HomeMy WebLinkAboutWQ0041956_Application (FTSE)_20200923Permit Number WQ0041956
Program Category
Non -discharge
Permit Type
Gravity Sewer Extension, Pump Stations, & Pressure Sewer Extensions
Primary Reviewer
dean.hunkele
Coastal SWRuIe
Permitted Flow
52,560
Facility
Facility Name
Windpointe Subdivision
Location Address
Owner
Owner Name
Pluris LLC
Dates/Events
Scheduled
Ong Issue App Received Draft Initiated Issuance
9/23/2020 9/1/2020
THOMAS ENGINEERING, PA
www. thomasengineuhk,
1316-B Commerce Drive
Post Office Box 1309
New Bern, NC 28563
Federal Exnress
tracking number: 771404524872
To: NCDEQ
Division of Water Quality
Non -Discharge Permitting
127 Cardinal Drive Extension
Wilmington, NC 28405
Attn: Dean Hunkele
August 31, 2020
Re: Windpointe
Fast Track Sewer System Extension Application (Pluris, LLC)
Onslow County, North Carolina
Dear Dean,
ngmeermgpa.com
P: 252.637.2727
F: 252.636.2448
M.' 252.671.5855
RECEIVED
SEP 01 2020
NCDEQ
WILMINGTON RO
Please find enclosed for the referenced project the original Fast -Track Sewer System
Extension Application (including NC Secretary of State verification), the original Flow
Tracking/Acceptance for Sewer Extension Permit Applications, the USGS Topographic Map
and Street level Map (aerial), the Certificate of Public Convenience and Necessity, the Flow
Reduction approval letter, and one copy of each for your review and approval. Also attached
is the application fee of $480.00 (Thomas Engineering, PA check # 15020).
This application is for the construction and operation upon certification of a 143 gallons per
minute sewer pump station, approximately 3243 linear feet of 4-inch sewer force -main,
approximately 9354 linear feet of 8-inch gravity sewer, and service connections to serve 173
single family residential lots in the Windpointe subdivision located in Onslow County, NC.
Wastewater generated by this project in using the approved flow reduction of 80 gpd per
bedroom is 52,560 llons per day to be treated in the Pluris North Topsail Wastewater
Treatment FaciliW.
If you hav%Any questigns or comments, please do not hesitate to call.
1291
Enclosures
State of North Carolina
DWR Department of Environmental Quality
Division of Water Resources
15A NCAC 02T .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
Division of Water Resources FTA 04-16 & SUPPORTING DOCUMENTATION
Application Number: �J�QQ�I`�J(� (to be completed byDwR)
All items must be completed or the application will be returned
I. APPLICANT INFORMATION:
I. Applicant's name: Pluris. LLC (company, municipality, HOA, utility, etc.)
2. Applicant type: ❑ Individual
❑ Corporation ❑ General Partnership
❑ Federal
❑ State/County ❑ Municipal
3. Signature authority's name: Randy
Hoffer per 15A NCAC 02T .0106(bJ
Title: Regional Manager
4. Applicant's mailing address: 1095 NC Hwy 210
City: Sneads Ferry
State: NC Zip: 28460-
5. Applicant's contact information:
Phone number: (888) 758-7471
Email Address: rhoffer@plurisusa.com
II. PROJECT INFORMATION:
® Privately -Owned Public Utility
❑ Other
1. Project name: Windpointe
2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project
If a modification, provide the existing permit number: WQ00_ and issued date:
If new construction but part of a master plan, provide the existing permit number: W000_
3. County where project is located: Onslow
4. Approximate Coordinates (Decimal Degrees): Latitude: 34.5353' Longitude:-77.3994'
5. Parcel ID (if applicable): 773-60
(or Parcel ID to closest downstream sewer)
III. CONSULTANT INFORMATION:
1. Professional Engineer: John G. Thomas License Number: 10147
Firm: Thomas En ineering. PA
Mailing address: P. 0. Box 1309
City: New Bern State: NC Zip: 28563-
Phone number: (252) 637-2727 Email Address: iohnthomas@thomasen ing eeringpa.com
IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION:
1. Facility Name: Pluris North Topsail Permit Number: W00005849
Owner Name: Pluris, LLC
V. RECEIVING DOWNSTREAM SEWER INFORMATION (if different than WWTF):
1. Permit Number(s): W00034485 Downstream (Receiving) Sewer Size: 6 inch
System Wide Collection System Permit Number(s) (if applicable): WQCS00275
Owner Name(s):
FORM: FTA 04-16 Page 1 of 5
VI. GENERAL REQUIREMENTS
1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached?
® Yes ❑No ❑N/A
2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached?
