HomeMy WebLinkAboutWQ0041881_Application (FTSE)_20200825Central Files: APS _ SWP -
8/7/2020
Permit Number WQ0041881
Program Category
Non -discharge
Permit Type
Gravity Sewer Extension, Pump Stations, & Pressure Sewer Extensions
Primary Reviewer
dean.hunkele
Coastal SWRule
Permitted Flow
Facility
Facility Name
Bountiful Village
Location Address
Owner
Permit Tracking Slip
Status
Project Type
In review
New Project
Version
Permit Classification
A
Individual
Permit Contact Affiliation
Major/Minor Region
Minor Wilmington
County
New Hanover
Facility Contact Affiliation
Owner Name Owner Type
Cape Fear Public Utility Authority Government - Municipal
Owner Affiliation
James R. Flechtner
PE
235 Government Center Dr
Dates/Events Wilmington NC 28403
Scheduled
Orig Issue App Received Draft Initiated Issuance
8/6/2020
Regulated Activities
PORT CITY CONSULTING ENGINEERS, PLLC
6216 STONEBRIDGE ROAD
WILMINGTON, NORTH CAROLINA,
28409
(910)599-1744
TO: Dean Hunkele
NCDWQ
127 Cardinal Drive
Wilmington, NC 28405
ME ° OO v VR'/i M00'/U
DATE 8/06/20
JOB NO.
ATTENTION
PHONE #
RE: Bountiful Village
Sewer Permit Submittal
Public Sewer
NCDEQ
WE ARE SENDING YOU ® Attached ❑ Under separate cover
❑ Shop Drawings ❑ Prints ❑ Plans
❑ Copy of Letter ❑ Change order ❑ Diskette
❑ Samples
El
WILMINGTON RG
the following items:
❑ Specifications
COPIES
DATE
NO.
DESCRIPTION
1
Check for 480 each for application fee
2
One Original & one copy of: Fast Track Application and
Flow Tracking Form
1
USGS Quad Sheet
1
Sewer Narrative w/ pump station calculations
THESE ARE TRANSMITTED as checked below:
❑
copies for
® For approval
❑ Approved as submitted
Resubmit
approval
copies for
❑ For your use
❑ Approved as noted
❑ Submit
_distribution
❑ As requested
❑ Returned for corrections
❑ Return
corrected prints
❑ For review and
comment
❑
❑ FOR BIDS DUE 20 ❑ PRINTS RETURNED AFTER LOAN TO US
COPY TO: File
SIGNED: MA.Yk.N. ftar9'r0VP1
If enclosures are not as noted, kindly notify us at once.
State of North Carolina
DWR Department of Environmental Quality
Division of Water Resources
15A NCAC 02T .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
Dlvlslon of Water Resources FTA 04-16 & SUPPORTING DOCUMENTATION
Application Number: lla&WX 1a I (to be completed by DWR)
All items must be completed or the application will be returned
I. APPLICANT INFORMATION:
1. Applicant's name: Cane Fear Public Utility Authority (company, municipality, HOA, utility, etc.)
2. Applicant type: ❑ Individual ❑ Corporation ❑ General Partnership ❑ Privately -Owned Public Utility
❑ Federal ❑ State/County ❑ Municipal ® Other
3. Signature authority's name: Jeff Theberge. PE per 15A NCAC 02T .0106(b)
Title: Engineering Manager
4. Applicant's mailing address: 235 Government Center Drive
City: Wilmington State: NC Zip: 28403
5. Applicant's contact information:
Phone number: (21Q) 332-6673 Email Address: jefftheberge@cfoua.org
II. PROJECT INFORMATION:
1. Project name: Bountiful Village
2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project
If a modification, provide the existing permit number: W000_ and issued date:
If new construction but part of a master plan, provide the existing permit number: W000_
3. County where project is located: New Hanover
4. Approximate Coordinates (Decimal Degrees): Latitude: 34_30° Longitude:-77_94.
5. Parcel ID (if applicable): R03300-001-037-000
(or Parcel ID to closest downstream sewer)
III. CONSULTANT INFORMATION:
1. Professional Engineer: Mark N. Hargrove License Number: 019742
Finn: Port City Consulting Engineers, PLLC
Mailing address: 6216 Stonebrid eg Road
City: Wilmington State: NC Zip: 28409-_
Phone number: (910) 599-1744 Email Address: mhargrovep_ec.rr.com
IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION:
1. Facility Name: James A. Laughlin NSWWTP Permit Number: NC 0023965
Owner Name: Cane Fear Public Utility Authority
V. RECEIVING DOWNSTREAM SEWER INFORMATION (if diffe ent than WWTF):
1. Permit Number(s):WQ(�Q'36�P�' �i2✓ �rra Rw"V
System Wide Collection System Permit Number(s) (if applicable): WQCS_ /
Owner Name(s): CFPUA
FORM: FTA 04-16 Page l of 5
VI. GENERAL REQUIREMENTS
1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached?
