HomeMy WebLinkAboutNC0033430_Draft Permit_20200811 ROY COOPER 4.. ---1
Governor g
MICHAEL S.REGAN
Secretary
S.DANIEL SMITH NORTH CAROLINA
Director Environmental Quality
Mr.Walter Synalovski
Camp Judaea
1440 Spring St NW
Atlanta,GA 30309
Subject: Draft NPDES Permit NC0033430
Camp Judaea WWTP
Grade II Biological WPCS
Henderson County
Dear Mr. Synalovski:
The Division has reviewed your request to renew the subject permit. Please review this draft carefully to ensure a
thorough understanding of the information,conditions,and requirements it contains.
The draft permit includes the following significant changes from the existing permit:
➢ Section A.(2)has been updated regarding electronic submission of effluent data.Federal regulations
require electronic submittal of all discharge monitoring reports(DMRs).
> Regulatory citations have been added to the permit.
The NPDES standard conditions(Parts II, III,and IV)that are a part of the permit are not included in this draft
document(cover,map,and Part I).The conditions are the same as in your current permit except that agency and
division names have been updated. The latest version is available at https://bit.ly/2BZ4xxx and can be viewed
online or downloaded as a PDF file.
With this notification,the Division will solicit public comment on this draft permit by publishing a notice in
newspapers having circulation in the general Henderson County area, per EPA requirements. Please provide
your comments,if any,to me no later than 30 days after receiving this draft permit.
Following the 0- apublic commentperiod,the Division will review all pertinent comments and take
30-day y
appropriate action to issuinga finalpermit. Ifyou havequestions concerningthe draft, please contact me at
prior
919-707-3616,or via e-mail at charles.weaver@ncdenr.gov.
Sincerely,
/1/040- /-1. limlui )7.
Charles H.Weaver,Jr.
NPDES Compliance and Expedited Permitting
cc: NPDES File(Laserfiche)
North Carolina Department of Environmental Quality I Division of Water Resources
,) 512 North Salisbury Street i 1611 Mail Service Center i Raleigh,North Carolina 27699-1611
��+ �� /6/ 919.707.9000
Permit NC0033430
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENTAL QUALITY
DIVISION OF WATER RESOURCES
PERMIT
TO DISCHARGE WASTEWATER UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
(NPDES)
In compliance with the provisions of North Carolina General Statute 143-215.1, other lawful standards
and regulations promulgated and adopted by the North Carolina Environmental Management
Commission, and the Federal Water Pollution Control Act,as amended,
Camp Judaea, Inc.
is hereby authorized to discharge wastewater from a facility located at the
Camp Judaea WWTP
49 Camp Judaea Lane
Hendersonville
Henderson County
to receiving waters designated as Henderson Creek in the French Broad River Basin in accordance
with effluent limitations,monitoring requirements, and other conditions set forth in Parts I, II, III and
IV hereof.
This permit shall become effective
This permit and authorization to discharge shall expire at midnight on
November 30, 2025.
If the permittee intends to continue to discharge at the facility beyond the term of this permit, a
renewal application must be submitted no later than June 3, 2025 (180 days before the expiration of
this permit).
Signed this day
ip?"9.
ak
S. Daniel Smith, Director
Division of Water Resources
By Authority of the Environmental Management Commission
Page 1 of 6
Permit NC0033430
SUPPLEMENT TO PERMIT COVER SHEET
All previous NPDES Permits issued to this facility, whether for operation or discharge are hereby
revoked, and as of this issuance, any previously issued permit bearing this number is no longer
effective. Therefore, the exclusive authority to operate and discharge from this facility arises under the
permit conditions,requirements,terms,and provisions included herein.
Camp Judaea, Inc. is hereby authorized to:
1. Continue to operate an existing 0.03 MGD extended aeration wastewater treatment system that
includes the following components:
• 7,500 gallon flow equalization basin w/manual bar screen
• Dual pumps (one grinder pump)w/dual alarms
• Flow splitter box
• Dual aeration basins (13,000 and 17,000 gallon w/dual blowers providing diffused air)
• 2,700 gallon and 3,900 gallon clarifiers w/skimmers and sludge returns
• 2,600 gallon aerobic digester
• Tablet chlorinator
• 1,200 gallon chlorine contact chamber
• 30°v-notch weir and staff gauge
• Tablet dechlorinator
• 160 linear feet of 6-inch gravity outfall
This facility is located south of Fruitland at the Camp Judaea WWTP, (49 Camp Judea Lane,
Hendersonville), Henderson County.
2. Discharge from said treatment works via Outfall 001, at the location specified on the attached map,
into Henderson Creek [stream index 6-55-11-9], currently classified C-Trout waters located within
sub-basin 04-03-02 [HUC: 06010105] of the French Broad River Basin.
Page 2 of 6
Permit NC0033430
PART 1
Grade II Biological Water Pollution Control System [15A NCAC 08G.0302]
A. (1) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
[15A NCAC 02B .0400 et seq., 02B .0500 et seq.]