❑ Yes [—]No ®N/A
3. If the Applicant is a Home/Property Owners' Association. has an Operational Agreement (FORM: HOA) been attached?
❑ Yes ❑No ®N/A
4. Origin of wastewater: (check all that apply):
® Residential Owned ❑ Retail (stores, centers, malls) ❑ Car Wash
❑ Residential Leased ❑ Retail with food preparation/service ❑ Hotel and/or Motels
❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool /Clubhouse
❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash
❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment)
5. Nature of wastewater: 100 % Domestic/Commercial % Commercial
% Industrial (See 15A NCAC 02T .0103(20))
"Is there a Pretreatment Program in effect? ❑ Yes ❑ No
6. Hasa flow reduction been approved under 15A NCAC 02T .0114(f)? ®Yes ❑ No
➢ If yes, provide a copv of flow reduction approval letter
7. Summarize wastewater generated by project:
Establishment Type (see 02T.0114(fl)
Daily Design Flow °"
No. of Units
Flow
3 bedroom single family residential units
240 gaVunit
52
12,480 GPD
4 bedroom single family residential units
320 gal/unit
104
33,280 GPD
5 bedroom single family residential units
400 gal/unit
17
6,800 GPD
gal/
GPD
gal/
GPD
gal/
GPD
Total
52,560 GPD
a See 15A NCAC 02T .0114(b). (d). (e)(1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per
dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas;
and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined
in G.S. 42A-4).
b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01141 shall be
determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data.
8. Wastewater generated by project: 52560 GPD (per 15A NCAC 02T .0114)
➢ Do not include future flows or previously permitted allocations
If permitted flow is zero, indicate why:
❑ Pump Station or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line
❑ Flow has already been allocated in Permit Number:
❑ Rehabilitation or replacement of existing sewer with no new flow expected
❑ Other (Explain):
FORM: FTA 04-16 Page 2 of 5
VIL GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T .0305 & MDC (Gravity Sewers):
1. Summarize gravity sewer to be permitted:
Size (inches)
Length (feet)
Material
8
8537
PVC
8
817
DIP
�u
A3 1
➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria
➢ Section III contains information related to minimum slopes for gravity sewer(s)
➢ Oversizing lines to meet minimum slope requirement is not allowed and a violation of the MDC
VIII. PUMP STATION DESIGN CRITERIA (If Applicable) —02T .0305 & MDC (Puma Stations/Force Mains):
COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
1. Pump station number or name: Windpointe
2. Approximate Coordinates (Decimal Degrees): Latitude: 34.5353' Longitude:-77.3994°
3. Design flow of the pump station:.052560 millions gallons per day (firm capacity)
4. Operational point(s) of the pump(s): 143 gallons per minute at 152 feet total dynamic head (TDH)
5. Summarize the force main to be permitted (for this Pump Station):
Size (inches)
Length (feet)
Material
4
3053
PVC
4
190
DIP
6. Power reliability in accordance with 15A NCAC 02T .0305(h)(1):
® Standby power source or pump with automatic activation and telemetry - 15A NCAC 02T .0305(h)(1)(B)*.
➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
➢ Must be permanent to facility
Or if the pump station has an average daily flow less than 15,000 gallons per day:
❑ Portable power source with manual activation, quick -connection receptacle and telemetry - 15A NCAC 02T
.0305(h)(1)(C)
or
❑ Portable pumping unit with plugged emergency pump connection and telemetry - 15A NCAC 02T .0305(h)(1)(C):
➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant (draft agreement)
and is compatible with the station.
➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage
capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided
in the case of a multiple station power outage.
FORM: FTA 04-16 Page 3 of 5
IX. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T.0305(f)):
1. Does the project comply with all separations found in 15A NCAC 02T.0305(f) & (g)
➢ 15A NCAC 02T.0305 contains minimum separations that shall be provided for sewers stems:
® Yes ❑ No
Setback Parameter*
Separation Required
Storm sewers and other utilities not listed below vertical
24 inches
Water mains vertical -water over sewer including in benched trenches
18 inches
Water mains horizontal
10 feet
Reclaimed water lines vertical - reclaimed over sewer
18 inches
Reclaimed water lines horizontal - reclaimed over sewer
2 feet
**Any private or public water supply source, including any wells, WS-1 waters of Class I or
Class II impounded reservoirs used as a source of drinking water
100 feet
*"Waters classified WS (except WS-1 or WS-V), B, SA, ORW, HQW, or SB from normal
high water or tide elevation and wetlands see item IX.2
50 feet
**Any other stream, lake, impoundment, or ground water lowering and surface drainage
ditches
10 feet
Any building foundation
5 feet
Any basement
10 feet
Top sloe of embankment or cuts of 2 feet or more vertical height
10 feet
Drainage systems and interceptor drains
5 feet
Any swimminp pools
10 feet
Final earth grade vertical
36inches
➢ 15A NCAC 02T.0305(e) contains alternatives where separations in 02T.0305(f) cannot be achieved.
➢ **Stream classifications can be identified using the Division's NC Surface Water Classifications webnaee
➢ If noncompliance with 02T.0305(f) or (R), see Section X of this application
2. Does the project comply with separation requirements for wetlands? (50 feet of separation) ❑ Yes ® No ❑ N/A
➢ See the Division's draft separation requirements for situations where separation cannot be meet
➢ No variance is required if the alternative design criteria specified is utilized in design and construction
➢ As built documents should reference the location of areas effected
3. Does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ® Yes ❑ No ❑ N/A
➢ This would include Trout Buffered Streams per 15A NCAC 213.0202
4. Does the project require coverage/authorization under a 404 Nationwide or ® Yes ❑ No
individual permits or 401 Water Quality Certifications?
