQ0016376_Final Permit_20201020ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANI£L SMITH
Director
JOSEPH P. VILLARI — OWNER
S & J VILLARI LIVESTOCK LLC
892 PENNY BRANCH ROAD
WARSAW, NORTH CAROLINA 28398
Dear Mr. Villari:
NORTH CAROLINA
Environmental Quality
October 20, 2020
Subject: Permit No. WQ0016376
S & J Villari Livestock WWTF
Wastewater Irrigation System
Duplin County
In accordance with your permit minor modification request received April 22, 2020, and subsequent
additional information received July 6, 2020 and September 8, 2020, we are forwarding herewith Permit
No. WQ0016376 dated October 20, 2020, to S & J Villari Livestock LLC for the construction and operation
of the permitted modifications, as well as the continued operation of the existing wastewater treatment and
irrigation facilities.
The following modifications to the subject permit are as follows: Adjusted the acreages for Zones
1 and 2; adding a pump station with a 240 gallon per minute (GPM) pump and approximately 320 linear
feet 4-inch force main.
This permit shall be effective from the date of issuance through November 30, 2025, shall void
Permit No. WQ0016376 issued January 3, 2020, and shall be subject to the conditions and limitations
therein. The Permittee shall submit a renewal application no later than June 3, 2025.
Please pay attention to the monitoring requirements listed Attachments A, B, and C for they may
differ from the previous permit issuance. Failure to establish an adequate system for collecting and
maintaining the required operational information shall result in future compliance problems.
The following permit conditions are new since the last permit issuance dated January 3, 2020:
➢ Condition I.I. — The condition requires an Engineering Certification be submitted upon
completion of construction and prior to operation of the permitted modifications.
➢ Condition L2 — The condition requires the Permittee to notify the Wilmington Regional Office
prior to the initial operation of the constructed facilities.
➢ Condition L3. — The condition requires a Final Operation and Maintenance Plan be submitted.
D Q
�� North Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 1 1617 Mail Service Center I Raleigh, North Carolina 27699-1617
NOR fH CA�in!.INA
14'torenwm—ta�a"1 919,707.9000
Mr. Joseph P. Villari
October 20, 2020
Page 2 of 2
If any parts, requirements, or limitations contained in this permit are unacceptable, the Permittee
has the right to request an adjudicatory hearing upon written request within 30 days following receipt of
this permit. This request shall be in the form of a written petition, conforming to Chapter 150B of the North
Carolina General Statutes, and filed with the Office of Administrative Hearings at 6714 Mail Service
Center, Raleigh, NC 27699-6714. Otherwise, this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this permit, please contact Vivien Zhong at (919) 707-3627 or
vivien.zhongkncdenr.gov.
Sincerely,
7L4( �-2)
S. Daniel Smith, Director
Division of Water Resources
cc: Duplin County Health Department (Electronic Copy)
Wilmington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Jeff Cappadona, PE — Cavanaugh & Associates, P.A. (Electronic Copy)
Laserfiche File (Electronic Copy)
Digital Permit Archive (Electronic Copy)
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
RALEIGH
WASTEWATER IRRIGATION SYSTEM PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
S & J Villari Livestock LLC
Duplin County
FOR THE
operation of a 100,260 gallon per day (GPD) wastewater treatment and irrigation facility consisting of the:
construction and operation of. a pump station with a 240 gallon per minute (GPM) pump; approximately
320 linear feet (LF) of 4-inch force main; and all associated piping, valves, controls, and appurtenances;
and the
continued operation of. a T-R solids separator; a curbed 20-feet by 24-feet solids collection area with
leachate collection and daily solids rendering collection; a 10,000 gallon storage tank; a 2,000 gallon pump
tank with dual solids handling pumps; a 3.65 million gallon (MG) synthetically -lined facultative lagoon
with a curtain baffle separating it into two zones, and served by two 10 horsepower (hp) floating aerators;
a 1.88 MG above -ground stainless steel storage tank; a 21,000 gallon chlorine contact chamber; a 41.09
acre spray irrigation area consisting of 18 zones ; and all associated piping, valves, controls, and
appurtenances
to serve the S & J Villari Livestock WWTF, with no discharge of wastes to surface waters, pursuant to the
application received April 22, 2020, subsequent additional information received July 6, 2020 and
September 8, 2020, and in conformity with the Division -approved plans and specifications considered a
part of this permit.
This permit shall be effective from the date of issuance through November 30, 2025, shall void Permit No.
