September 4, 2020
CERTIFIED MAIL #: 70191120 0000 8361 0520
RETURN RECEIPT REQUESTED
Mr. Tony Konsul
Carolina Water Service, Inc. of NC
Post Office Box 240908
Charlotte, North Carolina 28224
Subject: Notice of Violation
Compliance Evaluation Inspection
Riverpointe WWTP
NPDES Permit No. NCO071242
Mecklenburg County
Tracking #: NOV-2020-PC-0402
Dear Mr. Konsul:
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject
facility on August 27, 2020, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible
Charge (ORC) of our findings by forwarding a copy of the enclosed report.
This report is being issued as a Notice of Violation (NOV) due to the following:
- Failure to collect a minimum of 100 ml. per aliquot/grab sample on composite sampler (repeat violation);
- Failure to perform all required facility visitations by either the designated ORC or Backup ORC during
multiple weeks in June and July 2020.
All are violations of the subject NPDES Permit and North Carolina General Statute (G.S.) 143-215.1 as detailed
in the Record Keeping/Summary and Effluent Sampling Sections of the attached report. Please be advised that
G.S. 143-215.6A provides for a civil penalty assessment of not more than twenty-five thousand dollars
($25,000.00), or twenty-five thousand dollars ($25,000.00) per day when the violation is of a continuing nature,
against any person who violates or fails to act in accordance with the terms, conditions, or requirements of any
permit issued pursuant to G.S. 143-215.1. Penalties may also be assessed for any damage to surface waters of the
State that may result from the violation.
�� Office
Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR7H ORROLINA i
�,"r1 J m Em^'m'"^e^ai Qmli /`� 704.663.1699
Tony Konsul
Page Two
September 4, 2020
It is requested that a written response be submitted to this Office by September 24, 2020, detailing the actions
taken to address these violations. In responding, please address your comments to the attention of Mr. Wes Bell.
Should you have any questions concerning this letter, please do not hesitate to contact Mr. Bell at (704) 235-
2192, or via email at wes.bell(&ncdenr. gov.
Sincerely,
DocuSigned by:
A14CC681 AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure:
Inspection Report
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO071242 I11 121 20/08/27 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70LJ 71 I„ I 72 L71 74 79
I I I I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
11:18AM 20/08/27
20/08/01
Riverpointe WWTP
15820 Alloway Ln
Exit Time/Date
Permit Expiration Date
Charlotte NC 28278
01:08PM 20/08/27
25/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Charles Edward Wood/ORC/704-621-9204/
Danny Lemont Hoyle//704-922-4086 /
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Tony Konsul,PO Box 240908 Charlotte NC 282240908/Director of
Operations/704-525-7990/7045258174 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
cuSigned by:
Wes Bell DWR/MRO WQ/704-663-1699 Ext.2192/ 9/3/2020
2 re&
E��
1696D90=437...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
9/4/2020
AiaccsatAFz7azs... Page#
NPDES yr/mo/day Inspection Type
NCO071242 I11 12I 20/08/27 117 18 I c
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
RECORD KEEPING SECTION cont'd:
The chain of custody form (CoC) is in the process of being updated to show sample type and
preservative (if applicable) for each parameter sampled and the time when samples were placed on
ice. Note: An updated CoC (draft) has been recently submitted to this Office for review.
The facility is currently classified as a Grade 2 Biological water pollution control treatment system
(WPCTS). The subject NPDES Permit (Part 11, Section C(1) Certified Operator) requires Grade 2
Biological WPCTS to be visited by either the designated ORC or one of the designated Backup ORCs
five days per week excluding holidays. The treatment facility did not meet these visitation requirements
during the weeks of 6/14/20, 6/28/20, 7/5/20 and 7/12/20. In addition, the permittee will need to updatE
the current listing of designated Backup ORCs on file with the Division.
Page#
Permit: NCO071242 Owner -Facility: Riverpointe WWTP
Inspection Date: 08/27/2020 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The last compliance evaluation inspection at this facility was performed by DWR staff on
5/14/19.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Page# 3
Permit: NCO071242 Owner -Facility: Riverpointe WWTP
Inspection Date: 08/27/2020 Inspection Type: Compliance Evaluation
Record Keeping Yes No
NA NE
Comment: The records reviewed during the inspection were organized and well maintained. Discharge
Monitoring Reports (eDMRs) were reviewed for the period July 2019 through June 2020. All
monitoring frequencies were correct. Daily maximum effluent violations were reported in
July 2019 (TSS), August 2019 (fecal coliform), October 2019 (TSS), January 2020
(TSS)
and March 2020 (TSS). A monthly average effluent TSS violation was also reported in
January 2020. These violations will be separately addressed by the Division through
the
issuances of Notice of Violations (NOVs) and/or NOV/civil penalty assessments.
