HomeMy WebLinkAboutNC0065986_CEI_20200828
August 28, 2020
Evans Jones
Dogwood Trails Homeowners Association Inc.
PO Box 63
Maggie Valley, NC 28751
SUBJECT: Compliance Inspection Report
Dogwood Trails Subdivision
NPDES WW Permit No. NC0065986
Haywood County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Dogwood Trails Subdivision on
8/24/2020. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0065986. Please carefully review the
comments noted in the enclosed copy of the inspection report.
Additionally, after reviewing historical records, it appears there are discrepancies between the originally
permitted AtoC and the permitted hydraulic capacity of the facility. Please provide documentation that shows
the currently installed treatment components sizing. This request will be added to the renewed permit, if the
additional information is not received before its issuance.
DocuSign Envelope ID: 0ACB22AB-99AA-4575-A1AD-E533360A5714
If you should have any questions, please do not hesitate to contact me at 828-296-4686 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist II
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: LF
Environmental Inc.
DocuSign Envelope ID: 0ACB22AB-99AA-4575-A1AD-E533360A5714
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0065986 20/08/24 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Dogwood Trails Subdivision
Evans Cove Rd
Maggie Valley NC 28751
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
01:00PM 20/08/24 16/08/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Joedavid Matthew Hall/ORC/828-586-5588/
Other Facility Data
02:00PM 20/08/24 21/01/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Evans Jones,PO Box 63 Maggie Valley NC 28751//803-730-1879/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Mikal Willmer DWR/Division of Water Quality/828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 0ACB22AB-99AA-4575-A1AD-E533360A5714
8/28/2020
8/28/2020
NPDES yr/mo/day
20/08/24
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Mikal Willmer, with the Asheville Regional Office, conducted a compliance evaluation inspection of the
Dogwood Trails WWTP on August 25, 2020. This inspection was conducted to determine whether the
facility is being operated and maintained in compliance with NPDES Permit No. NC0065986. Joedavid
Hall, ORC, was present and assisted in the inspection.
Overall the facility appears to be operated and maintained in compliance.
This facility is permitted for 0.02 MGD and is currently in renewal. Please verify the hydraulic capacity
of this facility. Historical records indicate it was initially planned for a phased expansion with an initial
AtoC approval from the Division for a 0.01 MGD WWTP. A request will be made to verify this during the
permit renewal. This is not currently an issue based on average flows; however, as expansion occurs it
may begin to exceed the facilities treatment capacity, if only a 0.01 MGD package plant was installed.
The ORC indicated new homes were being constructed.
All homes gravity feed into the WWTP. Environmental Inc. helps with CS issues when contracted to do
so. There were no noted issues with trash or debris in the WWTP at the time of the inspection. The
ORC believes each home may have a settling tank. Should facility staff begin to see significant debris
entering the WWTP, a bar screen is recommended. Solids are hauled from the facility once a year.
Soda ash is used to adjust pH as needed. Mr. Hall does not believe there are any major issues with I&I
in the neighborhood based on flows during rain events.
The permit is in renewal. When finalized, please ensure a copy is made available to facility staff as
there is always the potential for updates to permit requirements.
NC0065986 17 (Cont.)
Page#2
DocuSign Envelope ID: 0ACB22AB-99AA-4575-A1AD-E533360A5714
Permit:NC0065986
Inspection Date:08/24/2020
Owner - Facility:
Inspection Type:
Dogwood Trails Subdivision
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
ORC checks DO and pH.Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Need to verify the hydraulic capacity of the facility. Discrepancies in permitted flow and
historical records for phasing.
Comment:
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Facility is permitted for 0.02 MGD and only requires instantaneous flow measurement.
Flows are determined by volume over time.
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Page#3
DocuSign Envelope ID: 0ACB22AB-99AA-4575-A1AD-E533360A5714
Permit:NC0065986
Inspection Date:08/24/2020
Owner - Facility:
Inspection Type:
Dogwood Trails Subdivision
Compliance Evaluation
Aeration Basins Yes No NA NE
ORC attempts to keep DOs within the aeration basin between 1 and 2 mg/L. Only one
blower is needed to maintain DOs. Blowers are alternated and run approximately 15
minutes every hour.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
ORC reports solids are hauled about once a year. No issues with pass through debris or
floating solids.
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?1
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
ORC checks chlorine levels to ensure appropriate disinfection and dechlorination.Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Page#4
DocuSign Envelope ID: 0ACB22AB-99AA-4575-A1AD-E533360A5714
Permit:NC0065986
Inspection Date:08/24/2020
Owner - Facility:
Inspection Type:
Dogwood Trails Subdivision
Compliance Evaluation
De-chlorination Yes No NA NE
Tablets are in HDPE containers and stored in the WWTP building. ORC is using one tube
for both dechlor and chlorine.
Comment:
Are tablet de-chlorinators operational?
Number of tubes in use?1
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Grab samples are collected post dechlor since it’s difficult to collect samples from the
outfall.
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Outfall is accessible, but difficult to collect samples from due to location in bank.Comment:
Page#5
DocuSign Envelope ID: 0ACB22AB-99AA-4575-A1AD-E533360A5714
Certificate Of Completion
Envelope Id: 0ACB22AB99AA4575A1ADE533360A5714 Status: Completed
Subject: Please DocuSign: NC0065986_CEI_20200828.docx, NC0065986_CEI_20200828.insp.pdf
Source Envelope:
Document Pages: 7 Signatures: 3 Envelope Originator:
Certificate Pages: 2 Initials: 0 Mikal Willmer
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-05:00) Eastern Time (US & Canada)
217 W. Jones Street
Raleigh, NC 27699
Mikal.willmer@ncdenr.gov
IP Address: 149.168.204.10
Record Tracking
Status: Original
Aug 28, 2020 | 09:31
Holder: Mikal Willmer
Mikal.willmer@ncdenr.gov
Location: DocuSign
Signer Events Signature Timestamp
Mikal Willmer
mikal.willmer@ncdenr.gov
Environmental Specialist
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 149.168.204.10
Sent: Aug 28, 2020 | 09:37
Viewed: Aug 28, 2020 | 09:37
Signed: Aug 28, 2020 | 09:37
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
Daniel Boss
daniel.boss@ncdenr.gov
Environmental Specialist
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 149.168.204.10
Sent: Aug 28, 2020 | 09:37
Viewed: Aug 28, 2020 | 09:38
Signed: Aug 28, 2020 | 09:51
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted Aug 28, 2020 | 09:37
Certified Delivered Security Checked Aug 28, 2020 | 09:38
Signing Complete Security Checked Aug 28, 2020 | 09:51
Envelope Summary Events Status Timestamps
Completed Security Checked Aug 28, 2020 | 09:51
Payment Events Status Timestamps