HomeMy WebLinkAboutSW8970616_COMPLIANCE_20120722STORMWATER DIVISION CODING SHEET POST -CONSTRUCTION PERMITS PERMIT NO. SW�(CIrlDill� DOC TYPE ❑ CURRENT PERMIT ❑ APPROVED PLANS ❑ HISTORICAL FILE COMPLIANCE EVALUATION INSPECTION DOC DATE YYYYMMDD HIGH DENSITY STATE STORMWATER INSPECTION REPORT Project Name: Trolley Path Condo Association Permit No: SW8970616 Expiration date: 7/22/2015 Contact Person: Joseph Shapira Phone No: 910-452-3555 County: New Hanover Center of Project GPS: Lat: 340 13' 34.68 "N Long: 770 55' 00.14 "W Facility Address: Wrightsville Ave. near RR and Spofford. City: Wilmington Zip: 28403 (If multiple basins exist, specify basin(s): Entry time: 1:30 am ❑ pm ® Exit time: 2:05 am ❑ pm ® Date: 6/25/08 Method of Treatment: (check one) ® Wet Detention ❑ Dry Detention ❑ Bioretention ❑ Wetland ❑ Sandfilter ❑ Swale ❑ Pocket Wetland ❑ Level Spreader ❑ Permeable Pavement ❑ Infiltration Basin Other: ❑ Receiving Waters: Burnt Mill Creek . Classification: C-Sw River Basin: Cape Fearr GENERAL QUESTIONS FILE REVIEW 1. A signed copy of the Engineer's certification is in the files: 2. A signed copy of the Operation & Maintenance Agreement is in the files: 3. A copy of the recorded deed restrictions is in the files: SITE VISIT 1. Drainage area is consistent with the permit: 2. Built -upon area to drainage area is consistent with the permit: 3. All built -upon area (as permitted) is graded such that'the runoff drains to the system: 4. The outlet structure is located per the approved plans: 5. The trash rack is provided on the outlet/bypass structure: 6. The trash rack is free of debris and excess trash: 7. All slopes are grassed with permanent vegetation: 8. Vegetated slopes are no steeper than 3:1 9. The inlets are located per the approved plans and do not cause short-circuiting of the system: YES NO HLA NE ® ❑ ❑ - ❑ YES NO NA NE 10. Access points are clear and well maintained: ® ❑ ❑ ❑ 11. Forebay is free of excessive sediment: ❑ ® ❑ ❑ 12. Banks are stable with no erosion present: ❑ ® ❑ ❑ 13. Vegetation and trash have been removed as needed: ❑ ® ❑ ❑ 14. Drawdown device is correctly sized per the approved plans: ® ❑ ❑ ❑ 15. Grass is mowed (not scalped) as required: ® ❑ ❑ ❑ 16. All required parts of the system are provided (such as vegetated shelf and a forebay): ® ❑ ❑ ❑ 17. The swale or outlet bypass is in the correct place and is in good condition: ® ❑ ❑ ❑ 18. Vegetated shelf is 6:1 and properly vegetated: ® ❑ ❑ ❑ 19. Invasive species/tree control is provided as needed ® ❑ ❑ ❑ 20. Tree pruning, mulch and plant replacement are provided as needed in the bioretention basin: ❑ ❑ ® ❑ 21. Permeable pavement has had regular sweeping and vacuuming: ❑ ❑ ® ❑ 22. Gravel replacement is performed as needed: ❑ ❑ ® ❑ 23. Excessive landscape debris (grass clippings, leaves, & sediment) are controlled: ❑ ❑ ® ❑ 24. Large stemmed vegetation is kept off of the level spreader: ❑ ❑ ® ❑ 25. Sediment and debris is removed from behind the lip of the level spreader on a routine basis: ❑ ❑ ® ❑ 26. Maintenance records are available for inspection: ❑ ® ❑ ❑ _COMMENTS: (each NO answer should have a comment) 1. Your permit was reissued on July 22, 2005 and expires on July 22, 2015. 