During the period beginning on the effective date of the permit and lasting until expiration, the
Permittee is authorized to discharge from Outfall 001. Such discharges shall be limited,monitored
and reported' by the Permittee as specified below:
PARAMETER LIMITS MONITORING REQUIREMENTS
Monthly Daily Measurement Sample Sample
Parameter Code Average Maximum Frequency Type Location
Flow Influent or
50050 0.03 MGD Weekly Instantaneous Effluent
Total Residual Chlorine 2 28 µg/L 2/Week Grab Effluent
50060
BOD, 5-day(20°C)
C0310 30.0 mg/L 45.0 mg/L Weekly Grab Effluent
Total Suspended Solids
30.0 mg/L 45.0 mg/L Weekly Grab Effluent
C0530
NH3 as N(April 1 —October 31)
C0610 19.0 mg/L 35.0 mg/L Weekly Grab Effluent
NH3 as N(Nov.1 —March 31)
C0610 Weekly Grab Effluent
Fecal Coliform(geometric mean) 200/100 ml 400/100 ml Weekly Grab Effluent
31616
Temperature(°C)
Weekly Grab Effluent
00010
pH Not<6.0 or>9.0
00400 standard units Weekly Grab Effluent
Footnote:
1. The Permittee shall submit discharge monitoring data electronically using the Division's
eDMR system [See A.(2)].
2. The Division shall consider all effluent TRC values reported below 50 µg/L to be compliant
with the permit. However,the Permittee shall continue to record and submit all values reported
by a North Carolina-certified test methods(including field-certified),even if these values fall
below 50 µg/L.
Condition:
The Permittee shall discharge no floating solids or visible foam in other than trace amounts.
Page 3 of 6
Permit NC0033430
A. (2) ELECTRONIC REPORTING - DISCHARGE MONITORING REPORTS
[G.S. 143-215.1(b)]
Federal regulations require electronic submittal of all discharge monitoring reports (DMRs)and
program reports. The final NPDES Electronic Reporting Rule was adopted and became effective on
December 21,2015.
NOTE: This special condition supplements or supersedes the following sections within Part II of this
permit(Standard Conditions for NPDES Permits):
• Section B.(11.) Signatory Requirements
• Section D.(2.) Reporting
• Section D.(6.) Records Retention
• Section E.(5.) Monitoring Reports
1. Reporting Requirements [Supersedes Section D. (2.) and Section E. (5.) (a)1
The permittee shall report discharge monitoring data electronically using the NC DWR's
Electronic Discharge Monitoring Report(eDMR) internet application.
Monitoring results obtained during the previous month(s) shall be summarized for each month and
submitted electronically using eDMR. The eDMR system allows permitted facilities to enter
monitoring data and submit DMRs electronically using the internet. Until such time that the state's
eDMR application is compliant with EPA's Cross-Media Electronic Reporting Regulation
(CROMERR), permittees will be required to submit all discharge monitoring data to the state
electronically using eDMR and will be required to complete the eDMR submission by printing,
signing, and submitting one signed original and a copy of the computer printed eDMR to the
following address:
NC DENR/Division of Water Resources/Water Quality Permitting Section
ATTENTION: Central Files
1617 Mail Service Center
Raleigh,North Carolina 27699-1617
If a permittee is unable to use the eDMR system due to a demonstrated hardship or due to the
facility being physically located in an area where less than 10 percent of the households have
broadband access,then a temporary waiver from the NPDES electronic reporting requirements
may be granted and discharge monitoring data may be submitted on paper DMR forms (MR 1, 1.1,
2, 3)or alternative forms approved by the Director. Duplicate signed copies shall be submitted to
the mailing address above. See"How to Request a Waiver from Electronic Reporting"section
below.
Regardless of the submission method,the first DMR is due on the last day of the month following
the issuance of the permit or in the case of a new facility, on the last day of the month following the
commencement of discharge.
Starting on December 21,2020,the permittee must electronically report the following compliance
monitoring data and reports, when applicable:
• Sewer Overflow/Bypass Event Reports;
• Pretreatment Program Annual Reports; and
• Clean Water Act(CWA) Section 316(b)Annual Reports.
Page 4 of 6
Permit NC0033430
The permittee may seek an electronic reporting waiver from the Division(see"How to Request a
Waiver from Electronic Reporting"section below).
2. Electronic Submissions
In accordance with 40 CFR 122.41(1)(9),the permittee must identify the initial recipient at the time
of each electronic submission. The permittee should use the EPA's website resources to identify
the initial recipient for the electronic submission.
Initial recipient of electronic NPDES information from NPDES-regulated facilities means the
entity (EPA or the state authorized by EPA to implement the NPDES program)that is the
designated entity for receiving electronic NPDES data [see 40 CFR 127.2(b)].
EPA plans to establish a website that will also link to the appropriate electronic reporting tool for
each type of electronic submission and for each state. Instructions on how to access and use the
appropriate electronic reporting tool will be available as well. Information on EPA's NPDES
Electronic Reporting Rule is found at: http://www2.epa.gov/compliance/final-national-pollutant-
discharge-elimination-system-npdes-electronic-reporting-rule.
Electronic submissions must start by the dates listed in the"Reporting Requirements" section
above.
