HomeMy WebLinkAboutWQ0000485_Compliance Evaluation Inspection_20200921DocuSign Envelope ID: AAE61 FB1 -C247-440B-9E1 9-851 BDF235CB9 ROY COOPER Governor MICHAEL S. REGAN secretary S. DANIEL SMITH Dlreetor Toby John Schlink Valley Proteins Inc PO Box 1026 Rose Hill, NC 28458 NORTH CAROLINA Envrraningatal Quality September 21, 2020 SUBJECT: Compliance Inspection Report Valley Proteins - Rose Hill WWTF Non -discharge Permit No. WQ0000485 Duplin County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Valley Proteins - Rose Hill WWTF on 9/16/2020. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0000485. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact Bryan Lievre with the Water Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at bryan.lievre@ncdenr.gov. ATTACHMENT Sincerely, EW DocuSigned by: mLt a, Sa n GIA�—f 14 EMBAMA=C434... Morella Sanchez -King, Regional Supervisor Water Quality Regional Operations Section Wilmington Regional Office Division of Water Resources, NCDEQ Q�North CsrotnaDepartrnentofEnvironmeatadQuality I DiuisionofWater Rescurces WilfningtanRegonaIOffiice 1127 CarMaai Dive Extension I Wilra ngton, North Caroina2d34D5 "•• 910-756-7215 Compliance Inspection Report Permit: WQ0000485 Effective: 11/01/19 Expiration: 03/31/25 Owner: Valley Proteins Inc SOC: Effective: Expiration: Facility: Valley Proteins - Rose Hill WWTF County: Duplin 469 Yellowcut Rd Region: Wilmington Rose Hill NC 28458 Contact Person: Toby John Schlink Title: District Manager Phone: 910-289-2083 Directions to Facility: From Rose Hill, take Hwy 117 North approx. 0.8 miles to Yellowcut Rd., left to end of road System Classifications: SI, WW2, Primary ORC: Corey Myles Lanier Certification: 1007689 Phone: 910-660-1173 Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 09/16/2020 Entry Time 09:OOAM Exit Time: 11:OOAM Primary Inspector: Bryan Lievre Phone: 910-796-7215 Secondary Inspector(s): Reason for Inspection: Routine Inspection Type: Compliance Evaluation Permit Inspection Type: Wastewater Irrigation Facility Status: Compliant ❑ Not Compliant Question Areas: Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions Treatment Flow Measurement -Water Treatment Record Keeping Use Records Treatment Lagoons End Use -Irrigation Treatment Disinfection Treatment Flow Measurement Standby Power (See attachment summary) Page 1 of 6 Permit: WQ0000485 Owner - Facility: Valley Proteins Inc Inspection Date: 09/16/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine Inspection Summary: A routine compliance inspection of the Valley Protein's wastewater treatment and spray irrigation disposal system was conducted on September 16, 2020. The purpose of the inspection was to verify that the facility is operating in compliance with the conditions specified within Permit WQ0000485. Present during the inspection were Corey Lanier, operator for the system, and myself (Bryan Lievre). The facility is a rendering plant located at 469 Yellow Cut Road, Rose Hill, NC. The wastewater system is permitted for the treatment of up to 350,000 gallons per day. The system includes an 0.084 million gallon (MG) process water equalization tank; 0.05 MG anaerobic reactor tank with floating modular membrane for odor control and heat retention; a dissolved air flotation (DAF) unit; a 3.5 million gallon (MG) aeration basin (Lagoon 1) with surface aerators; a 1.72 MG complete mixed activated sludge (CMAS) basin with jet aerators; a secondary DAF unit; a 0.01 MG DAF clarifier cell effluent tank that pumps to the cooling towers or irrigation storage lagoons; a 0.35 million gallon per day (MGD) reverse osmosis system for treating internal process recycle wastewater; a sodium hypochlorite feed system at the irrigation pump station; two 2.9 acre (Lagoon 2 and 3) and one 4.65 acre (Lagoon 4) storage lagoons; and, an 78.99 acre spray irrigation area which is split into eight fields. The types of industrial wastewater generated at the facility is either from wash down and truck drainage or cooker condensate. The effluent from the wastewater treatment system is either disposed of by spray irrigation or evaporated in the cooling towers. The facility also utilizes recycled wastewater for wash down. Sanitary wastewater generated from the bathroom facilities at the plant flows into the Town of Rose Hill sewer collection system. During the recent inspection, freeboard in all of the lagoons was below two feet (2.1' in Lagoon 1, 2.5' in Lagoon 2, 2.4' in Lagoon 3, and 2.5' in Lagoon 4). Wastewater is pumped from Lagoon 3 to any of the existing eight (8) spray fields (Fields 2 through 9, whereas Field 1 has been closed with the expansion of the process facility) which are located at and in the vicinity of the site. An updated site map and a water/wastewater flow diagram are recommended. Records were readily available, organized and complete. The facility is in compliance with Permit WQ0000485. Please review the comment sections of the inspection report for more details. Page 2 of 6 Permit: WQ0000485 Owner - Facility: Valley Proteins Inc Inspection Date: 09/16/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Recycle/Reuse ❑ Single Family Drip ❑ Activated Sludge Drip, LR ❑ Activated Sludge Spray, HR ❑ Infiltration System ❑ Lagoon Spray, LR ❑ Single Family Spray, LR ❑ Reuse (Quality) ❑ Activated Sludge Spray, LR Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑ Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑ Comment: Treatment Flow Measurement -Influent Yes No NA NE Is flowmeter calibrated annually? 