2. This facility is in violation of its' permit conditions for operation and maintenance. 3. There were several roof drains that were directed to the forebay as well as the storage pond. All flow going into the system should enter by way of the inlet structures to the forebay. Flows that enter elsewhere in the system will allow the flow to short circuit and not receive the treatment that it was designed to due to decreased detention times. 4. There were areas of erosion that should be repaired as required by your permit. 5.' The orifice in the outlet structure appeared to be plugged with lawn debris, and trash. You are required to visit the site after every significant runoff producing rainfall event and at least monthly for sediment accumulation, erosion, trash accumulations, vegetated cover and general condition. 6. There appeared to be an excessive amount of sediment in the forebay. You should check the elevations to determine if sediment must be removed. Please refer to your signed Operation and Maintenance agreement for your requirements. 7. Operation and Maintenance records were not available on the inspection date. If you have such records, please submit the last three months of data along with your response to this notice. Be advised that your permit requires that records be kept. 8. The sideslopes and rip -rap are placed where previously approved by Wilmington Regional Office Staff. You must however, repair any areas of erosion around the riprap. _Porch area built over pond slope, rip rap as per previously approved Gutters do not drain to the inlet end of the forebay. with riprap and some erosion present excessive sediment in forebay Forebay erosion and slopes with lack of vegetation Gutters should drain to inlet end of forebay Sideslope erosion rip rap not replaced gutters draining to storage pond causes short circuiting outlet plugged _Flow not exiting pond orifice appeared to be plugged with debris and trash gutter drain causing channeling and erosion Another hidden gutter drain going into storage pond not forebay YES NO Compliant ❑ Non -Compliant ® NOV sent ❑ ❑ Date sent NOV Inspectors name& signature: Pat C Durrett & Rhonda Hall _ Date: 6/25/08 Date Design Check Andrew and Kuske 902 Market St. CONSULTING ENGINEERS, iNC. Wilmington, N.G. 28401 Job For .57a2�w�T�� � L�GGS/G'nJ %��✓I�i-~L cotry+che+at+b��� v4lk�-�l N STORMWA TER E C E 1 V E JUN . 131997 PROJ # fj& jq2Q�p + (p Sheet Job No. R-7«-3 Data for SPOFFORD MILLS (7-9-0 u T4 Page 1 TYPE III 24-HOUR RAINFALL= 7.0 IN Prepared by ANDREW & KUSKE CONSULTING ENGINEERS, INC. 20 May 97 HydroCAQ 4.523 000479 (c) 1986-1996 Applied Microcomputer Systems WATERSHED ROUT'ING OSU3CATCHMENT El REACH /\ POND 1� LINK STORMWATER E C E! V E JUN 1 31997 D E M PROJ # �r Data for SPOFFORD MILLS Page 2 TYPE III 24-HOUR RAINFALL= 7.0 IN Prepared by ANDREW & KUSKE CONSULTING ENGINEERS, INC. 20 May 97 H droCAD 4.523 000479 c 1986-1996 applied Microcomputer Systems SUBCATCHMENT 1 ENTIRE SITE PEAK= 22.00 CFS O 12.02 HRS, VOLUME= 1.52 AF ACRES CN SCS TR-20 METHOD 2.77 98 IMPERVIOUS AREAS TYPE III 24-HOUR 1.94 45 GRASS RAINFALL= 7.0 IN 4.71 76 SPAN= 10-20 HRS, dt=.1 HRS Method Comment Tc min DIRECT ENTRY ENTIRE SITE 5.0 22 22 }B }6 U 12 10 3 O 8 J LL- { 4 2 0m SUBCATCHMENT 1 RUNOFF ENTIRE SITE fV m Q 111 'D TIME Chours) AREA= 4.71 AC Tc= 5 MIN CN- 76 SCS TR--20 METHOD TYPE III 24-HOUR RAINFALL= 7.0 IN PEAK= 22.00 CF5 e 12.02 HRS VOLUME= 1.52 AF r- 07 m m - - - N Data for SPOFFORD MILLS Page 3 TYPE III 24-HOUR RAINFALL= 7.0 IN Prepared by ANDREW & KUSKE CONSULTING ENGINEERS, INC. 20 May 97 HydroCAD 4.523 000479 (c) 1986-1996 Applied Microcomputer Systems REACH 1 OUTLET Qin = 7.09 CPS Q 12.36 HRS, VOLUME= 1.24 AF Qout= 7.09 CPS @ 12.37 HRS, VOLUME= 1.24 AF,. ATTEN= 0%, LAG= .1 MIN DEPTH END AREA DISCH (FT) _ (SQ-FT) (CFS) 24" PIPE STOR-IND+TRANS METHOD 0.0 -0.0 0.00 PEAK DEPTH= .87 FT .2 .2 .36 n= .012 PEAK VELOCITY= 5.4 FPS .4 .4 1.52 LENGTH= 20 FT TRAVEL TIME = .1 MIN .6 .8 3.39 SLOPE= .005 FT/FT SPAN= 10-20 HRS, dt=.1 HRS 1.4 2.3 14.51 1.6 2.7 16.94 1.8 3.0 18.47 1.9 3.1 18.64 1.9 3.1 18.47 2.0 3.1 17.33 REACH 1 DISCHARGE OUTLET ze 1.8 }.6 1.2 1.0 a- w b 0 4 6.0m N M Nr D 0 n m M m- ru v in 0 r 0 DISCHARGE ( cf s ) Data for SPOFFORD MILLS Page 4 TYPE III 24-HOUR RAINFALLS 7.0 IN Prepared by ANDREW & KUSKE CONSULTING ENGINEERS, INC. 20 May 97 HydroCAD 4.523_000479 _(c) 1986-1996 Applied Microcomputer Systems REACH 1 INFLOW & OUTFLOW OUTLET 7.0 6.5 24'' PIPE 5 0 n=.012 L=20' S=.005 5.5 STDR-IND+TRANS METHOD r, 5.0 VELDCITY= 5.4 FPS LO 4.5 TRAUEL= .1 MIN U 4-0 - 3,5 QIn= 7.09 CFS 3.0 Dout= 7.09 CFS O LAG= I MIN 2 5 2.0 1.5 1.0 5 0 0m r Ln - v N TIME (hours) ti Data for SPOFFORD MILLS Page 5 TYPE III 24-HOUR RAINFALL= 7.0 IN Prepared by ANDREW & KUSKE CONSULTING ENGINEERS, INC. 20 May 97 HydroCAD 4.523 000479 (c) 1986-1996 Applied Microcomputer Systems POND 1 POND Qin = 22.00 CFS @ 12.02 HRS, VOLUME= 1.52 AF Qout= 7.09 CFS @ 12.36 HRS, VOLUME= 1.24 AF, ATTEN= 68W, LAG= 20.5 MIN ELEVATION AREA INC.STOR CUM.STOR STOR-IND METHOD (FT) (SF) (CF) (CF) PEAK STORAGE = 44424 CF 17.0 340 0 0 PEAK ELEVATION= 25.5 FT 22.5 6055 17586 17586 FLOOD ELEVATION= 26.0 FT 24.3 9535 14031 31617 START ELEVATION= 22.5 FT 24.5 9960 1949 33567 SPAN= 10-20 HRS, dt=.1 HRS 25.0 11150 5278 38844 Tdet= 166.8 MIN (.84 AF) 26.0 13410 12280 51124 # ROUTE INVERT OUTLET DEVICES 1 P 22.5' 1.8" ORIFICE/GRATE Q=.6 PI