HomeMy WebLinkAboutNC0025135_Compliance Evaluation Inspection_20200810DocuSign Envelope ID: FODCOF6E-F7B8-4OB3-ACC5-7362FF388CBE
.
ROY COOPER
MICHAEL S. REGAN
Secr&a
Secretary
'��"`•'�'
S. DANIEL SMITH
NORTH CAROLINA
Alrecror
Environmental Quality
August 10, 2020
Lee T Huffman
Huffman Finishing Company Inc
PO Box 170
Granite Falls, NC 28630-0170
SUBJECT: Compliance Inspection Report
Huffman Finishing
NPDES WW Permit No. NCO025135
Caldwell County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Huffman Finishing on
8/06/2020. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0025135. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
Please respond in writing to this office within 30 days of your receipt of this letter regarding your plans
or measures to be taken to address the following issues:
• The rake in the secondary clarifier is functioning but appears to have reached the end of its
functional life and is nearing structural failure, this component should be evaluated for repair or
replacement immediately.
If you should have any questions, please do not hesitate to contact me with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
ATTACHMENTS
Ec: LF
Sincerely,
IrDocuSigned by:
PAbf� t�60i
082B1105A3CA418...
Tim Heim, P.E., Environmental Engineer
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
NortrDEro rsDepartmentofEnvironmental Quslrty I Division of Water Resources
Ashswe Ragnna.Off:ce 1 2090 V.S. 70Hthw3y I Sw nanoa, North Caro:ina 23773
223296-4500
DocuSign Envelope ID: FODCOF6E-F7B8-4OB3-ACC5-7362FF388CBE
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO025135 I11 121 20/08/06 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:30AM 20/08/06
16/05/01
Huffman Finishing
4919 Hickory Blvd
Exit Time/Date
Permit Expiration Date
Granite Falls NC 28630
11:30AM 20/08/06
20/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Jonathan David Gragg/ORC/828-396-4444/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Lee T Huffman,PO Box 170 Granite Falls NC
286300170/Manager/Owner/828-396-1741 / No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar 0 Facility Site Review
Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim DWR/ARO WQ/828-296-4665/
8/10/2020
DocuSigned by:
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
FDocuSi9ned by: 8/ 10 / 2 0 2 0
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: FODCOF6E-F7B8-40B3-ACC5-7362FF388CBE
NPDES yr/mo/day Inspection Type (Cont.)
NC0025135 I11 12I 20/08/06 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a Compliance Evaluation Inspection on August 6,
2020. Jonathan Gragg (ORC) was present at the time of the inspection. Mr. Gragg took over as ORC
approximately 2 months ago and reported that while the facility was well run, he is continuing small
process adjustments to optimize the facility for both treatment and energy efficiency.
The inspection included a file review of the Permit status, bench sheets and DMRs, as well as a facility
inspection. The NPDES Outfall was not able to be access due to a downed tree blocking the road.
Sample record keeping was thorough and well organized. The site was well maintained and appeared
to be operating within compliance to permit NCO025135 and no violations of permit conditions were
observed at the time of the inspection. The ORC demonstrated detailed knowledge of the facility, its
history and its operation.
The facility currently operates at approximately 40,000 gal/day, 4 days a week. Influent combines
industrial and domestic wastewater from the mill.
The following items were noted at the time of the inspection:
The rake in the secondary clarifier is functioning but appears to have reached the end of its functional
life and is nearing structural failure, this component should be evaluated for repair or replacement
immediately.
Secure the chlorine gas cylinders to prevent accidental tip over.
Maintain the road to the Outfall to allow access.
Page#
DocuSign Envelope ID: FODCOF6E-F7B8-4OB3-ACC5-7362FF388CBE
Permit: NCO025135 Owner -Facility: Huffman Finishing
Inspection Date: 08/06/2020 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Process controls include pH and MLSS. Influent quality is very consistent and the facility
does not experience I&I.
Permit
Yes
No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment:
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
0
❑
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Oxidation Ditches
Yes
No
NA
NE
Are the aerators operational?
0
❑
❑
❑
Are the aerators free of excessive solids build up?
0
❑
❑
❑
# Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Are settleometer results acceptable (> 30 minutes)?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Page# 3
DocuSign Envelope ID: FODCOF6E-F7B8-4OB3-ACC5-7362FF388CBE
Permit: NCO025135 Owner -Facility: Huffman Finishing
Inspection Date: 08/06/2020 Inspection Type: Compliance Evaluation
Oxidation Ditches
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
Yes No NA NE
❑ ❑ ❑ ■
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Wastewater in the clarifier at this facility is typically black from the dye process. ORC report
the sludge depth is maintained at approximately 2-3' out of a total depth of 15'.
The rake arm appears to be at the end of its useful life and should be evaluated for
replacement immediately.
Disinfection -Gas
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Yes No NA NE
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Comment: Spare gas cylinders need to be secured to prevent them from accidentally falling over.
Page# 4
DocuSign Envelope ID: FODCOF6E-F7B8-40B3-ACC5-7362FF388CBE
Permit: NC0025135 Owner -Facility: Huffman Finishing
Inspection Date: 08/06/2020 Inspection Type: Compliance Evaluation
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Yes
No
NA
NE
■
❑
❑
❑
❑
❑
■
❑
■
❑
❑
❑
❑
❑
❑
■
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: The mill maintains the backup generator. Long term power loss would also result in
termination of influent from the mill.
Page# 5