❑ Yes ❑No ®N/A
2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached?
[—]Yes ❑No ®N/A
3. If the Applicant is a Home/Property Owners' Association. has an Operational Agreement (FORM: HOA) been attached?
❑ Yes ❑No ®N/A
4. Origin of wastewater: (check all that apply):
® Residential Owned ❑ Retail (stores, centers, malls) ❑ Car Wash
❑ Residential Leased ❑ Retail with food preparation/service ❑ Hotel and/or Motels
❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool /Clubhouse
❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash
❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment)
5. Nature of wastewater : 100 % Domestic/Commercial % Commercial
_ % Industrial (See 15A NCAC 02T .0103(20))
L---->Is there a Pretreatment Program in effect? ❑ Yes ® No
6. Hasa flow reduction been approved under 15A NCAC 02T .0114(f)? ®Yes ®No
➢ If yes, provide a copy of flow reduction approval letter
7. Summarize wastewater generated by project: %h
Establishment Type (see 02T.0114(f)
Daily Design Flow a'b
No. of Units
Flow
Single Family House
240 gal/house
30
7,200 GPD
Single Family House
320 gal/house
5
1,600 GPD
gall
GPD
gal/
GPD
gall
GPD
gall
GPD
Total
8,800 GPD
a See 15A NCAC 02T .0114(b). (d). (e)(1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per
dwelling; proposed unknown non-residential development uses; public access facilities located near high public use
areas; and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals
as defined in G.S. 42A-4).
b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01141 shall
be determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data.
8. Wastewater generated by project: 8 800 GPD (per 15A NCAC 02T .0114)
➢ Do not include future flows or previously permitted allocations
If permitted flow is zero, indicate why:
❑ Pump Station or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line
❑ Flow has already been allocated in Permit Number:
❑ Rehabilitation or replacement of existing sewer with no new flow expected
❑ Other (Explain):
FORM: FTA 04-16 Page 2 of 5
VIL GRAVITY SEWER DESIGN CRITERIA (if Applicable) - 02T .0305 & MDC (Gravity Sewersl:
1. Summarize gravity sewer to be permitted:
Size (inches)
Length (feet)
Material
8
1,373
C900 PVC & DIP
➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria
➢ Section III contains information related to minimum slopes for gravity sewer(s)
➢ Oversizing lines to meet minimum slope requirement is not allowed and a violation of the MDC
VIII. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains):
COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
1. Pump station number or name:.).
2. Approximate Coordinates (Decimal Degrees): Latitude: 34.3003' Longitude:-77,9358'
3. Design flow of the pump station: 0.187 millions gallons per day (firm capacity)
4. Operational point(s) of the pump(s): 130 gallons per minute at 26 feet total dynamic head (TDH)
5. Summarize the force main to be permitted (for this Pump Station):
Size (inches)
Length (feet)
Material
4
300
C900 PVC & DIP
6. Power reliability in accordance with 15A NCAC 02T .0305(h)(1):
® Standby power source or pump with automatic activation and telemetry - 15A NCAC 02T .0305(h)(1)(B)_
➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
➢ Must be permanent to facility
Or if the pump station has an average daily flow less than 15,000 gallons per day:
❑ Portable power source with manual activation, quick -connection receptacle and telemetry - 15A NCAC 02T
.0305(h)(1)(C)
or
❑ Portable pumping unit with plugged emergency pump connection and telemetry - 15A NCAC 02T .0305(h)(1)(C):
➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant (draft agreement)
and is compatible with the station.
➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations'
storage capacities and the rotation schedule of the portable power source or pump, including travel titneframes, shall be
provided in the case of a multiple station power outage.