r-2 SQR(2g) SQR(H-r) 2 P 24.0' 5' x .25, ORIFICE/GRATE Q=.6 width 2/3 SQR(2g) (H-1.5 - (H-Height]-1.5) 3 P 25.5' 16' SHARP -CRESTED RECTANGULAR WEIR Q=C L H-1.5 C=3.27+.4 H/1 L=Length-0(.1 H) POND i DISCHARGE POND 26.0 B --- 1 6' FaRP-(REST-EREC-T-PNGULRFZ- QEIR 25.5 - - -Sl - - - ;_ - - - - - - - - - - - - - - - 25.8 24.5 - 5' x .25' CRIFICE/GRATE 24.8 - - - - - - - - - - - - - - - - - - - - - - - 23.5 " 23.8 1.8'' ORIFICE/GRRTE 22.5 - - - - - - - - - - - - - - - - - - - - - - - Z 22.0 O 21.5 21 . B 20.5 20.13 w 19.5 -j 19.B w 18-5 1B.13 17.5 17. Bm N ➢ W m N V SA m N ¢ W' M' DISCHARGE (cfs) "Data for SPOFFORD MILLS Page 6 TYPE III 24-HOUR RAINFALL- 7.0 IN Prepared by ANDREW & KUSKE CONSULTING ENGINEERS, INC. 20 May 97 'H droCAD 4.523 000479 c 1986-1996 Applied Microcom uter Systems POND 1 INFLOW 8 OUTFLOW POND 22 20 STOR-IND METHOD 18 PEAK STDR= 44424 CF PEAK ELEU=. 25.5 FT 16 Dina 22.02 CF5 !1 14 Dout= 7.09 CF5 u 12 LAG= 20.5 MIN 1 3 0 O B J LL 6 . 4 r r 2 r 0m - n, rr) v rn to rl m m m - - - - - - - -- - N TIME (hour5) 1l 1Ci (l �i� rIw Lnrr "W-y- tv INV. 22.5 W/ 10' X 15' X 152`' ENERGY DIS IPATOR�� /�6 NCDOT CLASSB EROSION CONTROL TELPU;V r o / STONE SILT FENCE- % ! k NORMAL POOL �f �� ELEVATION — 22.5 iplo, BUM, jo b� �, ; �/� ,/I� • tits C01,01CT WDi 6ASIN -- AT END OF UISTM . 30, GIP TOP GRATE = 24.Of AV. 1173' PONE DiECX L1W 1. f IN FRONT OF INV. 22,3� W/ 10' X 15' X 15" i'; . ; t-' ENERGY DISSIPATOR NCDOT CLASS 8 Jo /', ; , �:' EROSION CONTROLX A X 2 TrE STONE i i, 1FES qATE VALVE CASE VAL ! c' &' BLOW 01 tit swg qj oc016 OVER H0RT1��P Beth Easley Wetherill, CPESC Soil Erosion Specialist New Hanover County Engineering Department 230 Market Place Drive - Suite 160 Wilmington, North Carolina 28403 Phone: (910) 798-71391Fax: (910)-798-7051 Email: bwetherill@nhcgov.com SEDIMENTATION INSPECTION REPORT Project Grading Permit Project: T-0 Project Loc on: lir' e, Person(s)Financially Responsible L' a Address: 'WlC p Z 19 R 1. Pictures: Yes 6) # Weather & Soil Cori itions: e &Z Z 2. Is site currently under Notice of Violation: Yes +� 3, Is the site in compliance with NHC Soil Erosion & Sedimentation Control Ordinance? Yes(1�Circle violations below: 4. Violations: (Circle letter) (A) No approved plan. (B) Failure to follow approved plan. (C) Failure to submit revised plan. (D) Failure to provide adequate ground cover. (DInsufficient measures to retain sediment on site, (F) Failure to take. all .reasonable measures. (G) Inadequate buffer zone. (H) Graded slopes & fills too steep. �Dknprotected exposed slopes. 10Failure to maintain erosion control measures. (K) NPDES Problems (L) Other (describe) 5: Has off -site sedimentation occurred since last inspection? Yes No Degree: Slight Moderate Severe 6. ' Contact made with Title: Inspection report give sen k a-ui;c --hlun ,(/[ le-- Chu 7: Inspection Report sent to person(s) responsible:'p Datesent 8. Corrective Actions Needed: •".fi�S �/� fLJLf os-E, �r�r1[{��,✓lG /]►�Ar G S/�c>c..