WQ0016376 issued January 3, 2020, and shall be subject to the following conditions and limitations:
I. SCHEDULES
Upon completion of construction and prior to operation of the permitted modifications, the Permittee
shall submit an engineering certification from a North Carolina licensed Professional Engineer
certifying that the permitted facility has been constructed in accordance with G.S. 143-215.1,
Administrative Code Title 15A Subchapter 02T, this permit, and the Division -approved plans and
specifications. For phased and partially certified facilities, the Permittee shall retain the responsibility
to track further construction approved under this permit, and shall provide a final engineering
certification upon project completion. Mail the Engineering Certification to the Division of Water
Resources, Non -Discharge Branch, 1617 Mail Service Center, Raleigh, NC 27699-1617, or Non-
Discharge.Reports&ncdenr.gov. [15A NCAC 02T .0116(a)]
WQ0016376 Version 4.1 Shell Version 200201 Page 1 of 11
2. The Permittee shall notify the Wilmington Regional Office, telephone number (910) 796-7215, at least
two business days in advance of initial operation of the constructed facilities so that the Division can
conduct a startup inspection. [15A NCAC 02T .0108(b)(1)(B)]
3. Prior to operation of the newly installed facilities, a Final Operation and Maintenance Plan shall be
submitted for review. The plan shall be sent to the Division of Water Resources, Non -Discharge
Branch, 1617 Mail Service Center, Raleigh, NC 27699-1617 or Non-Discharge.Reportskncdenr.gov.
[15A NCAC 02T .0108(b)(1)(B), 02T .0507(a)]
4. The Permittee shall request renewal of this permit on Division -approved forms no later than June 3,
2025. [15A NCAC 02T .0105(b), 02T .0109]
II. PERFORMANCE STANDARDS
The Permittee shall maintain and operate the subject non -discharge facilities so there is no discharge to
surface waters, nor any contravention of groundwater or surface water standards. In the event the
facilities fail to perform satisfactorily, including the creation of nuisance conditions due to improper
operation and maintenance, or failure of the irrigation areas to assimilate the effluent, the Permittee
shall take immediate corrective actions, including Division required actions, such as the construction
of additional or replacement wastewater treatment or disposal facilities. [15A NCAC 02T
.0108(b)(1)(A)]
2. This permit shall not relieve the Permittee of their responsibility for damages to groundwater or surface
water resulting from the operation of this facility. [15A NCAC 02T .0108(b)(1)(A)]
3. Groundwater monitoring wells shall be constructed in accordance with 15A NCAC 02C .0108
(Standards of Construction for Wells Other than Water Supply), and any other jurisdictional laws and
regulations pertaining to well construction. [15A NCAC 02C .0108]
4. Effluent quality shall not exceed the limitations specified in Attachment A. [15A NCAC 02T .0505(b)]
5. Application rates, whether hydraulic, nutrient, or other pollutant, shall not exceed those specified in
Attachment B. [15A NCAC 02T .0505(c), 02T .0505(n)]
6. Wastewater irrigation fields permitted on or after December 30, 1983 have a compliance boundary that
is either 250 feet from the wastewater irrigation area, or 50 feet within the property boundary,
whichever is closest to the wastewater irrigation area. Any exceedance of groundwater standards at or
beyond the compliance boundary shall require corrective action. Division -approved relocation of the
compliance boundary shall be noted in Attachment B. Multiple contiguous properties under common
ownership and permitted for use as a disposal system shall be treated as a single property with regard
to determination of a compliance boundary. [15A NCAC 02L .0106(d)(2), 02L .0107(b), 02T .0105(h),
G.S. 143-215.1(1), G.S. 143-215.1(k)]
7. The review boundary is midway between the compliance boundary and the wastewater irrigation area.
Any exceedance of groundwater standards at or beyond the review boundary shall require preventative
action. [15A NCAC 02L .0106(d)(1), 02L .0108]
8. The Permittee shall apply for a permit modification to establish a new compliance boundary prior to
any sale or transfer of property affecting a compliance boundary (i.e., parcel subdivision). [ 15A NCAC
02L .0107(c)]
9. No wells, excluding Division -approved monitoring wells, shall be constructed within the compliance
boundary except as provided for in 15A NCAC 02L .0107(g). [15A NCAC 02L .0107]
WQ0016376 Version 4.1 Shell Version 200201 Page 2 of 11
10. Except as provided for in 15A NCAC 02L .0107(g), the Permittee shall ensure any landowner who is
not the Permittee and owns land within the compliance boundary shall execute and file with the Duplin
County Register of Deeds an easement running with the land containing the following items:
a. A notice of the permit and number or other description as allowed in 15A NCAC 02L .0107(f)(1);
b. Prohibits construction and operation of water supply wells within the compliance boundary; and
c. Reserves the right of the Permittee or the State to enter the property within the compliance boundary
for purposes related to the permit.
The Director may terminate the easement when its purpose has been fulfilled or is no longer needed.