FORM: FTA 04-16 Page 3 of 5
IX. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T.0305(f)):
1. Does the project comply with all separations found in 15A NCAC 02T.0305(f) & (e)
➢ 15A NCAC 02T.0305(f) contains minimum separations that shall be Drovided for sewer systems:
® Yes ❑ No
Setback Parameter*
Separation Required
Storm sewers and other utilities not listed below vertical
24 inches
Water mains vertical -water over sewer including in benched trenches
18 inches
Water mains horizontal
10 feet
Reclaimed water lines vertical - reclaimed over sewer
18 inches
Reclaimed water lines horizontal - reclaimed over sewer
2 feet
**Any private or public water supply source, including any wells, WS-I waters of Class I or
Class II impounded reservoirs used as a source of drinking water
100 feet
**Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal
high water or tide elevation and wetlands see item IX.2
50 feet
**Any other stream, lake, impoundment, or ground water lowering and surface drainage
ditches
10 feet
Any building foundation
5 feet
Any basement
10 feet
Top slope of embankment or cuts of 2 feet or more vertical height
10 feet
Drainage systems and interceptor drains
5 feet
Any swimming pools
10 feet
Final earth grade vertical
36inches
➢ 15A NCAC 02T.0305(g) contains alternatives where separations in 02T.0305(f) cannot be achieved.
➢ **Stream classifications can be identified using the Division's NC Surface Water Classifications webpaee
➢ If noncompliance with 02T.0305(f) or (g). see Section X of this application
2. Does the project comply with separation requirements for wetlands? (50 feet of separation) ® Yes ❑ No
➢ Seethe Division's draft separation requirements for situations where separation cannot be meet
➢ No variance is required if the alternative design criteria specified is utilized in design and construction
➢ As built documents should reference the location of areas effected
3. Does the project comply with all setbacks found in the river basin rules per 15A NCAC 02B .0200? ® Yes [-]No
➢ This would include Trout Buffered Streams per 15A NCAC 213.0202
4. Does the project comply with an individual 404 Permit or any 401 Certifications? ® Yes ❑ No
➢ Wetland -related permits shall be requested, obtained, and adhered to for projects that impact wetlands or surface waters
➢ Information can be obtained from the 401 & Buffer Permitting Branch
5. Does project comply with 15A NCAC 02T.0105(c)(6 (additional perm is/certifications)?
® Yes [-]No
Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications are being prepared, have
been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and
sedimentation control plans, stormwater management plans, etc.).
6. Does this project include any sewer collection lines that are deemed "high -priority?"
Per 15A NCAC 02T.0402, "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer
positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer.
❑ Yes ® No
➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location).
High priority lines shall be inspected by the permittee or its representative at least once every six -months and
inspections documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System -Wide Collection permit.
FORM: FTA 04-16 Page 4 of 5
X. CERTIFICATIONS:
1. Does the submitted system comply with I SA NCAC 021, the Minimum Design Criteria for the Permitting of Pump Stations
and Force Mains (latest version). and the Gravi Sewer Minimum Design Criteria (latest version) as applicable?
® Yes ❑ No
If No, complete and submit the Variance/Altemative Design Request application (VADC 10-14) and supporting documents
for review. Approval of the request is required prior to submittal of the Fast Track Application and supporting
documents.
2. Professional Engineer's Certification:
I Mark N. Hargrove, PE
attest that this application for
(Professional Engineer's name from Application Item IE.1.)
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications,
engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best
of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer
Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track
Permitting of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain
portions of this submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this
material and have judged it to be consistent with the proposed design.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.613, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation.
......................00.0°0.4"......................
000 eo 0p
North Carolina Professional Engineer's seal, signature, and date:
S/0, q °
0
°
SEAL
019742 0
°°
3. Applicant's Certification per 15A NCAC 02T .0106(b):
I Jeff Theberge, Engineering Manager
attest that this application for
(Signature Authority's name &title from Application Item 1.3 J
has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of
this application are not completed and that if all required supporting documentation and attachments are not included, this
application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non -
discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties,
injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water Resources should a
condition of this permit be violated. I also understand that if all required parts of this application package are not completed
and that if all required supporting information and attachments are not included, this application package will be returned to
me as incomplete.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation.
Signature: L4� Date:7/29/2020
FORM: FTA 04-16 Page 5 of 5
State of North Carolina
Department of Environmental Quality
Division of Water Resources
Flow Tracking for Sewer Extension Applications
(FTSE 10-18)
Entity Requesting Allocation: CH Bountiful Operating, LLC
Project Name for which flow is being requested: Bountiful Village
More than one FTSE may be required for a single project if the owner of the WWTP is not responsible for all pump
stations along the route of the proposed wastewater flow.
I. Complete this section only if you are the owner of the wastewater treatment plant.
a. WWTP Facility Name: James A. Loughlin (Northside) WWTP
b. WWTP Facility Permit #: NPDES NC 0023965
All flows are in MGD
c. WWTP facility's permitted flow 16.000
d. Estimated obligated flow not yet tributary to the WWTP 3.454
e. WWTP facility's actual avg. flow 10.661
f. Total flow for this specific request 0.0088
g. Total actual and obligated flows to the facility 14.123
h. Percent of permitted flow used 88.3
1I. Complete this section for each pump station you are responsible for along the route of this proposed
wastewater flow.
