HomeMy WebLinkAboutNC0071447_Compliance Evaluation Inspection_20200730 (2)United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 u 3 I NCO071447 I11 121 20/07/23 I17 18I � I 19 I s I 201 I 211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 67 2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80 L—I ty L-1 I I Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09:20AM 20/07/23 15/10/01 Catholic Conference Center WWTP 1551 Trinity Ln NCSR 1120 Exit Time/Date Permit Expiration Date Hickory NC 28602 10:10AM 20/07/23 20/07/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Dennis W Murdock/ORC/828-238-4659/ Robert Charles White//336-549-8990 / Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Scott Gilfillan,1551 Trinity Ln Hickory NC 28602//828-327-7441/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenar Records/Reports Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Wes Bell DocuSigned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 7/29/2020 A61696D90CC3437... Signature of Ma gerrlYn`isdnA`ft-viewer Agency/Office/Phone and Fax Numbers Date H P 7. 30.2020 Andrew Pitn r'9 R/MRO WQ/704-663-1699 Ext.2180/ F161FB69A2D84A3... EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NC0071447 I11 12I 20/07/23 117 18 i c i Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On -Site Representatives: The following personnel were in attendance during the inspection: Chip White/Envirolink, Dennis Murdock/Envirolink and Ashley Dowdy/Catholic Conference Center. Page# Permit: NCO071447 Owner -Facility: Catholic Conference Center WWTP Inspection Date: 07/23/2020 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new 0 ❑ ❑ ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The Division received the permit renewal package on 2/5/2020. Tablet dechlorination will need to be added to the facility description in the reissued permit. The last compliance evaluation inspection at the facility was performed by DWR staff on 4/12/17. Record Keeping Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Is the backup operator certified at one grade less or greater than the facility classification' Is a copy of the current NPDES permit available on site? Facility has copy of previous year's Annual Report on file for review? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ ■ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ■ ❑ Page# 3 Permit: NCO071447 Inspection Date: 07/23/2020 Record Keeping Owner -Facility: Catholic Conference Center WWTP Inspection Type: Compliance Evaluation Yes No NA NE Comment: The records reviewed durina the insDection were oraanized and well maintained. Discharae Monitoring Reports (eDMRs) were reviewed for the period June 2019 through May 2020. Effluent BOD violations (daily maximum and monthly average) were reported in January 2020. The Division has previously addressed these violations through the issuance of a Notice of Violation (NOV). Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: On -site field analvses (dissolved oxvaen. DH. temDerature. total residual chlorine) are performed under Envirolink's field laboratory certification #5212. Statesville Analytical (Certification #440) has also been contracted to provide analytical support. The ORC must ensure to perform post -analysis calibration checks on the pH meter and total residual chlorine meter (if no mid -range checks are performed at each site) if these field analyses are performed at multiple sites throughout a day. Post -analysis calibration checks must be performed in accordance with the NC Wastewater/Groundwater laboratory certification aDDroved Drocedures for the analvses of DH and total residual chlorine. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: The subject permit requires effluent grab samples Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Page# 4 Permit: NCO071447 Owner -Facility: Catholic Conference Center WWTP Inspection Date: 07/23/2020 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Comment: The wastewater treatment facility appeared to be properly operated and well maintained. Process control measurements were being performed and documented. Bar Screens Yes No NA NE Type of bar screen a.Manual b.Mechanical ❑ Are the bars adequately screening debris? 0 ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screening in compliance? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: The facility is equipped with a coarse bar screen. Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? 0 ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ 0 ❑ Comment: Lime is added on an as -needed basis. The 30-minute settleabilitv test measured 330 ml/L with a clear supernate during the inspection. The facility only has one operational blower/motor unit. The second blower/motor unit is in the process of being repaired/replaced. In addition, the check valve for second blower unit will also have to be repaired/replaced. Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? 0 ❑ ❑ ❑ Is the site free of weir blockage? 0 ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Page# 5 Permit: NC0071447 Inspection Date: 07/23/2020 Owner -Facility: Catholic Conference Center WWTP Inspection Type: Compliance Evaluation Secondary Clarifier Yes No NA NE Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? 0 ❑ ❑ ❑ Is the return rate acceptable (low turbulence)? M ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) 0 ❑ ❑ ❑ Comment: Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? 0 ❑ ❑ ❑ Number of tubes in use? 1 Is the level of chlorine residual acceptable? M ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? 0 ❑ ❑ ❑ Comment: Calcium Hypochlorite is used for disinfection. De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? ❑ ❑ 0 ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ 0 ❑ Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 2 Comment: Sodium Sulfite is used for dechlorination. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ 0 ❑ Is flow meter calibrated annually? ❑ ❑ 0 ❑ Is the flow meter operational? ❑ ❑ 0 ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Page# 6 Permit: NCO071447 Inspection Date: 07/23/2020 Flow Measurement - Effluent Owner -Facility: Catholic Conference Center WWTP Inspection Type: Compliance Evaluation Yes No NA NE Comment: Instantaneous flows are measured by the bucket and stop watch method. The ORC and staff must ensure to measure flow durina the collection of effluent samDles (BOD, TSS, ammonia, etc.). Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: The effluent appeared clear with no floatable solids or foam. The receiving stream did not appear to be negatively impacted. Aerobic Digester Is the capacity adequate? Is the mixing adequate? Is the site free of excessive foaming in the tank? # Is the odor acceptable? # Is tankage available for properly waste sludge? Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment: Lake Norman Sewer and Septic Services has been contracted to remove sludge on an as -needed basis. Page# 7