[15A NCAC 02L .0107(f)]
11. The facilities herein were permitted per the following setbacks:
a. Fields 1-14 were originally permitted July 27, 2000, July 3, 2003, and April 2, 2004. The setbacks
for spray irrigation sites originally permitted or modified from February 1, 1993 to August 31, 2006
are as follows (all distances in feet):
i. Each habitable residence or place of assembly under separate ownership:
400 1
ii. Each private or public water supply source:
100
iii. Surface waters:
100
iv. Groundwater lowering ditches:
100
v. Surface water diversions (upslope):
100
vi. Surface water diversions (downslope):
100
vii. Each well with exception of monitoring wells:
100
viii. Each property line:
150 '`
ix. Top of slope of embankments or cuts of two feet or more in vertical height:
15
x. Each water line:
10
xi. Each swimming pool:
100
xii. Public right of way:
50
xiii. Nitrification field:
20
xiv. Each building foundation or basement:
15
' Habitable residences or places of assembly under separate ownership constructed after the
facilities herein were originally permitted or subsequently modified are exempt from this
setback.
2 Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[15A NCAC 02H .02190)(5)]
WQ0016376 Version 4.1 Shell Version 200201 Page 3 of 11
b. Fields 15-17 were originally permitted May 17, 2013. The setbacks for spray irrigation sites
originally permitted or modified from September 1, 2006 to August 31, 2018 are as follows (all
distances in feet):
i.
Each habitable residence or place of assembly under separate ownership:
400 1
ii.
Each habitable residence or place of assembly owned by the Permittee:
200
iii.
Each private or public water supply source:
100
iv.
Surface waters:
100
v.
Groundwater lowering ditches:
100
vi.
Surface water diversions:
25
vii.
Each well with exception of monitoring wells:
100
viii.
Each property line:
150 2
ix.
Top of slope of embankments or cuts of two feet or more in vertical height:
15
x.
Each water line:
10
xi. Subsurface groundwater lowering drainage systems: 100
xii. Each swimming pool: 100
xiii. Public right of way: 50
xiv. Nitrification field: 20
xv. Each building foundation or basement: 15
' Habitable residences or places of assembly under separate ownership constructed after the
facilities herein were originally permitted or subsequently modified are exempt from this
setback.
2 Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[15A NCAC 02T .0506(a), 02T .0506(e), 02T .0506(fl]
c. The storage and treatment units were modified May 17, 2013. The setbacks for storage and
treatment units originally permitted or modified from September 1, 2006 to August 31, 2018 are as
follows (all distances in feet):
i. Each habitable residence or place of assembly under separate ownership: 1001
ii. Each private or public water supply source: 100
iii. Surface waters: 50
iv. Each well with exception of monitoring wells: 100
v. Each property line: 50 2
' Habitable residences or places of assembly under separate ownership constructed after the
facilities herein were originally permitted or subsequently modified are exempt from this
setback.
2 Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[15A NCAC 02T .0506(b), 02T .0506(e), 02T .0506(f)]
WQ0016376 Version 4.1 Shell Version 200201 Page 4 of 11
III. OPERATION AND MAINTENANCE REQUIREMENTS
1. The Permittee shall operate and maintain the subject facilities as anon -discharge system. [15A NCAC
02T .0500]
2. The Permittee shall maintain an Operation and Maintenance Plan, which shall include operational
functions, maintenance schedules, safety measures, and a spill response plan. [15A NCAC 02T
.0507(a)]
3. Upon the Water Pollution Control System Operators Certification Commission's (WPCSOCC)
classification of the subject non -discharge facilities, the Permittee shall designate and employ a certified
operator in responsible charge (ORC), and one or more certified operators as back-up ORCs. The ORC
or their back-up shall operate and visit the facilities as required by the WPCSOCC. [15A NCAC 02T
.0117]
4. The Permittee shall maintain vegetative cover on the irrigation sites, such that crop health is optimal,
allows even effluent distribution, and allows inspection of the irrigation system. [15A NCAC 02T
.0507(b)]
5. The Permittee shall take measures to prevent effluent ponding in or runoff from the irrigation sites
listed in Attachment B. [15A NCAC 02T .0507(c)]
6. The Permittee shall not irrigate treated effluent during inclement weather, or when the soil is in a
condition that will cause ponding or runoff. [15A NCAC 02T .0505(x)]
7. Irrigation equipment shall be tested and calibrated once per permit cycle. [15A NCAC 02T .0507(d)]
8. Only treated effluent from the S & J Villari Livestock WWTF shall be irrigated on the sites listed in
Attachment B. [15A NCAC 02T .0501]
9. The Permittee shall not allow vehicles or heavy machinery on the irrigation area, except during
equipment installation or maintenance activities. [15A NCAC 02T .0507(e)]
10. The Permittee shall prohibit public access to the wastewater treatment, storage, and irrigation facilities.
[15A NCAC 02T .0505(q)]
11. The Permittee shall dispose or utilize generated residuals in a Division -approved manner. [15A NCAC
02T .0508, 02T .I 100].