List pump stations located between the project connection point and the WWTP:
(A)
(B)
(C)
(D)=(B+C)
(E)=(A-D)
Design
Obligated,
Pump
Pump
Average
Approx.
Not Yet
Total Current
Station
Station
Firm
Daily Flow**
Current
Tributary
Flow Plus
(Name or
Permit
Capacity, *
(Firm / pl),
Avg. Daily
Daily Flow,
Obligated
Available
Number)
No.
MGD
MGD
Flow, MGD
MGD
Flow
Capacity***
157
N/A
0.816
0.257
0.069
0.182
0.251
0.006
123
N/A
0.441
0.176
0.042
0.023
0.065
0.111
109 N/A 0.197 0.047 0.000 0.009 0.038
* The Firm Capacity (design flow) of any pump station is defined as the maximum pumped flow
that can be achieved with the largest pump taken out of service.
** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking factor
(pi) not less than 2.5, per Section 2.02(A)(4)(c) of the Minimum Design Criteria.
*** A Planning Assessment Addendum shall be attached for each pump station located
between the project connection point and the WWTP where the Available Capacity is < 0.
Downstream Facility Name (Sewer): _ Cape Fear Public Utility Authority
Downstream Permit Number:
Page 1 of 6
FTSE 10-18
III. Certification Statement:
I Jeff Theberge, CFPUA Eng. Mgr certify to the best of my knowledge that the addition of
the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving
wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity
related sanitary sewer overflows or overburden any downstream pump station en route to the receiving
treatment plant under normal circumstances, given the implementation of the planned improvements
identified in the planning assessment where applicable. This analysis has been performed in accordance
with local established policies and procedures using the best available data. This certification applies to
those items listed above in Sections I and II plus all attached planning assessment addendums for which I
am the responsible party. Signature of this form certifies that the receiving collection system or treatment
works has adequate capacity to transport and treat the proposed new wastewater.
Official Signature Date
Engineering Manager
Title of Signing Official
Page 2 of 6
FTSE 10-18
8/7/2020
Go:)gle Maps 34018'01.2"N 7705616.6"W
RPplow
D,p,00ntl0. n
� Grmnwwam
r; M�c1YG
'Af h
x If
m
P
n
Cmtl�M1 flU
'fife C[ .--'
4�
34'18'01.2"N 77°56'16.6"W - Google Maps
S�ns,u Apartments
Google
0
Sw¢4n�l Ntl
�y.
0
Qa
,, -1 Q,
c
l0e 1, Rd a Je41e'
Klntl:ddvllie�
Map data @2020 500 ft
https://w .google.com/maps/place/34*18'01.2"N.77°56'16.6"W/@34.3011079,-77.9403931,16.24z/data=!4m5!3m4!1sOxO:OxO!8m2!3d34.300332!4d-77.937938?hl=en 1/2
O
T 1Q )5
.. �MAI FO/ION IT -
. XERMIrPLE RD rt
CFNIfNN/9l OR BE LLWJOO AV[
17
17
\.
0
pNLU5 OR -
0
e' x 0
F
o
J LLADIDIVS FO
zs
Dnvrs Lx'
Walnut 6
Hills
zS e RDCRx.LL RDtf
\ _
w
SWPPiSVILLE RD
y ¢
p x DID Mlll RD
.ten SS RD
F S _
t =fit
PUMP-
ST�\ f� AITTER DF.
ATION NCODR-- ARLENE DR_
BOUNTIFUL DR' PFLLOVATOfv
IESADR o
(D EY 0.D SANG LN t
VILLAGE SITE wNIrMAx�evE Wrightsboro Acres R/pVXA,B
RARRELLs —
LN LONL-EAF DR
ORVI(LEWRILXT MAV
o µUPEL DR
\a� WIxDRBEL DR _.
+
DP0. �" l - NORNE VLdCE JR __-
B
�I,,.,01 - Wnghtsboro a AVE
R
�zi
�p
- Seitter as.
Acres a zs "o
E) t S` _ ._ .10 �9MA BAR/IALf PAFN LR R V %4
Dq p
1)
s
eis = Sedgefield
w
4R[/NLION IPRIPL l"
\ -- l5-._. OR yAf RO
Bn
-YORKTOWN DR y
t �e Council Heights �; ^a N
w LerE
Wilminal o
International Nrpon
CASTLE HAYNE,2013