HomeMy WebLinkAboutNC0026441_Compliance Sampling Inspection_20201001ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
Roy Lynch, Town Manager
Town of Siler City
PO Box 769
Siler City, NC 27344
NORTH CAROLINA
Environmental Quality
October 1, 2020
Subject: Compliance Sampling Inspection (CSI)
Siler City WWTP
NPDES Permit No. NCO026441
Chatham County
Dear Mr. Lynch:
On July 21, 2020, Cheng Zhang of the Raleigh Regional Office (RRO) conducted a compliance sampling
inspection of the subject facility. The assistance provided by Ms. Brittany York, the operator in
responsible charge (ORC), was greatly appreciated as it facilitated the inspection process. The inspection
report is attached. The following observations were made:
Siler City WWTP is permitted to discharge at a rate of 4.0 MGD and consists of. automatic and
manual bar screens, grit collection unit, influent pump station, influent equalization basin (Zone 2),
dual oxidation ditches with surface jet aeration, flow splitter box, alum feed station, lime feed
station, dual secondary clarifiers, dual aerobic digesters, sludge transfer station, dissolved air
flotation (DAF) unit (Used as needed), sludge thickener basin, influent equalization or sludge
storage basins (Zone 3 A & B used as needed), four tertiary filters, filter backwash basin, gaseous
chlorine disinfection, chlorine contact chamber, gaseous sulfur dioxide dechlorination, and step -
aeration. The facility discharges into Loves Creek, which is classified C waters in the Cape Fear
Basin.
The current permit was modified on April 40, 2019 and expired on May 31, 2019. An interim
total nitrogen load limit was added in the modified permit (effective from January 1, 2020
through December 31, 2022). Lower total nitrogen load limit will become effective on January 1,
2023. On November 30, 2018, the Division received the Town's permit renewal application for
the Siler City WWTP. The Division is in the process of renewing this NPDES permit.
2. At the time of inspection, all listed treatment units were in operable conditions. Some treatment
units (equalization basins and DAF unit) were not in use. Waste activated sludge was treated in
the two aerobic digesters and two EQ basins, and thickened in the sludge thickener basin. It was
norDE Q�� North Carolina Department of Environmental Quality I Division of Water Resources
r rnani wa Raleigh Regional Office 13800 Barrett Drive I Raleigh, North Carolina 27609
oep,m ,t ie n��m.nni"i;� 919.791.4200
noted that all sludge digesters/basins were full. As a result, the facility was unable to waste
sludge as needed; mixed liquor suspended solids were high (around 7000 mg/L).
3. As part of this CSI, effluent composite samples were collected using the DWR portable sampler
(a grab effluent sample was also collected for analysis of fecal coliform), these samples were
analyzed by DWR Laboratory. Field parameters (except total residual chlorine) were measured
using a DWR YSI Proplus meter. The sampling results are summarized in the following tables:
Effluent
Parameter
Sample Type
Permit Limit (Weekly average)
Result
BOD
Composite
7.5 mg/L
4.2 mg/L
TSS
Composite
45 mg/L
<6.2 mg/L
Ammonia
Composite
3 mg/L
0.06 mg/L
TKN
Composite
1.2 mg/L
Nitrate + Nitrite
Composite
9.4 mg/L
Total Nitrogen
Calculated
10.6 mg/L
Total Phosphorous
Composite
0.5 mg/L (Quarterly average)
0.09 mg/L
Fecal Coliform
Grab
400 CFU /100 ml
230 CFU /100 ml
Effluent - Field Parameters
Parameter
Sample Type
Permit Limit
Result
Temperature
Grab
29.4 °C
H
Grab
6-9
7.58
Dissolved Oxygen
Grab
>6 mg/L
7.08 mg/L
4. Influent and effluent sampling performed by the facility was observed and found to meet the permit
requirements.
The result of this compliance sampling inspection is compliant. If you have any questions regarding the
attached reports or any of the findings, please contact Cheng Zhang at: (919) 791-4200 (or email:
Cheng. zhang@ncdenr. gov).
Sincerely,
DocuSigned by:
`/aV�.t,SSa f.
62916E6AB32144F...
Vanessa E. Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources
Attachment: EPA Water Compliance Inspection Report
Cc: Central Files w/attachment (Laserfiche)
Raleigh Regional Office w/attachment
Brittany York, ORC (electronic copy only)
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0026441 I11 121 20/07/21 I17 18I e I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701� I 711 L
LJ L -1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:OOAM 20/07/21
19/05/01
Siler City WWTP
370 Waste Treatment Plant Rd
Exit Time/Date
Permit Expiration Date
Siler City NC 27344
11:OOAM 20/07/21
19/05/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Brittany Nicole York/ORC/919-742-4581/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Roy Lynch,PO Box 769 Siler City NC 27344/Town Manager/919-742-4581/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenar 0 Records/Reports 0 Self -Monitoring Progran 0 Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Cheng Zhang Docusignedby: DWR/RRO WQ/919-791-4200/
E101112020
D6171508P EC41F...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by: 101112020
Sa Vcunt.S`�, DWR/RRO WQ/919-791-4232
�-- 62916HAB32144F...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO026441 I11 121
20/07/21 117 18 1 S I
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
24-hour composite effluent sample (started at 10:19 am, July 20, 2020, ended at 10:19 am, July 21,
2020, time paced, 100 ml/20 minutes) was collected using DWR portable sampler, composite
samples were collected on July 21, 2020 for BOD, TSS, ammonia nitrogen, nitrate/nitrite, TKN, and
total phosphorous. Effluent sample was also collected for fecal coliform. Field parameters (except total
residual chlorine) were measured using a DWR YSI Proplus meter.