12. The Permittee shall not divert or bypass untreated or partially treated wastewater from the subject
facilities. [15A NCAC 02T .05050)]
13. Freeboard in the 3.65 MG facultative lagoon and the 1.88 MG above -ground stainless steel storage tank
shall not be less than two feet at anytime. [15A NCAC 02T .0505(d)]
14. Gauges to monitor waste levels in the 3.65 MG facultative lagoon and the 1.88 MG above -ground
stainless steel storage tank shall be provided. These gauges shall have readily visible permanent
markings, at inch or tenth of a foot increments, indicating the following elevations: maximum liquid
level at the top of the temporary liquid storage volume; minimum liquid level at the bottom of the
temporary liquid storage volume; and the lowest point on top of the dam. [15A NCAC 02T .0507(f)]
15. A protective vegetative cover shall be established and maintained on all berms, pipe runs, erosion
control areas, surface water diversions, and earthen embankments (i.e., outside toe of embankment to
maximum allowable temporary storage elevation on the inside of the embankment). Trees, shrubs, and
other woody vegetation shall not be allowed to grow on the earthen dikes or embankments. Earthen
embankments shall be kept mowed or otherwise controlled and accessible. [15A NCAC 02T .0507(g)]
WQ0016376 Version 4.1 Shell Version 200201 Page 5 of 11
16. Metering equipment shall be tested and calibrated annually. [15A NCAC 02T .0507(d)]
IV. MONITORING AND REPORTING REQUIREMENTS
The Permittee shall conduct and report any Division required monitoring necessary to evaluate this
facility's impact on groundwater and surface water. [15A NCAC 02T .0108(c)]
2. A Division -certified laboratory shall conduct all analyses for the required effluent, groundwater, and
surface water parameters. [15A NCAC 02H .0800]
3. Flow through the treatment facility shall be continuously monitored, and daily flow values shall be
reported on Form NDMR. Facilities with a permitted flow less than 10,000 GPD may estimate their
flow from water usage records provided the water source is metered. [15A NCAC 02T .0105(k), 02T
.0108(c)]
4. The Permittee shall monitor the treated effluent at the frequencies and locations for the parameters
specified in Attachment A. [15A NCAC 02T .0108(c)]
5. The Permittee shall maintain records tracking the amount of effluent irrigated. These records shall
include the following information for each irrigation site listed in Attachment B:
a. Date of irrigation;
b. Volume of effluent irrigated;
c. Site irrigated;
d. Length of time site is irrigated;
e. Continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings;
f. Continuous monthly and year-to-date loadings for any non -hydraulic parameter specifically
limited in Attachment B;
g. Weather conditions; and
h. Maintenance of cover crops.
[15A NCAC 02T .0108(c)]
6. Freeboard (i.e., waste level to the lowest embankment elevation) in the 3.65 MG facultative lagoon and
the 1.88 MG above -ground stainless steel storage tank shall be measured to the nearest inch or tenth of
a foot, and recorded weekly. Weekly freeboard records shall be maintained for five years, and shall be
made available to the Division upon request. [15A NCAC 02T .0108(c)]
7. Three copies of all monitoring data (as specified in Conditions IV.3. and IVA.) on Form NDMR for
each PPI and three copies of all operation and disposal records (as specified in Conditions IV.S. and
IV.6.) on Form NDAR-I, and three copies of all field loading records on Form NDMLR for every site
in Attachment B shall be submitted on or before the last day of the following month. NDMLR data
shall include cover crop type and PAN loading for each month as well as cumulative PAN loading for
the year. If no activities occurred during the monitoring month, monitoring reports are still required
documenting the absence of the activity. All information shall be submitted to the following address:
Division of Water Resources
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
[15A NCAC 02T .0105(l)]
WQ0016376 Version 4.1 Shell Version 200201 Page 6 of 11
8. The Permittee shall maintain a record of all residuals removed from this facility. This record shall be
maintained for five years, and shall be made available to the Division upon request. This record shall
include:
a. Name of the residuals hauler;
b. Non -Discharge permit number authorizing the residuals disposal, or a letter from a municipality
agreeing to accept the residuals;
c. Date the residuals were hauled; and
d. Volume of residuals removed.
[15A NCAC 02T .0508(b)]
9. A maintenance log shall be kept at this facility. This log shall be maintained for five years, and shall
be made available to the Division upon request. This log shall include:
a. Date of flow measurement device calibration;
b. Date of irrigation equipment calibration;
c. Visual observations of the plant and plant site; and
d. Record of preventative maintenance (e.g., changing of equipment, adjustments, testing, inspections
and cleanings, etc.).
