HomeMy WebLinkAboutNC0083321_Compliance Evaluation Inspection_20200924DocuSign Envelope ID: A3DB55F8-lFA3-4D25-87F0-14F298306261
ROY COOPER
Governor
MICHAEL S. REGAN
secretary
S. DANIEL SMITH
Dlreetor
Seth Adam Brown
Onslow Water and Sewer Authority
228 Georgetown Rd
Jacksonville, NC 28540
NORTH CAROLINA
Envhraningatal Quality
September 23, 2020
SUBJECT: Compliance Inspection Report
Hubert WTP
NPDES WW Permit No. NCO083321
Onslow County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Hubert WTP on
9/23/2020. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0083321. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report". There were no significant issues or findings noted during the
inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Bryan Lievre with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
bryan.lievre@ncdenr.gov.
ATTACHMENTS
Sincerely,
EW
DocuSigned by:
Vt u a, Sad GIA�Alm
EMBAMA=C434...
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
Q�North CsrotnaDepartrnentofEnvironmeatadQuality I DiuisionofWater Rescurces
WilfningtanRegonaIOffiice 1127 CarMaai Dive Extension I Wilra ngton, North Caroina2d34D5
"•• 910-756-7215
DocuSign Envelope ID: A4DF77CB-8D8A-4833-B819-20E2C3F038F6
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0083321 I11 121 20/09/23 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:OOAM 20/09/23
20/07/01
Hubert WTP
374 Hubert Blvd
Exit Time/Date
Permit Expiration Date
Hubert NC 28539
11:30AM 20/09/23
22/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
James Willie Arnold/ORC/910-455-0722/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
James R McDonnel,228 Georgetown Rd Jacksonville NC 28540/Water
Superintendent/910-915-6937/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Compliance Schedules
Effluent/Receiving Wate 0 Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Bryan Lievre Docusignedby- DWR/WIRO WQ/910-796-7215/ 9/23/2020
Y�2*�ccn. �tir�vtr.
74249ABED37443E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
F144bVt,�,a SawnI�Al 9/23/2020
"-E3ABA14 C=434.
EPA Form 3560-3 (Rev 9-94) Previous eNions are obsolete.
Page#
DocuSign Envelope ID: A4DF77CB-8D8A-4833-B819-20E2C3F038F6
NPDES yr/mo/day Inspection Type (Cont.)
NCO083321 I11 12I 20/09/23 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
A routine compliance inspection of the Onslow Water and Sewer Authority (ONWASA) Hubert Water
Treatment Plant (WTP) was conducted on September 23, 2020. The purpose of the inspection was to
verify that the facility is operating in compliance with the conditions and limitation specified within
Permit NC0083321. Present during the inspection were James Arnold (ONWASA ORC) and myself
(Bryan Lievre).
The WTP is located at 372 Hubert Blvd, Hubert, North Carolina and derives water from 14 water supply
wells (Well No's. 1 through 4 and 6 through 15). The raw water is equipped with three aeration units
(set up in parallel), then the water is pumped through one of three trains of greensand filters (for iron
and manganese removal and each train has four filters set up in parallel and potassium permanganate
is added to regenerate the filters) ), then through three trains of ion exchanger softeners (whereas Trair
1 has 2 units and Trains 2 & 3 have 3 units and all units in each train are installed in parallel and a brin(
solution is added to regenerate each unit), and then treated with fluosilicic acid (i.e. fluoride to prevent
tooth decay), orthophosphate (for corrosion control) and sodium hypochlorite (for disinfection).
The permitted effluent water is the backwash water from the greensand filters and ion exchange
softeners, water from floor drains from within the WTP building and a sink within the WTP building
which is used to check finished water quality. The bathroom wastewater from the WTP building is
discharged into an on -site subsurface system with a pump tank located near the northeast corner of
the WTP building and a drain field located near the middle of the western property line.
The effluent water (i.e. backwash water and water from floor drains) is sent to one of four lagoons and
each lagoon is lined and has a capacity of 0.75 million gallons. The lagoons are set up in series,
although the last lagoon (Lagoon #4) is used primarily as an overflow basin. Backwash water is
typically sent into Lagoon #1 and is pumped for discharge from Lagoon #3.
The WTP has a design flow rate of 6 million gallons per day (MGD) and a maximum monthly average
discharge of approximately 0.3585 MGD. The water is discharged into Queen Creek, a tributary of the
White Oak River Basin, on the north side of NC Highway 24, approximately 0.75 miles east of the
WTP. In the vicinity of the discharge location, Queen Creek has a surface water classification of SA;
HQW waters (i.e. High Quality Waters within tidal surface waters which used for shellfishing or market
purposes).
