HomeMy WebLinkAboutNC0007064_Compliance Evaluation Inspection_20200917DocuSign Envelope ID: B1751 D35-F2C3-4080-AOD6-FAFE18400147
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0007064 I11 121 20/09/17 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I ni I 71 I 74 79 I I I I I I I80
701a I 711 L
L—I L -1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09:45AM 20/09/17
18/05/01
Brunswick Steam Electric Plant
8470 River Rd SE
Exit Time/Date
Permit Expiration Date
Southport NC 28461
11:45AM 20/09/17
22/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Charles David Nelson//910-457-3600 /
Charles K Wilson/ORC/910-457-3687/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
John Krakuszski,PO Box 10429 Southport NC 28461/Plant Manager//
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Do
Brian S Wcusignedby: DWR/WIRO WQ/910-796-7341/ 9/23/2020
� . ' I'1CS1
E�1
14 2EF61AOAA2445...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
c1uuSiig'need by: 9/2 3/2020
ADo�
rVWY C.ii.(A�sm4t,-, 6"
3 B,F� 4ACZDG44,...
EPA Form 356&J ev J 64 Previous editions are obsolete.
Page#
DocuSign Envelope ID: B1751 D35-F2C3-4080-AOD6-FAFE18400147
NPDES yr/mo/day Inspection Type
NC0007064 I11 12I 20/09/17 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
A routine NPDES inspection was conducted with the assistance of Chuck Nelson and Charles Wilson.
Staff addressed all questions presented and provided access to all facility areas requested.
A review of data submitted for the ocean outfall temperature monitoring event on 2/18/20 was reviewed
Data submitted demonstrate compliance with the temperature monitoring requirements and standards
as described in permit condition A(1).
Please note additional comments in each section of the report.
Page#
DocuSign Envelope ID: B1751 D35-F2C3-4080-AOD6-FAFE18400147
Permit: NC0007064 Owner -Facility: Brunswick Steam Electric Plant
Inspection Date: 09/17/2020 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes
No
NA
NE
Is the plant generally clean with acceptable housekeeping? 0
❑
❑
❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
❑
❑
❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Two site domestic treatment facilities were combined in early 2019 to be treated at one
facility (outfall 010). The effluent pipe from the former 004 domestic treatment facility was
filled with concrete. The current facility is an SBR system with 4 treatment trains (2 are
currently idle). The internal outfall 003 Radwaste Treatment System discharges by batch
from one of two internal water treatment process storage tanks at the rate of 20-30k gallons
approximately twice per week. Internal outfall 005 discharges primarily stormwater. The
receiving basin is planned to be lined with a synthetic liner. Internal outfall 006 is permitted
to discharge metal cleaning wastes; no reported discharges during this permit cycle.
Internal outfall 011 discharges primarily stormwater and water extracted from wells
surrounding the 005 basin. Internal outfall 012 discharges groundwaters to 011; no
discharge reported this permit cycle. Twelve site pump stations are monitored by telemetry
and are routinely inspected
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Station staff provided access to all areas requested during the visit
Record Keeping
Yes
No
NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
❑
Name of individual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses
❑
Transported COCs ❑
Are DMRs complete: do they include all permit parameters? 0 ❑ ❑ ❑
Page# 3
DocuSign Envelope ID: B1751 D35-F2C3-4080-AOD6-FAFE18400147
Permit: NC0007064
Inspection Date: 09/17/2020
Record Keeping
Owner -Facility: Brunswick Steam Electric Plant
Inspection Type: Compliance Evaluation
Yes No NA NE
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc 0 ❑ ❑ ❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: A brief QA check of facility effluent sample commercial lab reports and submitted DMRs
found no discrepancies in transfer of data.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: Flow at 001 is reported from pumping logs. Flow at the 010 outfall is measured using
a flow
totalizer (since discharge is by batch). The meter is routinely
checked for accuracy
versus
measurement at the plant effluent parshall flume
Sequencing Batch Reactors
Yes
No
NA NE
Type of operation:
Is the reactor effluent free of solids?
0
❑
❑
❑
Does minimum fill time correspond to the peak hour flow rate of the facility?
❑
❑
❑
Is aeration and mixing cycled on and off during fill?
❑
❑
❑
The operator understands and can explain the process?
❑
❑
❑
Comment: Operators are very knowledgeable of the treatment plant process and operational controls.
Waste sludge from the plant is pressed and dried on site. Screenings from the plant influent
screening process and the dried sludge are transported to the site low-level radwaste
storage facility until it can be disposed
Effluent Sampling
Yes
No
NA NE
Is composite sampling flow proportional?
❑
❑
N
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
Page# 4
DocuSign Envelope ID: B1751 D35-F2C3-4080-AOD6-FAFE18400147
Permit: NC0007064 Owner -Facility: Brunswick Steam Electric Plant
Inspection Date: 09/17/2020 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑
representative)?
Comment: All samples are grab -type. Total chlorine residual is measured monthly from 001 at the
Caswell Beach pump station using a Hach colorimetric kit. There have been no reported
chlorine residual detections during this permit cycle.
Page# 5