[15A NCAC 02T .0507(h)]
10. Monitoring wells MW-1, MW-2, MW-3, MW-5, MW-6, MW-7, MW-8, and MW-9 shall be sampled
at the frequencies and for the parameters specified in Attachment C. All mapping, well construction
forms, well abandonment forms and monitoring data shall refer to the permit number and the well
nomenclature as provided in Attachment C and Figure 1. [15A NCAC 02T .0105(m)]
11. Two copies of the monitoring well sampling and analysis results shall be submitted on a Compliance
Monitoring Form (GW-59), along with attached copies of laboratory analyses, on or before the last
working day of the month following the sampling month. The Compliance Monitoring Form (GW-59)
shall include this permit number, the appropriate well identification number, and one GW-59a
certification form shall be submitted with each set of sampling results. All information shall be
submitted to the following address:
Division of Water Resources
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
[15A NCAC 02T .0105(m)]
12. An annual representative soils analysis (i.e., Standard Soil Fertility Analysis) shall be conducted on
each irrigation site listed in Attachment B. These results shall be maintained at the facility for five
years, and shall be made available to the Division upon request. Each Standard Soil Fertility Analysis
shall include the following parameters:
Acidity
Exchangeable Sodium Percentage
Phosphorus
Base Saturation (by calculation)
Magnesium
Potassium
Calcium
Manganese
Sodium
Cation Exchange Capacity
Percent Humic Matter
Zinc
Copper
pH
[15A NCAC 02T .0108(c)]
WQ0016376 Version 4.1 Shell Version 200201 Page 7 of 11
13. Noncompliance Notification:
The Permittee shall report to the Wilmington Regional Office, telephone number (910) 796-7215,
within 24 hours of first knowledge of the following:
a. Treatment of wastes abnormal in quantity or characteristic, including the known passage of a
hazardous substance.
b. Any process unit failure (e.g., mechanical, electrical, etc.) rendering the facility incapable of
adequate wastewater treatment.
c. Any facility failure resulting in a discharge to surface waters.
d. Any time self -monitoring indicates the facility has gone out of compliance with its permit
limitations.
e. Ponding in or runoff from the irrigation sites.
Emergencies requiring reporting outside normal business hours shall call the Division's Emergency
Response personnel at telephone number (800) 662-7956, (800) 858-0368, or (919) 733-3300. All
noncompliance notifications shall file a written report to the Wilmington Regional Office within five
days of first knowledge of the occurrence, and this report shall outline the actions proposed or taken to
ensure the problem does not recur. [15A NCAC 02T .0108(b)(1)(A)]
V. INSPECTIONS
1. The Permittee shall perform inspections and maintenance to ensure proper operation of the wastewater
treatment and irrigation facilities. [15A NCAC 02T .0507(i)]
2. The Permittee shall inspect the wastewater treatment and irrigation facilities to prevent malfunctions,
facility deterioration, and operator errors that may result in discharges of wastes to the environment,
threats to human health, or public nuisances. The Permittee shall maintain an inspection log that
includes the date and time of inspection, observations made, and maintenance, repairs, or corrective
actions taken. The Permittee shall maintain this inspection log for a period of five years from the date
of the inspection, and this log shall be made available to the Division upon request. [15A NCAC 02T
.0507(h), 02T .0507(i)]
3. Division authorized representatives may, upon presentation of credentials, enter and inspect any
property, premises, or place related to the wastewater treatment and irrigation facilities permitted herein
at any reasonable time for determining compliance with this permit. Division authorized
representatives may inspect or copy records maintained under the terms and conditions of this permit,
and may collect groundwater, surface water, or leachate samples. [G.S. 143-215.3(a)(2)]
WQ0016376 Version 4.1 Shell Version 200201 Page 8 of 11
VI. GENERAL CONDITIONS
1. Failure to comply with the conditions and limitations contained herein may subject the Permittee to a
Division enforcement action. [G.S. 143-215.6A, 143-215.613, 143-215.6C]
2. This permit is effective only with respect to the nature and volume of wastes described in the permit
application, and Division -approved plans and specifications. [G.S. 143-215.1(d)]
3. Unless specifically requested and approved in this permit, there are no variances to administrative codes
or general statutes governing the construction or operation of the facilities permitted herein. [15A
NCAC 02T .0105(n)]
4. The issuance of this permit does not exempt the Permittee from complying with all statutes, rules,
regulations, or ordinances that other jurisdictional government agencies (e.g., local, state, and federal)
may require. [15A NCAC 02T .0105(c)(6)]
5. If the permitted facilities change ownership, or the Permittee changes their name, the Permittee shall
submit a permit modification request on Division -approved forms. The Permittee shall comply with
all terms and conditions of this permit until the permit is transferred to the successor -owner. [G.S. 143-
215.1(d3)]
6. The Permittee shall retain a set of Division -approved plans and specifications for the life of the facilities
permitted herein. [15A NCAC 02T .0105(o)]
7. The Permittee shall maintain this permit until the proper closure of all facilities permitted herein, or
until the facilities permitted herein are permitted by another authority. [15A NCAC 02T .01050)]
8. This permit is subject to revocation or modification upon 60-day notice from the Division Director, in
whole or part for:
a. violation of any terms or conditions of this permit or Administrative Code Title 15A Subchapter
02T;
b. obtaining a permit by misrepresentation or failure to disclose all relevant facts;
c. the Permittee's refusal to allow authorized Department employees upon presentation of credentials:
I. to enter the Permittee's premises where a system is located or where any records are required
to be kept;
ii. to have access to any permit required documents and records;
iii. to inspect any monitoring equipment or method as required in this permit; or
iv. to sample any pollutants;
d. the Permittee's failure to pay the annual fee for administering and compliance monitoring; or
e. a Division determination that the conditions of this permit are in conflict with North Carolina
Administrative Code or General Statutes.