��/���P- �.d . -_ . u- Za— �r �r I - 1- ►.L >^ ►l a C-. do 1, P GLac/ If 107 0-c- -- Report By: at'n - L �r1 d Date: Others present: Time to Comply: ro CORRECTIVE ACTIONS NEEDED (ADDITIONAL- Ye �r4 d.. ;�407 Tti JIY,vh ' l Cl �- r r �,o XV ir., it n.l /V.,k e � CAPE FEAR RIVER BASIN Name of Stream Subbasin Stream Index Number Map Number Class Bridge Branch CPF19 18-68-2-12-2-2 H25NE8 C;Sw Broad Branch CPF16 18-50-4 I24SE5 C Broad Mouth Branch CPF09 17-20 E20NE4 C Brooks Creek (Branch) CPF04 16-36 D22SW7 WS-IV,B;NSW Brown Branch CPF03 16-19-11-1 C21SW2 C;NSW Browns Creek (Cross Pond) CPF16 18-45 I24NWB C Browns Swamp CPF18 18-68-12-3.5 G24SW2 C;Sw Brunswick River CPF17 18-77 J27SW7 SC Brush Creek CPF02 16-11-4-(1) C19SW2 WS-III;NSW Brush Creek CPF09 17-23 E20NE6 C Brush Creek (hake Higgins) CPF02 16-11-4-(2) C19NW9 WS-III;NSW,CA Bryant Mill Creek CPF17 18-65 126SW3 C;Sw Bryant Swamp CPF19 18-68-1-17-5 G24SE2 C;Sw Buck Branch CPFOS 16-41-1-17-1-1 D23NW9 WS-IV;NSW Buck Branch CPF06 16-41-2-9 D22NEB WS-IV;NSW Buck Branch CPF22 18-74-23-0.5-2 H28NW2 C;Sw Buck Creek CPF10 17-26-8 F20NE5 C Buck Creek CPF1B 18-68-12-5-2 G24SW8 C;Sw Buck Marsh Branch CPP21 18-74-8 G27NW6 C;Sw Buckhall Creek CPF19 1B-6B-2-10-1 H26NE1 C;Sw Buckhead Creek (Buckland Creek) CPF15 18-31-24-6 G23SW5 C Buckhorn Branch CPF06 16-41-1-15-1-1-1 D22NE4 C;NSW Buckhorn Creek CPF07 16-7-(1) E23SE1 C Buckhorn Creek CPF07 18-7-(2) E23SW3 B Buckhorn Creek CPF07 18-7-(11) E23SW6 C Buckhorn Creek (Roney Pond) CPF19 16-68-2-12-2 H25NE8 C;Sw Buckhorn Creek (Harris Lake) CPF07 18-7-(3) E23SW3 WS-V Buckle Swamp Creek CPF20 18-68-22-1-2 J26NW7 C;Sw Buckskin Swamp CPF22 18-74-21-1.7 H27NW1 C;Sw Buffalo Creek CPF02 16-11-14 C20NW9 C;NSW Buffalo Creek CPF10 17-28 F20NEB C Buffalo Creek CPF14 18-23-16 G22NE1 WS-III Buffalo Meadows Creek (Stevens Pond) CPF14 18-23-32-3 F23SE7 C Buies Creek CPF07 18-18 F24NW4 WS-IV Bull Branch CPF15 18-31-19-2-1 G22SW3 C Bull Branch CPF19 18-68-2-9 H26NW7 C;Sw Bull Branch CPF22 18-74--29-3-3 I26NE2 C;Sw Bull Run CPFOB 17-5-(1) C19SW6 WS-IV:+ Bull Run CPF08 17-5-(2) D19NW2 WS-IV;CA:` Bull Run CPF09 17-11-4-(1) D19SE3 WS-III,B Bull Run CPF09 17-11-4-(2) D19SE3 WS-1II,B;CA Bullard Branch CPF22 16-74-19-14 G27SW5 C;Sw Bullard Pond CPF18 18-66-12-8-1 H24NE1 C;Sw Bulldog Cut CPF17 18-GB-23 J26SE2 C;Sw Bulldog Cut CPF20 18-6B-23 J26SE2 C;Sw Bullhead Branch CPF20 18-68-18-1 I26NW9 C;Sw Bulltail Creek CPF20 18-68-18-2 I26NW9 C;Sw Bulltail Creek CPF22 18-74-29-3-1 H26SW7 C;Sw Burdens Creek CPF05 16-41-1-17-1-(0.3) D23NW9 C;NSW Burdens Creek CPF05 16-41-1-17-1-(0.7) D23NW9 WS-IV;NSW Burgaw Creek CPF23 18-74-39 I27SW6 C;Sw Burn Coat Creek (Maxwell Millpond) CPF22 18-74-17 G27SE5 C;Sw Burnt Mill Creek CPF23 18-74-63-2 K27NW2 C;Sw Burris Creek CPF17 18-88-6-2-3 