3. How to Request a Waiver from Electronic Reporting
The permittee may seek a temporary electronic reporting waiver from the Division. To obtain an
electronic reporting waiver, a permittee must first submit an electronic reporting waiver request to
the Division. Requests for temporary electronic reporting waivers must be submitted in writing to
the Division for written approval at least sixty (60) days prior to the date the facility would be
required under this permit to begin submitting monitoring data and reports. The duration of a
temporary waiver shall not exceed 5 years and shall thereupon expire. At such time, monitoring
data and reports shall be submitted electronically to the Division unless the permittee re-applies for
and is granted a new temporary electronic reporting waiver by the Division. Approved electronic
reporting waivers are not transferrable. Only permittees with an approved reporting waiver request
may submit monitoring data and reports on paper to the Division for the period that the approved
reporting waiver request is effective.
Information on eDMR and the application for a temporary electronic reporting waiver are found on
the following web page:
http://deq.nc.gov/about/divisions/water-resources/edmr
4. Signatory Requirements (Supplements Section B.(11.)(b)and Supersedes Section B. (11.)
•
All eDMRs submitted to the permit issuing authority shall be signed by a person described in Part
II, Section B. (11.)(a)or by a duly authorized representative of that person as described in Part II,
Section B. (11.)(b). A person, and not a position,must be delegated signatory authority for eDMR
reporting purposes.
Page 5 of 6
Permit NC0033430
For eDMR submissions,the person signing and submitting the DMR must obtain an eDMR user
account and login credentials to access the eDMR system. For more information on North
Carolina's eDMR system,registering for eDMR and obtaining an eDMR user account,please visit
the following web page:
http://deq.nc.gov/about/divisions/water-resources/edmr
Certification. Any person submitting an electronic DMR using the state's eDMR system shall
make the following certification [40 CFR 122.22]. NO OTHER STATEMENTS OF
CERTIFICATION WILL BE ACCEPTED:
"I certify, under penalty of law, that this document and all attachments were prepared under my
direction or supervision in accordance with a system designed to assure that qualified personnel
properly gather and evaluate the information submitted. Based on my inquiry of the person or
persons who manage the system, or those persons directly responsible for gathering the
information, the information submitted is, to the best of my knowledge and belief true, accurate,
and complete. I am aware that there are significant penalties for submitting false information,
including the possibility of fines and imprisonment for knowing violations."
5. Records Retention 'Supplements Section D. (6.)1
The permittee shall retain records of all Discharge Monitoring Reports, including eDMR
submissions. These records or copies shall be maintained for a period of at least 3 years from the
date of the report. This period may be extended by request of the Director at any time [40 CFR
122.41].
Page 6 of 6
v
Viiii;,„,,, :___,,/-...-1,--
0,, , x ii
• Vil . •,.. ..,,,\ ,,
• -.\------0,, ---------- oh
zi ...„..„.„:„
, /lb,I\c.s.`:11;#: 1 J b_Ny\-__,\____ui
O at/ * C.- ,0 (i) \
`,4r41\ \miler / \t,. ---- • i''
s .f/ i‘i ,wiii,-- . k 1
y•' , „it , • . "A)k .. co:\ : 4 1
,,._.., --. ..4/y
---7. r ---\._ -A.......,„,- ( ", " 7/ . 7.7'----;-s\''' ) Ifi n) )
zit - --„,. . \\ 0 1111 :1"
t - !I I wite,•&.:,.....1,'h.,, ,, I ‘I I I I I I I
0 ,,_ t 1' 1 ,_fif24
t II - � - - ' S. Mills Gap Rd.
Fruitland Rd. 1 *bA
i '! L
•\ +�.�? Fr 2 . : 'i c� g r 1 Q i
r . '
.'4170 j -,/" ._ts \ 2c,00• a 7 ev,
.-( / co N rc), „,
N_ >,0- „iiii ,,___._
r,:!AD / (c,...--\--,:„_-,3 , ..
t ir,po 7/ v ====0--- ,
1
. i -at --- -- —---------,.. ,...) \ -.
n ,,/v gd�
i V 1
0, i/Lf
■k\ �. __ Henderson Creek
" (flows NW) •
rill . ) \, If.
c2
�. T
0r. :, !
{ { \\ 21 '
•O 0 UFf ix 9 ' lie7/ZIPS146......
s �. Chimney
",,,-.t-"'`�� w�• I64` Y+ ` • Rock Rd. illi
�-` V�i \ � ,� Hwy 64)
Outfall 001 ,
i► Flows NE , •.•
• „ \�iiiMilitlirk 0 .r• �: . ' L. r
: 411A _ "-"--.-46101Iie i! ktir,4ittii, `1" " ‘ 1
larlieris 1_041111k. " LIPMAPIlikAtit111.; I-. \ :
Camp Judea WWTP
Facility
*
Location
Latitude: 35°22'38" USGS Quad: Fruitland not to scale liiiiii
Longitude: 82°22' 59" HUC: 06010105
Stream Class: C-Trout Sub-Basin: 040302
Stream Segment: 6-55-11{9) NPDES Permit NC0033430
Receiving Stream: Henderson Creek North orth
Henderson County