Loading...
HomeMy WebLinkAboutSW4070701_Add Info_20200226 Farkas, Jim J From:Farkas, Jim J Sent:Wednesday, February 26, 2020 9:16 AM To:Chris Brown Cc:j.meliski@mcgillassociates.com Subject:Echota IV SW4070701 Chris, I was looking over the additional information you provided on 2/17/2020. Everything looks good except for a few small issues: Please correct the following: 1) Clearly indicate on the plans which typical section applies to each swale. For example, swale 3, is shown to use the typical section for the v-ditch and also the drainage swale w/ 6” riprap while others, such as swale 12, do not have a listed typical section associated with them. 2) Please show or clarify in the calculations why certain swales use a Manning’s roughness coefficient of 0.035 and others use 0.104. Please provide a reference of some sort if using the 0.104 roughness coefficient. 3) Since the proposed side slopes of the vegetated conveyances are 2:1, please provide calculations showing stability of the channels during a 10-year storm. Please also indicate the method used to calculate the actual shear stress and provide a reference for the maximum allowable shear stress used. 4) Please sign & seal the calculations. 5) Please review the calculations for accuracy. For example, swale 9 appears to receive flow from swales 6, 7, & 8 (flow rates of 1.4 cfs, 0.7 cfs, & 0.8 cfs respectively). The flow reported for swale 9 (1.1 cfs) is less than the sum of the flow of the contributing swales. Please clearly indicate in the calculations which swales flow into each other and ensure that the calculations are correct. While not required, it is recommended that, where possible, riprap lined swales be avoided as they are not considered vegetated conveyances. Please provide the following: - 2x hard copies and 1 x electronic copy uploaded to Laserfiche of the applicable updated plan sheets. - 2x hard copies and 1 x electronic copy uploaded to Laserfiche of the title sheet indicating the revisions to the plan set. - 1x hard copy of the corrected swale calculations or 1x response to comments explanation for using the different Manning’s n values. - 1x hard copy of the swale shear calculations for the 10-year storm. - 1x original, signed hard copy of the calculation coversheet. - 1x electronic copy uploaded to Laserfiche of the full, corrected calculations. Since these are really minor things, once I get the hard copies, anything else that may have changed from addressing these issues, and the documents are uploaded to Laserfiche (Provided everything is still in order), we can issue the permit without doing a formal 30-45 day review. Let me know if you have any questions. Jim Farkas Environmental Engineer North Carolina Department of Environmental Quality 1 Division of Energy, Mineral, & Land Resources – Stormwater Program 512 N. Salisbury Street 1612 Mail Service Center Raleigh, NC 27699-1612 (919) 707-3646 Jim.Farkas@ncdenr.gov Email correspondence to and from this address is subject to the North Carolina Public Records Law and may be disclosed to third parties. 2