[15A NCAC 02T .0110]
WQ0016376 Version 4.1 Shell Version 200201 Page 9 of 11
9. Unless the Division Director grants a variance, expansion of the facilities permitted herein shall not
occur if any of the following apply:
a. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has been convicted of
environmental crimes under G.S. 143-215.6B, or under Federal law that would otherwise be
prosecuted under G.S. 143-215.6B, and all appeals of this conviction have been abandoned or
exhausted.
b. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has previously abandoned
a wastewater treatment facility without properly closing the facility.
c. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid a civil
penalty, and all appeals of this penalty have been abandoned or exhausted.
d. The Permittee or any parent, subsidiary, or other affiliate of the Permittee is currently not compliant
with any compliance schedule in a permit, settlement agreement, or order.
e. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid an annual
fee.
[15A NCAC 02T .0120(b), 02T .0120(d)]
10. This permit shall not be renewed if the Permittee or any affiliation has not paid the required annual fee.
[15A NCAC 02T .0120(c)]
Permit issued this the 20'h day of October 2020
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
7L46..�-z
S. Daniel Smith, Director
Division of Water Resources
By Authority of the Environmental Management Commission
Permit Number WQ0016376
WQ0016376 Version 4.1 Shell Version 200201 Page 10 of 11
Permit No. WQ0016376
S & J Villari Livestock LLC
S & J Villari Livestock WWTF
ENGINEERING CERTIFICATION
❑ Partial ❑ Final
Wastewater Irrigation System
October 20, 2020
Duplin County
I, , as a duly licensed North Carolina Professional
Engineer, having ❑ periodically / ❑ fully observed the construction of the permitted facilities, do hereby
state to the best of my abilities that the facility was constructed in compliance with G.S. 143-215.1,
Administrative Code Title 15A Subchapter 02T, this permit, and the Division -approved plans and
specifications.
Documentation of any variation to this permit, and the Division -approved plans and specifications, is in the
attached as -built drawings.
Description of variations:
Professional Engineer's Name
Firm Name
Firm No.
Address
City JL
State
Zip Code
Telephone
Email
Seal, Signature, and Dateaj
THE COMPLETED ENGINEERING CERTIFICATION, INCLUDING ALL SUPPORTING
DOCUMENTATION, SHALL BE SENT TO THE FOLLOWING ADDRESS:
NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY
DIVISION OF WATER RESOURCES
NON -DISCHARGE BRANCH
By U.S. Postal Service By Courier/Special DelivM
1617 MAIL SERVICE CENTER 512 N. SALISBURY ST.
RALEIGH, NORTH CAROLINA 27699-1617 RALEIGH, NORTH CAROLINA 27604
WQ0016376 Version 4.1 Shell Version 200201 Page 11 of 11
THIS PAGE BLANK
ATTACHMENT A — LIMITATIONS AND MONITORING REQUIREMENTS
PPI 001— WWTF Effluent
Permit Number: WQ0016376 Version: 4.1
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCS
Code
Parameter Description
Units of
Measure
Monthly
Average
Monthly
Geometric Mean Daily Minimum Daily Maximum
Measurement
Frequency
Sample
Type
00310
BOD, 5-Day (20 °C)
mg/L
Monthly
Grab
00940
Chloride (as Cl)
mg/L
3 x Year'
Grab
50060
Chlorine, Total Residual
mg/L
Weekly
Grab
31616
Coliform, Fecal MF, M-FC Broth, 44.5 °C
#/100 mL
Monthly
Grab
50050
Flow, in Conduit or thru Treatment Plant
GPD
100,260
Continuous
Recorder
00610
Nitrogen, Ammonia Total (as N)
mg/L
Monthly
Grab
00625
Nitrogen, Kjeldahl, Total (as N)
mg/L
Monthly
Grab
00620
Nitrogen, Nitrate Total (as N)
mg/L
Monthly
Grab
00600
Nitrogen, Total (as N)
mg/L
Monthly
Grab
00400
pH
su
Weekly
Grab
00665
Phosphorus, Total (as P)
mg/L
Monthly
Grab
70300
Solids, Total Dissolved — 180 °C
mg/L
3 x Year'
Grab
00530
Solids, Total Suspended
mg/L
Monthly
Grab
3 x Year monitoring shall be conducted in March, July, and November.