➢ Information can be obtained from the 401 & Buffer Permitting Branch
5. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permits/certifications)? ® Yes ❑ No
Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications are being prepared, have
been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and
sedimentation control plans, stormwater management plans, etc.).
6. Does this project include any sewer collection lines that are deemed "high -priority?"
Per 15A NCAC 02T.0402, "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer
positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer.
[-]Yes ® No ❑ N/A
➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location).
High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections
documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System -Wide Collection permit.
FORM: FTA 04-16 Page 4 of 5
X. CERTIFICATIONS:
1. Does the submitted system comply with 15A NCAC 02' the Minimum Design Criteria for the Permitting of Pump Stations
and Force Mains (latest version). and the Gravity Sewer Minimum Design Criteria (latest version) as applicable?
® Yes ❑ No
If No, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for
review. Approval of the request Is required m•lor to submittal of the Fast Track Application and sunpm•tine documents
2. Professional Engineer's Certification:
� s attest that this application for
name from Application Item I11.1.)
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications,
engineering calculations, and all other supporting documentation to the best of my knowledge. 1 further attest that to the best
of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer
Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting
of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this
submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and
have judged it to be consistent with the proposed design.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowin makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 pis nneanor, which may
include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation.
\hurt
North Carolina Professional Engineer's seal, signature, and date: A p/
Q Y
�= AI.
10147
Co
G114
t.........-............F.(.I..I..i..i..�.k.\.�......................
3. Applicant's Certification per 15A NCAC 02T .0106(b)_
attest that this application for
title from & Application Item I..)
has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of
this application are not completed and that if all required supporting documentation and attachments are not included, this
application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non -
discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties,
injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water Resources should a condition
of this permit be violated. I also understand that if all required parts of this application package are not completed and that if
all required supporting information and attachments are not included, this application package will be returned to the as
incomplete.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.61B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000 as well as civil penalties tip to $25,000 per violation.
Signature: Date: <
FORM: FTA 04-16 Page 5 of 5
State of North Carolina
Department of Environmental Quality
Division of Water Resources
Flow Tracking/Acceptance for Sewer Extension Applications
(FTSE 04-16)
Entity Requesting Allocation: Pluris LLC
Project Name for which flow is being requested: Windpoint
More than one FTSE may be required for a single project if the owner of the WWTP is not responsible for all pump
stations along the route of the proposed wastewater flow.
I. Complete this section only if you are the owner of the wastewater treatment plant.
a. WWTP Facility Name: Pluris North Topsail WWTP
b. WWTP Facility Permit #: WO0005849
All flows are in MGD
c. WWTP facility's permitted flow 1,542
d. Estimated obligated flow not yet tributary to the WWTP 0.40085
e. WWTP facility's actual avg. flow 0.66506
f. Total flow for this specific request 0.05256
g. Total actual and obligated flows to the facility 1.11847
h. Percent of permitted flow used 72%
II. Complete this section for each pump station you are responsible for along the route of this
proposed wastewater flow.
List pump stations located between the project connection point and the WWTP:
(A)
(B)
(C)
(D)=(B+C) (E)=(A-D)
Design
Obligated,
Pump
Average Daily
Approx.
Not Yet
Total Current
Station
Firm Flow**
Current Avg.
Tributary
Flow Plus
(Name or
Capacity, * (Firm / pi),
Daily Flow,
Daily Flow,
Obligated Available
Number)
MGD MGD
MGD
MGD
Flow Capacity***
The Firm Capacity of any pump station is defined as the maximum pumped flow that
can be achieved with the largest pump taken out of service.
** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking
factor (pf) not less than 2.5.
*** A Planning Assessment Addendum shall be attached for each pump station located
between the project connection point and the WWTP where the Available Capacity is <0.
Downstream Facility Name (Sewer): North Topsail South Consolidation
Downstream Permit Number: WQ0034485
Page 1 of 6
FTSE 04-16
III. Certification Statement:
I Randy Hoffer, Regional Manager certify to the best of my knowledge that the addition of
the volume of wastewater to be permitted in this project has been evaluated along the route to the
receiving wastewater treatment facility and that the flow from this project is not anticipated to
cause any capacity related sanitary sewer overflows or overburden any downstream pump station
en route to the receiving treatment plant under normal circumstances, given the implementation
of the planned improvements identified in the planning assessment where applicable. This
analysis has been performed in accordance with local established policies and procedures using
the best available data. This certification applies to those items listed above in Sections I and II
plus all attached planning assessment addendums for which I am the responsible party.
Signature of this form indicates acceptance of this wastewater flow.
Signing Official
WE
Page 2 of 6
FTSE 04-16
w
IV
,tea °�. l� `l\�� �' 1,=``v�3 � {t-•I"��w3 ' � ° w-
s CO,-��:� ,� �•< �� ' ,
24
2: