HomeMy WebLinkAboutNC0005126_Compliance Evaluation Inspection_20200820 (2)United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NC0005126 I11 121 20/08/07 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80
L—I ty L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:05AM 20/08/07
14/06/01
Tyson Farms, Inc.
501 Sheffield Rd
Exit Time/Date
Permit Expiration Date
Harmony NC 28634
12:25PM 20/08/07
19/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Kevin Todd Haynes/ORC/704-546-2602/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Steven Smith,PO Box 158 Harmony NC 28634/Plant Manager/704-546-2602/
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell Docusigned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 8/20/2020
2r6&
A61696D90CC3437...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0005126 I11 12I 20/08/07 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NC0005126 Owner - Facility: Tyson Farms, Inc.
Inspection Date: 08/07/2020 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
❑
❑
0
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The Division received the permit renewal package on 8/19/18.
The facilitv descriDtion noted in the Dermit will need to be uDdated to include all wastewater
treatment upgrades.
The last compliance evaluation inspection at this facility was performed bV DWR staff on
6/29/18.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Page# 3
Permit: NC0005126 Owner - Facility: Tyson Farms, Inc.
Inspection Date: 08/07/2020 Inspection Type: Compliance Evaluation
Record Keeping Yes
No
NA
NE
Comment: The records reviewed during the inspection were organized and well maintained.
Discharge
Monitoring Reports (eDMRs) were reviewed for the period July 2019 through June 2020. Nc
effluent limit violations were reported all monitoring frequencies were correct.
The ORC and staff must ensure that the ambient temperature inside the composite
sampler
is documented to verify proper preservation (less than or equal to six degrees Celsius)
during the 24-hr. sampling period.
Laboratory Yes
No
NA NE
Are field parameters performed by certified personnel or laboratory? 0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab? M
❑
❑
❑
# Is the facility using a contract lab? 0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑
❑
0
❑
Comment: On -site field analvses (dissolved oxvaen. DH, temDerature. total residual chlorine) are
performed under Tyson Farm's field laboratory certification #5081. PAR Labs (all effluent
parameters except field and toxicity), Meritech (toxicity) and ETT Environmental (toxicity)
have also been contracted to provide analytical support.
A five -point verification with primary standards (ultra -low range) must be performed initially
on the new total residual chlorine meter (DR 3900) and every twelve months while this
meter is being used for effluent analyses (Reference: North Carolina
Wastewater/Groundwater Lab Certification approved procedure for analysis of total residual
chlorine — DPD Colorimetric by SM 4500 Cl G-2011).
Effluent Sampling
Yes
No
NA NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
0
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑
representative)?
Comment: The subject permit requires composite and grab effluent samples. The sampler tubing
needed to be cleaned/replaced; however, the facility was not sampling during the inspection
In addition, the aliquot volume was slightly below 100 mis. during the inspection and previou
aliquot volume checks by on -site staff (multiple occasions). The ORC corrected the
sampler program to ensure a minimum of 100 mis per aliquot will be collected during future
samDlina events and later notified DWR staff that the tubina was chanaed.
Page#
Permit: NC0005126 Owner - Facility: Tyson Farms, Inc.
Inspection Date: 08/07/2020 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes
No
NA
NE
Is the plant generally clean with acceptable housekeeping? 0
❑
❑
❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
❑
❑
❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facilitv was beina DrODerIv oDerated and well maintained. The ORC and staff
incorporate a comprehensive process control program with all measurements being
properly documented and maintained on -site.
The facility is equipped with a SCADA system to assist the wastewater staff in the
operations of treatment processes/units. Although not required, the wastewater treatment
facility is staff with certified operators twenty-four (24) hours per day, seven (7) days per
week.
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Comment: The facilitv continues to eaualize waste streams with the 4.5 MG I
tanks (.845 MG and .034 MG).
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
IY47111111111►[•7►/_9►1:4
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
and two circular
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Comment: The DAF unit treats all process wastewater and waste activated sludge from .845 MG EQ
tank. DAF effluent is conveyed to the first anoxic treatment tank. The DAF solids are stored
in a tank prior to being transported and land applied to permitted sites located in either
Wilkes County or South Carolina by Terra Renewal Services.
Chemical Feed
Yes No NA NE
Page# 5
Permit: NC0005126
Inspection Date: 08/07/2020
Owner - Facility: Tyson Farms, Inc.
Inspection Type: Compliance Evaluation
Chemical Feed
Yes
No
NA
NE
Is containment adequate?
0
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Are backup pumps available?
0
❑
❑
❑
Is the site free of excessive leaking?
0
❑
❑
❑
Comment:
Nutrient Removal
Yes
No
NA
NE
# Is total nitrogen removal required?
0
❑
❑
❑
# Is total phosphorous removal required?
EIN
❑
❑
Type
Biological
# Is chemical feed required to sustain process?
❑
❑
0
❑
Is nutrient removal process operating properly?
0
❑
❑
❑
Comment: The facility is equipped with three anoxic reactors and three aerobic reactors. Glycerin is
available as a carbon supplement (not being added at time of inspection).
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Yes No NA NE
Ext. Air
Diffused
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: Aqueous lime is added to maintained appropriate alkalinity/pH levels.
The foam coveraae in both aeration tanks was areater than twentv-five Dercent: however. nc
foam carry-over was observed in the clarifier. The foam was later attributed to a surfactant.
The small amount of foam on the ground adjacent to one of the aeration tanks was in the
process of being cleaned up.
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Page# 6
Permit: NC0005126 Owner - Facility: Tyson Farms, Inc.
Inspection Date: 08/07/2020 Inspection Type: Compliance Evaluation
Secondary Clarifier
Yes
No
NA
NE
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
0
❑
❑
❑
Comment: A coagulant and flocculant are added to enhance settling.
Pumps-RAS-WAS
Yes
No
NA
NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Comment:
Disinfection -Liquid
Yes
No
NA NE
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
(Sodium Hypochlorite) Is pump feed system operational?
0
❑
❑
❑
Is bulk storage tank containment area adequate? (free of leaks/open drains)
0
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination
Yes
No
NA
NE
Type of system ?
Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
0
❑
❑
❑
Is storage appropriate for cylinders?
❑
❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑
❑
0
❑
Are the tablets the proper size and type?
❑
❑
0
❑
Comment: Sodium bisulfite is used for dechlorination.
Are tablet de -chlorinators operational?
❑
❑
0
❑
Page# 7
Permit: NC0005126
Inspection Date: 08/07/2020
De -chlorination
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
Owner - Facility: Tyson Farms, Inc.
Inspection Type: Compliance Evaluation
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: The flow meter is calibrated annuallv and was last calibrated on 6/5/2020 by Carotek.
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
❑
❑
0
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The effluent appeared clear with no floatable solids or foam.
Page# 8