WQ0016376 Version 4.1 Attachment A Page 1 of 2
PPI 002 - Surface Water Monitoring Upstream
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCS
Code
Parameter Description
Units of
Measure
Monthly
Average
Monthly
Geometric Mean Daily Minimum Daily Maximum
Measurement
Frequency
Sample
Type
31616
Coliform, Fecal MF, M-FC Broth, 44.5 °C
#/100 mL
Monthly
Grab
00610
Nitrogen, Ammonia Total (as N)
mg/L
Monthly
Grab
00625
Nitrogen, Kjeldahl, Total (as N)
mg/L
Monthly
Grab
00620
Nitrogen, Nitrate Total (as N)
mg/L
Monthly
Grab
00600
Nitrogen, Total (as N)
mg/L
Monthly
Grab
00665
Phosphorus, Total (as P)
mg/L
Monthly
Grab
PPI 003 - Surface Water Monitoring Downstream
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCs
Code
Parameter Description
Units of
Measure
Monthly Monthly Daily Minimum Daily Maximum
Average Geometric Mean
Measurement
Frequency
Sample
Type
31616
Coliform, Fecal MF, M-FC Broth, 44.5 °C
#/100 mL
Monthly
Grab
00610
Nitrogen, Ammonia Total (as N)
mg/L
Monthly
Grab
00625
Nitrogen, Kjeldahl, Total (as N)
mg/L
Monthly
Grab
00620
Nitrogen, Nitrate Total (as N)
mg/L
Monthly
Grab
00600
Nitrogen, Total (as N)
mg/L
Monthly
Grab
00665
j Phosphorus, Total (as P)
j mg/L
j
Monthly
Grab
WQ0016376 Version 4.1 Attachment A Page 2 of 2
ATTACHMENT B - APPROVED LAND APPLICATION SITES AND LIMITATIONS Permit Number: WQ0016376 Version: 4.1
S & J Villari Livestock LLC - S & J Villari Livestock WWTF
IRRIGATION AREA INFORMATION
APPLICATION LIMITATIONS
Field
Owner
County
Latitude
LongitudejNeDominant
Parameter
Hourly
Yearly
Double
Units
Soil Series
Rate
Max
Cro in1
S & J Villari Livestock LLC
Duplin
35.007257'
-78.120914'Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitro en - Loadin
300
350
lbs/acre
2
S & J Villari Livestock LLC
Duplin
35.007076'
-78.120648'Norfolk
01284 - lant Discharge Application Rate
0.6
41.96
inches
WQ09 -Plant Available Nitro en -Loadin
300
350
lbs/acre
3
S & J Villari Livestock LLC
Duplin
35.006930°
-78.120309°Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
4
S & J Villari Livestock LLC
Duplin
35.006808°
-78.119948°Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
5
S & J Villari Livestock LLC
Duplin
35.006687°
-78.119725°
1.19
Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
6
S & J Villari Livestock LLC
Duplin
35.006577'
-78.119378'
1.17
Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
7
S & J Villari Livestock LLC
Duplin
35.008520'
-78.119198'
1.05
Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
8
S & J Villari Livestock LLC
Duplin
35.007946'
-78.119001 °
1.25
Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
9
S & J Villari Livestock LLC
Duplin
35.007752'
-78.119358'
1.00
Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
10
S & J Villari Livestock LLC
Duplin
35.006378'
-78.119018'
1.46
Goldsboro
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
11
S & J Villari Livestock LLC
Duplin
35.006798'
-78.118499'
1.43
Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
12
S & J Villari Livestock LLC
Duplin
35.006555'
-78.118001'
1.23
Norfolk
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
13
S & J Villari Livestock LLC
Duplin
35.008212'
-78.118708'
2.19
Goldsboro
01284 - Non -Discharge Application Rate
0.6
41.96
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
14E
RSJ Properties, LLC 1
Duplin
35.010430'
-78.120250'
13.73
Goldsboro
01284 - Non -Discharge Application Rate
0.6
31.60
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
14W
RSJ Properties, LLC i
Duplin
35.011560'
-78.121484'
7.70
Goldsboro
01284 - Non -Discharge Application Rate
0.6
24.21
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
15
S & J Villari Livestock LLC
Duplin
35.007315'
-78.119095'
0.73
Norfolk
01284 - Non -Discharge Application Rate
0.6
30.44
inches
WQ09 - Plant Available Nitrogen - Loading
300
1 350
lbs/acre
16
S & J Villari Livestock LLC
Duplin
35.008628°
-78.120044°
1.25
Goldsboro
01284 - Non -Discharge Application Rate
0.6
13.83
inches
WQ09 - Plant Available Nitrogen - Loading
300
350
lbs/acre
17
S & J Villari Livestock LLC
Duplin
35.008315°
-78.121265'
0.82
Bibby
01284 - Non -Discharge Application Rate
0.5
16.95
inches
WQ09 -Plant Available Nitrogen -Loadin
300
350
lbs/acre
Totals
41.09
1. An easement recorded in the Duplin County Register of deeds (BK: 1906 PG: 489-493) allows the use of the parcel of land owned by RSJ Properties, LLC by S & J Villari Livestock LLC for the
irrigation of treated wastewater
WQ0016376 Version 4.1 Attachment B Page 1 of 1
THIS PAGE BLANK
ATTACHMENT C — GROUNDWATER MONITORING AND LIMITATIONS Permit Number: WQ0016376 Version: 4.1
Monitoring Wells: MW-1, MW-2, MW-3, MW-5, MW-6, MW-7, MW-8, and MW-9
GROUNDWATER CHARACTERISTICS
GROUNDWATER STANDARDS
MONITORING REQUIREMENTS
PCS Code
Parameter Description
Daily Maximum
Frequency Measurement
Sample Type
Footnotes
00680
Carbon, Tot Organic (TOC)
mg/L
3 x Year
Grab
1,6
00940
Chloride (as Cl)
250
mg/L
3 x Year
Grab
1
31616
Coliform, Fecal MF, M-FC Broth, 44.5 °C
#/100 mL
3 x Year
Grab
1
00610
Nitrogen, Ammonia Total (as N)
1.5
mg/L
3 x Year
Grab
1
00620
Nitrogen, Nitrate Total (as N)
10
mg/L
3 x Year
Grab
1
00400
pH
6.5-8.5
su
3 x Year
Grab
1,2
00665
Phosphorus, Total (as P)
mg/L
3 x Year
Grab
1
70300
Solids, Total Dissolved - 180 °C
500
mg/L
3 x Year
Grab
1
GWVOC
Volatile Compounds (GW)
Present: Yes/No
Annually
Grab
1, 4, 5
82546
Water Level, Distance from measuring point
feet
3 x Year
Calculated
L2,3
1. 3 x Year monitoring shall be conducted in March, July, and November; Annual monitoring shall be conducted in November.
2. The measurement of water levels shall be made prior to purging the wells. The depth to water in each well shall be measured from the surveyed point on the top of the casing. The measurement of
pH shall be made after purging and prior to sampling for the remaining parameters.
3. The measuring points (top of well casing) of all monitoring wells shall be surveyed to provide the relative elevation of the measuring point for each monitoring well. The measuring points (top of
casing) of all monitoring wells shall be surveyed relative to a common datum.
4. Volatile Organic Compounds (VOC) - In November only, analyze by one of the following methods:
a. Standard Method 6230D, PQL at 0.5 gg/L or less
b. Standard Method 6210D, PQL at 0.5 gg/L or less
c. EPA Method 8021, Low Concentration, PQL at 0.5 gg/L or less
d. EPA Method 8260, Low Concentration, PQL at 0.5 gg/L or less
e. Another method with prior approval by the Water Quality Permitting Section Chief
Any method used shall meet the following qualifications:
a. A laboratory shall be DWR certified to run any method used.
b. The method used shall include all the constituents listed in Table VIII of Standard Method 6230D.
c. The method used shall provide a PQL of 0.5 gg/L or less that shall be supported by laboratory proficiency studies as required by the DWR Laboratory Certification Unit. Any constituents
detected above the MDL but below the PQL of 0.5 gg/L shall be qualified (estimated) and reported.
5. If any volatile organic compounds (VOC) are detected as a result of monitoring as provided in Attachment C, then the Wilmington Regional Office supervisor, telephone number (910) 796-7215,
shall be contacted immediately for further instructions regarding any additional follow-up analyses required.
6. If TOC concentrations greater than 10 mg/L are detected in any downgradient monitoring well, additional sampling and analysis shall be conducted to identify the individual constituents comprising
this TOC concentration. If the TOC concentration as measured in the background monitor well exceeds 10 mg/L, this concentration will be taken to represent the naturally occurring TOC
concentration. Any exceedances of this naturally occurring TOC concentration in the downgradient wells shall be subject to the additional sampling and analysis as described above.
7. Monitoring wells shall be reported consistent with the nomenclature and location information provided in Figure 1 and this attachment.
WQ0016376 Version 4.1 Attachment C Page 1 of 1
Figure 1 - S & J Villari Livestock WWTF