HomeMy WebLinkAboutNC0045993_Compliance Evaluation Inspection_20201008 (2)ROY COOPER
Coverwr
MICHAEL S. REGAN
secretary
S. DANIEL SMITH
Director
Mr. Preston M. Baucom, EHS
ATI Allvac Monroe Plant
Post Office Box 5030
Monroe, NC 281115030
NORTH CAROLINA
En viraninen tat Quality
October 08, 2020
SUBJECT: Compliance Evaluation Inspection
ATI Allvac Monroe Plant WWTP
NPDES Permit NCO045993
Union County, NC
Dear Mr. Baucom:
On October 6, 2020, Roberto Scheller of this Office conducted a compliance inspection at the subject facility. This
inspection was conducted as a Compliance Evaluation Inspection (CEI) to insure compliance with permit requirements
and conditions. The subject facility appeared to be well operated and we wish to thank the operating staff for
assistance regarding this inspection.
The enclosed report should be self-explanatory; however, should you have any questions, please do not hesitate to
contact myself or Roberto Scheller at (704)235-2204 or roberto.scheller(a�ncdenr.gov.
Sincerely,
DocuSigned by:
A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: CEI Report
No rth Caroiina Department of E nvuon menu! Quairty I Dimsoo of Water Resources
Mooresville Regbfm! Office 1610 Es3 Center Avenue, Suite 301 I Mooresvlie, North Garoiina 25115
�L f •'� 704-ef3-1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0045993 111 121 20/10/07 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701� I 711 L
LJ L -1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:OOAM 20/10/07
14/06/01
ATI Specialty Materials - Monroe Plant
2020 Ashcraft Ave
Exit Time/Date
Permit Expiration Date
Monroe NC 28110
11:31AM 20/10/07
19/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Tommy W Long/ORC/704-289-4511/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Danny Caudle,2020 Ashcraft Ave Monroe NC 28110//704-289-4511/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Records/Reports Self -Monitoring Progran
Facility Site Review 0 Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Roberto Scheller sC,4,u,,4- DWR/MRO WQ/252-946-6481/ 10/8/2020
E91C2A007838943E.-
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
eyj � 10/8/2020
AlaccsalAFz7azs... Page#
NPDES yr/mo/day Inspection Type
NCO045993 I11 12I 20/10/07 117 18 i c i
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
At time of inspection records were current and available for review. Treatment facility appeared to be
well maintained. Effluent was clear with no visible suspended solids.
It was noted during inspection that water flowing through V-notch weir (Nappe) was collapsing against
downstream face of weir plate. It is recommended that weir plate be checked for vertical level and
slime growth cleaned from face of weir plate (downstream side). Flow over V-notch should be
monitored to see if nappe continues to collapse against weir plate.
Page#
Permit: NCO045993 Owner -Facility:
Inspection Date: 10/07/2020 Inspection Type:
ATI Specialty Materials -Monroe Plant
Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
E
❑
❑
❑
Comment: Facility operating under permit that expired on January 31, 2019.
Record Keeping
Yes
No
NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
❑
❑
0
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? 0 ❑ ❑ ❑
Is flow meter calibrated annually? E ❑ ❑ ❑
Page# 3
Permit: NC0045993
Inspection Date: 10/07/2020
Flow Measurement - Effluent
Is the flow meter operational?
Owner -Facility: ATI Specialty Materials -Monroe Plant
Inspection Type: Compliance Evaluation
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: At time of inspection effluent was clear with no visible suspended solids.
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ❑
Yes
No
NA
NE
❑
❑
❑
❑
❑
❑
❑
❑
❑
Page# 4