The system is currently working with others to provide a Discharge Alternatives Evaluation due to
historical sampling results which have indicated the potential for causing aquatic toxicity in the
receiving stream.
Records were readily available, organized and complete. The facility was clean and well organized.
The facility is in compliance with Permit NC0083321. Please review the comment sections of the
inspection report for more details.
Page#
DocuSign Envelope ID: A4DF77CB-8D8A-4833-B819-20E2C3F038F6
Permit: NCO083321 Owner -Facility: Hubert WTP
Inspection Date: 09/23/2020 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The permit was issued 5/27/2020 and expires 7/31/2022. The entire property is surrounded
by chain link fencing with barbed wire. An access code is needed to open the fence gate.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
0411111111 k, rss I! F-M k,I=
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
■
❑
❑
❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: Records were well maintained and accurate. Copies of monthly reports for January and
March 2020 were inspected while on -site.
Compliance Schedules Yes No NA NE
Is there a compliance schedule for this facility? 0 ❑ ❑ ❑
Page# 3
DocuSign Envelope ID: A4DF77CB-8D8A-4833-B819-20E2C3F038F6
Permit: NCO083321 Owner -Facility: Hubert WTP
Inspection Date: 09/23/2020 Inspection Type: Compliance Evaluation
Compliance Schedules
Is the facility compliant with the permit and conditions for the review period?
Comment: The system passed chronic toxicity sampling metals analyses for 6/2020.
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Yes No NA NE
■ ❑ ❑ ❑
Yes
No
NA
NE
❑
❑
❑
❑
❑
❑
Comment: The plant was found to be well maintained and organized. The system is certified for pH,
DO, salinity, conductivity and turbidity.
De -chlorination
Yes
No
NA NE
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑
❑
0 ❑
Is storage appropriate for cylinders?
❑
❑
0 ❑
# Is de -chlorination substance stored away from chlorine containers?
❑
❑
0 ❑
Comment:
Are the tablets the proper size and type? ❑ ❑ 0 ❑
Are tablet de -chlorinators operational? ❑ ❑ 0 ❑
Number of tubes in use?
Comment:
Lagoons
Yes
No
NA
NE
Type of lagoons?
Facultative
# Number of lagoons in operation at time of visit?
4
Are lagoons operated in?
Series
# Is a re -circulation line present?
0
❑
❑
❑
Is lagoon free of excessive floating materials?
0
❑
❑
❑
# Are baffles between ponds or effluent baffles adjustable?
❑
❑
0
❑
Are dike slopes clear of woody vegetation?
0
❑
❑
❑
Are weeds controlled around the edge of the lagoon?
0
❑
❑
❑
Are dikes free of seepage?
0
❑
❑
❑
Are dikes free of erosion?
0
❑
❑
❑
Are dikes free of burrowing animals?
0
❑
❑
❑
Page# 4
DocuSign Envelope ID: A4DF77CB-8D8A-4833-B819-20E2C3F038F6
Permit: NCO083321 Owner -Facility: Hubert WTP
Inspection Date: 09/23/2020 Inspection Type: Compliance Evaluation
Lagoons
Yes
No
NA
NE
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple
0
❑
❑
❑
locations?
# If excessive algae is present, has barley straw been used to help control the growth?
❑
❑
❑
Is the lagoon surface free of weeds?
0
❑
❑
❑
Is the lagoon free of short circuiting?
❑
❑
❑
Comment: With the exception of some alaae which was Dresent alona the edaes of the laaoons. the
structures apepared to be in good condition. Lagoon 1 is cleaned out every 3 years and is
planned to be cleaned later this year. The system staff have started taking measurements
on sludge thicknesses within each of the lagoons. The system has investigated methods to
decrease algae build-up (including stocking lagoons with fish, etc.) and continue to explore
alternatives.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: Water was observed flowing out of the six inch diameter effluent line at the outfall within
Queen Creek. This line can be submerged, depending on creek levels,
but was not
submerged during the current inspection.
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: A magnetic flow meter is located at a wet well with duplex pumps on the north side of
Lagoon #3 (whereas Lagoon #3 is located directly south of the treatment building). The flow
meter was last calibrated by Carolina Technical Services, Inc., 10/22/2019. Visual and
audible alarms are Dresent on the dUDlex DumD station.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 5
DocuSign Envelope ID: A4DF77CB-8D8A-4833-B819-20E2C3F038F6
Permit: NC0083321 Owner -Facility: Hubert WTP
Inspection Date: 09/23/2020 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑
representative)?
Comment: The composite sampler had a temperature gauge and the gauge indicated that the
temperature was 4.5 deegrees Celcius.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment: The generator automatically activates on a weekly basis.
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Page# 6