L27NW7 SA;14QW Bush Creek CPF05 16-41-4-(0.3) D22SE5 WS-IV;NSW Bush Creek CPF05 16-41-4-(0.7) D22SE5 WS-IV;NSW,CA Bush Creek CPF09 17-15 D20SW7 C Bush Creek CPF07 16-6 E22SE9 C Page 4 of 28 TROLLEY PATH CONDOS 6/25/2004 Trolley Path Condos -- SW8 970616 Area of Two Preserved Trees Rip Rap Around Section 1 of Pond Building That Appears To Extend Over The Slope Rip Rap Around Section 2 of Pond OF W A ��9 Michael F. Easley, Governor Q. William G. Ross Jr., Secretary v North Carolina Department of Environment and Natural Resources Alan W. Klimek, P.E.,Director p Division of Water Quality Coleen H. Sullins, Deputy Director Division of Water Quality November 24, 2003 Trolly Path Condos Live Oak Developement Co. 616 Princess Street Wilmington, NC 28401 NOTICE OF INSPECTION AND NON-COMPLIANCE Trolly Path Condos Stormwater Project No. SW8 970616 New Hanover County Dear permittee: Please find attached a copy of the completed form entitled "Stormwater Compliance Inspection Report". The report summarizes the findings of a recent inspection of the project's stormwater controls conducted on November 21, 2003 to determine compliance with Stormwater Permit Number SW8 970616 issued on may 20, 1997. A summary of the findings and comments are noted under Section 4 of the report. Please inform this Office in writing before December 21, 2003, of the specific actions that will be undertaken and the time frame required to correct the deficiencies. Failure to provide the requested information, when required, may initiate enforcement action. If you have any questions please contact me at the Wilmington Regional Office, telephone number (910) 395-3900. Sincerely, Gary H. Beecher Environmental Engineer RSSlghb: S:IWQSISTORMWATIINSPECT1970616.Nov03 cc: Mr. Phil Norris, P.E. Wilmington Regional Office Beth Weatherwill ( New Hanover Co.) N. C. Division of Water Quality 127 Cardinal Drive Extension (910) 395 3900 Customer Service AWA ENr Wilmington Regional Office Wilmington, NC 28405 (910) 350-2004 Fax 1 800 623-7748 NCD STORMWATER COMPLIANCE INSPECTION REPORT 2 3. Project Name: Trolly Path Condos Project Number: 970616 Water Body: Burnt Mill Creek Control Measure: detention Classification: C-Swamp Directions to site, address: Wrightsville Ave ( CSX Railroad and Spofford Circle ) Inspection Date: November 21, 2003 Weather Conditions: Dry and Sunny Compliance Issues: Y N ❑ ❑ The drainage area (including offsite) and built -upon area to the permitted system are per the approved plan. No unpermitted offsite drainage enters the system. ❑ ❑ All`the built -upon area associated with the project is graded such that'the runoff drains to the system. ❑ ❑ For pond shnfiltration, the outlet/bypass structure relative elevations`are per the approved plan. (Must be verified via as -built survey if in question). ❑ ❑ The inlets and outlet structure are located per the