Analytical results
BOD: 4.2 mg/L; ammonia nitrogen: 0.06 mg/L; TSS: <6.2 mg/L; nitrate plus nitrite: 9.4 mg/L; TKN: 1.2
mg/L; total phosphorous: 0.09 mg/L; fecal coliform: 230 CFU/100ml.
Field parameters:
Temperature: 29.4 degree C; pH: 7.58; DO: 7.08 mg/L.
Influent and effluent sampling and field parameter measurement condocted by the facility were
observed and found to meet permit requirements.
The facility was found to be compliant for the sampling compliance inspection.
Page#
Permit: NCO026441
Inspection Date: 07/21/2020
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Owner -Facility: Siler City WWTP
Inspection Type: Compliance Sampling
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is sampling performed according to the permit?
Comment:
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: A part needed to be replaced to perform flow proportional sampling
Yes
No
NA
NE
❑
❑
❑
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
Yes No NA NE
❑ ■ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility analyzes MLSS, DO, pH, sludge blankets, etc. for process control.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment:
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Page# 3
U.S. EPA Interim Revised NPDES Inspection Manual 12017
Wood, L.B., and Stanbridge, H.H. (1968). "Automatic Samplers," Water Pollution Control, 67(5): 495-520.
D. PERMITTEE SAMPLING INSPECTION CHECKLIST
A. PERMITTEE SAMPLING
EVALUATION
e
No
N/A
1.
Take samples at sites specified in permit.
No
N/A
2.
Locations adequate for representative samples.
Yes
o
N/A
3.
Flow proportioned samples obtained when required by permit.
e
No
N/A
4.
Complete sampling and analysis on parameters specified by permit.
Yes
No
N/A
5.
Conduct sampling and analysis in frequency specified by permit.
Des
No
N/A
6.
Permittee uses method of sample collection required by permit.
Required method:
If not, method being used is: () Grab (} Manual Composite
0 Automatic Composite
es
es
No
No
No
o
N/A
N/A
N/A
N/A
7.
Sample collection procedures adequate:
a. Samples refrigerated during compositing.
b. Proper preservation techniques used.
c. Containers and sample holding times before analyses conform to 40 CFR
136.3.
d. Samples analyzed in timeframe needed.
es
No
N/A
8.
Facility performs monitoring and analyses more often than required by permit; if
so, results reported in permittee's self -monitoring report.
Yes
Na
N/A
9.
Samples contain chlorine.
Yes
No
N/A
10. Use contract laboratory for sample analysis.
Yes
No
N/A
11. POTW collects samples from industrial users in pretreatment program.
B. SAMPLING INSPECTION PROCEDURES AND OBSERVATIONS
es
No
N/A
1.
Obtain grab samples.
No
N/A
2. Obtain composite sample. L t-1kfc"'fYet~' n3� 4
Compositing Frequency: Frvto�'
es
No
N/A
3.
Refrigerate sample during compositing.
No
N/A
4.
Obtain flow -proportioned sample. 1/I f /" a..-kf
57-
No
N/A
5.
Obtain sample from facility sampling device.
es
No
N/A
6.
Sample representative of volume and nature of discharge.
Yes
Q�V
N/A
7.
Sample split with permittee.
No
N/A
8.
Employ chain -of -custody procedures.
es
No
N/A
9.
Samples collected in accordance with permit.
e
No
N/A
10. Observe excessive foam, grease, floating solids at the outfall.
G % '- L15r L1/ W r 0 Gv. ,, jp 1: n .. C � c� Gn. lv �: • 3 f /t C 4-!,)
7_ a( — 2-020
Chapter 5 — Page 115
U.S. EPA Interim Revised NPDES Inspection Manual 12017
C. AUTOMATIC SAMPLER PROCEDURES AND OBSERVATIONS
es No
N/A
1.
Sample intake tubing place in a well -mixed, representative location (0.4 to 0.6
depth).
Yes No
N/A
2.
Individual aliquot volume checked and at least 100ml.
Y No
N/A
3.
Proper sample tubing (Teflon TM for organics, otherwise(Tygon ) and tubing at ID
at least 0.25 inch.
Yes No
N/A
4.
Proper composite sample container (glass for organics, otherwise lastic.
e No
les> No
N/A
N/A
5.
6.
Proper refrigeration (6°C or ice), with required documentation.
Proper wastewater velocity in the sample tubing (at least 2 fps).
Chapter 5 — Page 116