See "Summary" Section for additonal comments.
Laboratory Yes No
NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑
❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑
❑ ❑
# Is the facility using a contract lab? 0 ❑
❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑
0 ❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑
0 ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑
0 ❑
Comment: On -site field analvses (dissolved oxvaen. DH. temDerature. TRC) are Derformed under
Carolina Water Service of NC's field laboratory certification #5228. K&W Laboratories
(Certification #559) has also been contracted to provide analytical support for all effluent
analyses except field.
The dissolved oxygen meter calibration was not documented on the 6/30/20 effluent
sampling event. Please be advised that the dissolved oxygen meter calibrations must be
performed and documented each day the meter is used for effluent analyses (Reference:
North Carolina Wastewater/Groundwater Lab Certification approved procedure
for analysi
of dissolved oxygen)
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
0 ❑ ❑ ❑
Is sample collected below all treatment units?
0 ❑ ❑ ❑
Is proper volume collected?
❑ 0 ❑ ❑
Is the tubing clean?
0 ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0 ❑ ❑ ❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0 ❑ ❑ ❑
representative)?
Page# 4
Permit: NCO071242
Inspection Date: 08/27/2020
Owner -Facility: Riverpointe WWTP
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Comment: The subiect Dermit reauires composite and arab effluent samDles.The aliauot volume was
initially well below 100 mis. during the on -site inspection; however, the ORC corrected the
sampler program to ensure a minimum of 100 mis per aliquot will be collected during future
sampling events. Note: The failure to collect a minimum of 100 mis. per aliquot was noted it
the previous inspection. Please be advised that the subiect permit requires a minimum of
100 mis. per aliquot/grab sample (Permit Condition Reference: Part II, Section A Definitions
— Composite Sample).
Monthly (at a minimum) sampler aliquot checks should be performed and documented.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facilitv aDDeared to be DrODerIv operated and well maintained.
Process control measurements were being documented and maintained on -site. This
Office recommends in the incorporation of periodic MLSS and MLVSS testing in the aeration
basins to assist the operations staff in maintaining the proper solids inventory.
The telemetry type alarm system (Mission) was tested and operated properly during the
inspection.
Bar Screens
Yes
No
NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
0
❑
❑
❑
Page# 5
Permit: NCO071242 Owner -Facility: Riverpointe WWTP
Inspection Date: 08/27/2020 Inspection Type: Compliance Evaluation
Equalization Basins Yes No NA NE
# Is basin size/volume adequate? 0 ❑ ❑ ❑
Comment:
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
0
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0
❑
❑
❑
Comment: Lime is added (as -needed basis) to maintained appropriate alkalinity/pH levels. The
powdered lime is added directly into the equalization tank. This office recommends the
permittee to investigate the usage of a continuous feed system (aqueous) to provide a more
consistent and uniform application of lime throughout the day.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Filtration (High Rate Tertiary)
Type of operation:
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Yes No NA NE
Cross flow
Page# 6
Permit: NCO071242
Inspection Date: 08/27/2020
Filtration (High Rate Tertiary)
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Comment:
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Owner -Facility: Riverpointe WWTP
Inspection Type: Compliance Evaluation
Comment: Liquid chlorination would be used as a backup.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
■
❑
❑
❑
■
❑
❑
❑
Yes
No
NA NE
■
❑
❑
❑
❑
❑
❑
■
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: The flow meter is calibrated twice per year and was last calibrated on 6/24/2020 by B.W.
Allen Co.
Pump Station - Effluent
Yes
No
NA
NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
❑
❑
0
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment:
Page# 7
Permit: NC0071242 Owner -Facility: Riverpointe WWTP
Inspection Date: 08/27/2020 Inspection Type: Compliance Evaluation
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
❑
❑
0
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The effluent appeared clear with no floatable solids or foam. The effluent is discharged into
the receiving stream (Lake Wylie) via submerged outfall.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Comment: The sludge dewatering box was operational and in service. The dewatering box is removed
by L&L Environmental Services.
Standby Power
Yes
No
NA
NE
Is automatically activated standby power available?
0
❑
❑
❑
Is the generator tested by interrupting primary power source?
0
❑
❑
❑
Is the generator tested under load?
0
❑
❑
❑
Was generator tested & operational during the inspection?
0
❑
❑
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
0
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
0
❑
❑
❑
Is the generator fuel level monitored?
0
❑
❑
❑
Page# 8
Permit: NC0071242
Inspection Date: 08/27/2020
Standby Power
Owner -Facility: Riverpointe WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The backup generator is tested (automatically) under load weekly. A contracted company
(Kraft Power) services the generator twice per year.
Page#