approved plans and do not cause short-circuiting. ❑ ❑ A trash rack is provided over the outlet weir and orifice. ❑ JK All slopes are grassed with permanent vegetation and are not eroding. ❑ ❑ Vegetated slopes are no steeper than 3:1. ❑ ❑ The approximate amount of permitted surface area has been provided. (Must be verified via as -built survey or designer's certification.) ❑ ❑ Required drawdown devices are correctly sized per the approved plans. All required design depths are provided. ❑ ❑ All required parts of the system are provided, such as a vegetated shelf, and a forebay. ❑ ❑ The designer's certification has been submitted. ❑ ❑ The required deed restrictions are correctly recorded and submitted. ❑ ❑ The number of lots or outparcels is per the permitted amount. ❑ ❑ The built -upon area on the lots or outparcels does not appear to exceed the maximum amount (must be verified via as -built survey if in question) ❑ ❑ Curb outlet swales are constructed, located properly, are 100' long and have dense vegetated cover. ❑ ❑ The road, cul-de-sac, parking lot and sidewalk widths are per the approved plan. ❑ X Required maintenance is being performed. ❑ ❑ Outparcels have their own offsite permit. ❑ ❑ For low density projects, roadside swales are 3:1, vegetated and stable. ❑ ❑ For low density projects, there are no unpermitted pipes on the project. 4. Required Actions: (Explain each deficiency and what needs to be done to bring the system back into compliance) (a) The lamp post in the second detention pond is very unstable, the slope has blown out and severe erosion is occurring. This area must be stabilized with grass or rip/rap. (b) Both Detention ponds are not being maintained as specified in the permit. (c) The silt fence needs to be re-established and maintained in areas of on -going construction to help minimize sediment transport off property. (d) Slopes of both detention ponds need to be grassed to prevent further erosion from taking place. (e) Catch basins must also be cleaned periodically so they don't disrupt sediment flow. Inspector: Gary H. Beecher Quality/Wilmington Regional Office/(910) 395-3900 RSSlghb: S:IWQSISTORMWA-RINSPECT1970616.Nov03 TROLLY PATH APARTMENTS �' f.f1,�.4�� .. _. nor -�.. ! .i ��"�•�' yt�}�,s �-�lls�- •.:�., � `. ` _ _ ' `:,� _sac' �. .� . c � �� - = cv X FES INV. 22.5 / W/ 10' X 15' X 15''" r(jJ ENERGY DISSIPATOR i =. NCDOT CLASS 8 / 1 EROSION CONTROL TEIIPOPorR1' o STONE SILT FEWI 8 NORM& POOL of �C ' ELEVATION = 22.Efo 15 i�10' BUM - CON51W C,Mi BASIN AT END OF E(1SW 300 CWF TOP GRATE = 24.0t W. = 18.73' TONE CHECX DWI •/ A /�; _ - lH FRONT OF / / = . + _ l� / ; -. -�- - -T 24' FE$ IMI. 22.3 , � �.1� W. 21.5 -- W/ 10' X 15' X 15' ENERGY DISSIPATORTEE NCDOT CLASS B�ra EROSION CONTROL ,/ w,'� / _ f., ,, ' . STONEV. 3 1-8GATE VALVE 2 GATE VAL bUri.DW(3 -140. 6 GTCN BA511 Tt rP i i i afire nruc Lin L