0 ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? ❑ ❑ ❑ Comment: Treatment Flow Measurement -Water Use Records Yes No NA NE Is water use metered? ❑ ❑ ❑ Are the daily average values properly calculated? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement -Effluent Yes No NA NE Is flowmeter calibrated annually? 0 ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: Magnetic continous flow measuring flowmeters present at clarifier and a second for sprayfields. Both meters were calibrated 12/18/2019 by AMS Services. The meter at the clarifier was subsequently replaced 3/24/2020. Page 3 of 6 Permit: WQ0000485 Owner - Facility: Valley Proteins Inc Inspection Date: 09/16/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine Standby Power Yes No NA NE Is automatically activated standby power available? ❑ 0 ❑ ❑ Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑ Is generator operable? ❑ ❑ ❑ Does generator have adequate fuel? ❑ ❑ 0 ❑ Comment: Staff indicated that generators sufficiently capable of operating wastewater plant are rented prior to significant storm events. Treatment Disinfection Yes No NA NE Is the system working? 0 ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (-30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1 000-- ) If yes, then when was the RMP last updated? Comment: The system utilizes a 12-15% sodium hypochlorite solution which is fed before it is irrigated onto the spray fields. Record Keeping Yes No NA NE Is a copy of current permit available? ❑ ❑ ❑ Are monitoring reports present: NDMR? ❑ ❑ ❑ NDAR? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are application rates adhered to? ❑ ❑ ❑ Is GW monitoring being conducted, if required (GW-59s submitted)? ❑ ❑ ❑ Are all samples analyzed for all required parameters? ❑ ❑ ❑ Page 4 of 6 Permit: WQ0000485 Owner - Facility: Valley Proteins Inc Inspection Date: 09/16/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine Are there any 2L GW quality violations? ❑ ❑ ❑ Is GW-59A certification form completed for facility? 0 ❑ ❑ ❑ Is effluent sampled for same parameters as GW? 0 ❑ ❑ ❑ Do effluent concentrations exceed GW standards? 0 ❑ ❑ ❑ Are annual soil reports available? 0 ❑ ❑ ❑ # Are PAN records required? 0 ❑ ❑ ❑ # Did last soil report indicate a need for lime? ❑ ❑ 0 ❑ If so, has it been applied? ❑ ❑ 0 ❑ Are operational logs present? 0 ❑ ❑ ❑ Are lab sheets available for review? 0 ❑ ❑ ❑ Do lab sheets support data reported on NDMR? 0 ❑ ❑ ❑ Do lab sheets support data reported on GW-59s? 0 ❑ ❑ ❑ Are Operational and Maintenance records present? 0 ❑ ❑ ❑ Were Operational and Maintenance records complete? 0 ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? 0 ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ 0 ❑ No treatment units bypassed since last inspection? ❑ ❑ 0 ❑ Comment: Sampling results have indicated the presence of TDS in samples obtained within wells MW-10A MW-11A, MW-12B & MW-14A at levels above permit limits from sampling event performed 7/2020, 11/2019, 7/2019 & 3/2019. Intermittently chlorine and sulfate exceedences were also encountered in samples obtained from wells MW-12B & MW-14A. Monthly monitoring reports for 8/2020 & 9/2020 were checked during the inspection. Soil samplig was most recently performed by Corey Lanier 11/14/2019. End Use -Irrigation Yes No NA NE Are buffers adequate? ❑ ❑ ❑ Is the cover crop type specified in permit? ❑ ❑ ❑ Is the crop cover acceptable? ❑ ❑ ❑ Is the site condition adequate? ❑ ❑ ❑ Is the site free of runoff / ponding? ❑ ❑ ❑ Is the acreage specified in the permit being utilized? ❑ ❑ ❑ Is the application equipment present? ❑ ❑ ❑ Is the application equipment operational? ❑ ❑ ❑ Is the disposal field free of limiting slopes? ❑ ❑ ❑ Is access restricted and/or signs posted during active site use? ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ How close is the closest water supply well? ❑ ❑ ❑ Is municipal water available in the area? 0 ❑ ❑ ❑ Page 5 of 6 Permit: WQ0000485 Owner - Facility: Valley Proteins Inc Inspection Date: 09/16/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine # Info only: Does the permit call for monitoring wells? 0 ❑ ❑ ❑ Are GW monitoring wells located properly w/ respect to RB and CB? ❑ ❑ ❑ Are GW monitoring wells properly constructed, including screened interval? 0 ❑ ❑ ❑ Are monitoring wells damaged? ❑ 0 ❑ ❑ Comment: Wastewater was being applied to Field 7 during the recent inspection and Field 9 was not being used due to an overgrowth of weeds. Crops are planted in the fields and harvested by others. No evidence of ponding or runoff was observed during the recent inspection. During the recent inspection monitoring wells MW-&7A, MW-9 and MW-13A were located and found to have secured stick-up casings, well tags and a concrete pad. Page 6 of 6