HomeMy WebLinkAboutNC0081256_Regional Office Historical File Pre 2016Water Resources ENVIRONMENTAL QUALITY December 18, 2015 Mr. Wendell Pickett Water Treatment Superintendent City of High Point P.O. Box 230 High Point, NC 27261 SUBJECT: Compliance Evaluation Inspection Frank L. Ward Water Filtration Plant — City of High Point NPDES Permit No. NCO081256 Guilford County Dear Mr. Pickett: PAT MCCRORY Governor DONALD R. VAN DER VAART Secretory S. JAY ZIMMERMAN . Director On December 17, 2015, Mike Mickey of this office met with. you to perform a Compliance Evaluation Inspection on the NPDES wastewater discharge from the Ward Water Filtration Plant (WFP). The treatment facility was found to be compliant with the NPDES permit., The inspection findings are detailed below and an inspection checklist is attached. I. Permit The NPDES was finally reissued March 1, 2015 and expires next on August 31, 2016. A renewal notice should be mailed to you in the near future. H. Self -Monitoring Program The monthly discharge monitoring reports (DMR's) were reviewed for the period January 2015 through October 2015. The facility was found to be compliant with the final NPDES effluent limits for the above period (See data summary attached). In regards to the permit monitoring requirements, it was noted that all sampling was performed per the frequencies specified in the permit. III. Flow Measurement The NPDES permit contains two outfalls. Outfall #002 (north lagoon) is the primary discharge point. Flow at this outfall is measured using a Siemens ultrasonic meter and parshall flume. This. meter was last calibrated on October 16, 2015 by City of High Point staff. Outfall #001 (south lagoon) only discharges if solids are being removed from the north lagoon. Flow at this outfall is estimated by measuring water height in the flume. IV. Sludge Handling and Disposal Solids from the settling ponds are periodically removed every three or more years by dewatering with portable centrifuges. The last removal event occurred in June and July 2015. The dewatered sludge is disposed of at the City of High Point landfill. ti State of North Carolina I Environmental Quality I Water Resources 450 West Hanes Mill Road, Sulte 300, Winston-Salem, NC 27105 Phone: 336-776-9800 \ Internet: www.ncdenr.gov CJ Mr. Wendell Pickett Page 2 December 18, 2015 V. Operations and Maintenance The facility was competently operated and maintained. No problems or concerns were noted. VI. Facility Site Review The wastewater treatment components consist of the following: two 10 MG settling basins (operated in series), tablet dechlorinator unit and effluent flow measurement. The system discharges daily through outfall #002. VII. Records/Reports A review of thefacility files found the operators records to be complete and maintained according to the permit. A comparison of the October 2015 self -monitoring report with the corresponding operator records showed that all field measurements were transcribed onto the DMR correctly. VIH. Effluent/Receiving Waters The system discharges into an unnamed tributary to Richland Creek, class "WS-IV *" waters in the Cape Fear River Basin. The effluent was clear on the day of the inspection. Our office appreciates your efforts to comply with the NPDES permit. Should you have any questions concerning this report, please contact Mike Mickey or me at (336) 776-9800. Sincerely, Sherri V. Knight, PE Regional Supervisor Water Quality Regional Operations Section Division of Water Resources cc: Central Files Z, ` M Permit: NCO081256 Owner - Facility: Frank L. Ward WTP Inspection Date: 12/17/2015 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑ application? Is the facility as described in the permit? A ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ 0 ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0, ❑ ❑ ❑ Comment: The permit was reissued March 1, 2015 and expires next on August 31, 2016. For the review period January 2015 through October 2015 the Ward WTP was found to be compliant with all effluent limits and monitoring requirements. A review of the October 2015 DMR found that all values were transcribed correctly from the operator's records for pH and total residual chlorine. The High Point Laboratory performs the analysis for the remainder of the parameters. Toxicity testina beaan in April 2015 with re -issuance of the Dermit. The last six chronic toxicity tests of the effluent have passed. The permit requires quarterly testing with no limit. Operations $ Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: , The wastewater is aenerated from "sludae blowdown" from the uDflow clarifier alona with filter backwash from the filters. There are two 10 MIS settling basins that are operated in series. Outfall #002 (north lagoon) is the primary discharge point and has a tablet dechlorinator unit and ultrasonic flow meter. For outfall #001 (south lagoon), a discharge would only occur when accumulated solids are removed from the north lagoon using_ portable centrifuges. Removal typically occurs once every 3 or more years. The last solids removal from both lagoons occurred in June and July of 2015. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ N ❑ Page# 3 Permit: NCO081256 Inspection Date: 12/17/2015 Flow Measurement - Effluent owner - Facility: Frank L. Ward WTP Inspection Type: Compliance Evaluation Yes No NA NE Comment: The new permit now requires continuous flow recording. A siemens ultrasonic meter with parshall flume is used to measure flow at outfall # 002. This meter was calibrated by High Point staff on October 16 2015. Since outfall #001 is used infrequently, the flow is not metered but will be estimated if necessary by measuring the water height at the parshall flume. The average daily discharge volume from the Ward WTP for 1/15 -10/15 was 0.86 MGD. De -chlorination Yes No NA NE Type of system ? Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ Is storage appropriate for cylinders? ❑ ❑ M ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ M ❑ Comment: Are the tablets the proper size and type? M ❑ ❑ ❑ Are tablet de -chlorinators operational? M ❑ ❑ ❑ Number of tubes in use? 6 Comment: Outfall #002 has six dechlor tubes. Outfall #001. which was valved off, has a single dechlor tube available in the manhole Oust before the outfall. Effluent Pipe Yes No NA NE Is right of way to the butfall properly maintained? M ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ M ❑ Comment: Treated effluent is discharged into a tributary of Richland Creek, class "WS-IV*" waters in the Cape Fear River Basin. The effluent was observed to be clear. Page# 4 V City of High Point — Frank L. Ward WFP NPDES Permit No. NCO081256 Self -Monitoring Data Summary. January 2015 — October 2015 Parameters Monthly Avg. Permit Limit Monthly Avg. Limit Violations per DMR Daily Maximum Permit Limit Daily Max. Limit Violations per DMR Flow (MGD) - NA - NA TSS (mg/L) 30.0 None 45.0 None pH (S.U.) - NA (6.0-9.0) range None Res. Chlorine (ug/L) - NA 17.0* None Turbidity (NTU) - NA - NA Aluminum (ug/L) - NA - NA T. Iron (ug/L) - NA - NA T. Copper (ug/L) - NA - NA Manganese (ug/L) - NA - NA Flouride (mg/L) - NA - NA NH3-N (mg/L) - NA - NA T. Phosphorus (mg/L) - NA - NA T. Nitrogen (mg/L) - NA - NA Chronic Toxicity (P/F) monitoring only** NA - NA *TRC values reported below 50 ug/L are considered compliant. ** Chronic Toxicity monitoring is a pass/fail test @ 90% with no limit. Mickey, Mike From: Mickey, Mike Sent: Thursday, December 17, 2015 5:04 PM To: 'wendell.pickett@highpointnc.gov' Subject: FW: High Point Ward WTP - NC0081256 Wendell — See the email chain below regarding permit renewal process for possible coverage under the new WTP General Permit. In summary, you submit the usual Short Form C-WTP application and then request coverage under NCG590000 in your cover letter. Below is some information from our web site along with a web link. Hope this helps. Holler back if any questions. Thanks, Mike. * To be considered for coverage under NCG590000 general permit, please include the following information with your p application: ® No fee required for greensand and conventional VIT'Ps seeking individual permit renewal and requesting to be cansidered for tht ® A cover letter vex/application stating you have revieawved the conditions set forth in the NCG590000 general permit ai considered for coverage. Please also state you understand that upon issuance of a general permit, the individual N your facility will be rescinded. If this is a Conventional. %7P,Whole Effluent Toxicity tests shall be performed annualCy and complly vdath a "Pass" permit Qi NCG590 00 requires al0hTFs to comply vdth a turbidity effluent limitation http://Porta1.ncdenr.org/web/wq/swp/­ps/npdes/generaIpermits Mike.Mickey@NCDENR.gov NC DEQ Winston-Salem Regional Office Division of Water Resources — Water Quality Programs 450 W. Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 Phone: (336) 776-9697 From: Weaver, Charles Sent: Thursday, December 17, 2015 4:46 PM To: Mickey, Mike <mike.mickey@ncdenr.gov> Subject: Re: High Point Ward WTP - NC0081256 They should submit the Short Form C-WTP and ask for coverage under NCG590000 in their cover letter. Thanks for letting me know. Charles H. Weaver Environmental Specialist N.C. Division of Water Resources N.C. Department of Environmental Quality 919-807-6391 charles.weave Ka-ncd en r.g ov From: Mickey, Mike Sent: Thursday, December 17, 2015 2:48 PM To: Weaver, Charles Subject: High Point Ward WTP - NC0081256 Charles— Inspected the Ward WTP today. Their individual NPDES permit expires next on August 31, 2016, so they should be getting a renewal notice shortly. They are interested in seeking coverage under NCG59000. Do they still submit the Short Form C - WTP application but also include a cover letter requesting coverage under the General Permit? Thanks, Mike. Mike.Mickey@NCDENR.gov NC DEQ Winston-Salem Regional Office Division of Water Resources —Water Quality Programs 450 W. Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 Phone: (336) 776-9697 E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. Mickey, Mike From: Meadows, Susan Sent: Friday, December 11, 2015 11:35 AM To: Mickey, Mike Subject: RE: High Point Ward WTP - NC0081256 I know I have an entry in our Database for 7/15/15. 1 have NO explanation as to why it was not included on the list. Right now I am dealing with lots of lost data due to some "glitch" downtown having lost several files, some of those being 100's of tests I entered over the last few weeks. I know it is in our database and they did at least a test for July 2015, I'm not sure about October because I think the data entry was lost. I am in the process of re-entering all that was lost! Ugh! I will try to address the problem of that facility not being included on the printout. But, they are testing and reporting it to me. Susie Susan Meadows Environmental Biologist Aquatic Toxicology Branch DWR/Water Sciences Section Department of Environmental Quality tel: (919) 743-8439 fax: (919) 743-8517 susan.meadows@ncdenr.gov 4401 Reedy Creek Road Raleigh, NC 27607 ,.-�=---- othing Compares.---, ,.- Email correspondence to and from this address is subject to the North Carolina Public Records Law and may be disclosed to third parties. From: Mickey, Mike Sent: Friday, December 11, 2015 11:21 AM To: Meadows, Susan <susan.meadows@ncdenr.gov> Subject: High Point Ward WTP - NC0081256 Susan — I did not see the Ward WTP on the printout. Their permit requires them to submit the AT-1 form. Are you getting it or am I missing something? Thanks, Mike. Mike.Mickey@NCDENR.gov NC DEQ Winston-Salem Regional Office Division of Water Resources — Water Quality Programs 450 W. Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 Phone: (336) 776-9697 E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. From: Meadows, Susan Sent: Friday, December 11, 2015 10:19 AM To: Mickey, Mike <mike.mickey@ncdenr.Rov> Subject: RE: Tox request Sure, here you are. Would you like me to send them to you each month? Susie Susan Meadows Environmental Biologist Aquatic Toxicology Branch DWR/Water Sciences Section Department of Environmental Quality tel: (919) 743-8439 fax: (919) 743-8517 susan.meadows@ncdenr.gov 4401 Reedy Creek Road Raleigh, NC 27607 .. "=''1' tithing Compares._-, .- Email correspondence to and from this address is subject to the North Carolina Public Records Law and may be disclosed to third parties. From: Mickey, Mike Sent: Friday, December 11, 2015 9:55 AM To: Meadows, Susan <susan.meadows@ncdenr.gov> Subject: Tox request Hi Susan — Can you send me the latest "WET SelfMonitoring Printout WSRO". I don't get them anymore since Jen is gone. Thanks, Mike. Mike.Mickey@NCDENR.gov NC DEQ Winston-Salem Regional Office Division of Water Resources —Water Quality Programs 450 W. Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 2 Mickey, Mike From: Sledge, Bob Sent: Tuesday, January 20, 2015 1:32 PM To: wendell.pickett@highpointnc.gov Cc: Mickey, Mike Subject: Renewed NPDES Permit - NCO081256 Attachments: NCO081256 Final Permit 2015.pdf Hi Mr. Pickett, Thank you for all the help and kindness .you provided as we worked toward getting the NPDES permit for the water plant renewed. I've attached a copy of the signed permit. A hard copy will follow via the postal service after final processing of the renewal up here. Please call or reply if you have any questions. e �P �® NCDENR North Carolina Department of Environment and Natural Resources Pat McCrory Governor January 15, 2015 Mr. Wendell Pickett Water Treatment Superintendent City of High Point P.O.'Box 230 High Point, NC 27261 SUBJECT: Compliance Evaluation Inspection Frank L. Ward Water Filtration Plant — City of High Point NPDES Permit No. NCO081256 Guilford County Dear Mr. Pickett: Donald van der Vaart On January 13, 2015, Mike Mickey of this office and Bob Sledge from the Central Office met with you to perform a Compliance Evaluation Inspection on the NPDES wastewater discharge from the Ward Water Filtration Plant (WFP). The treatment facility was found to be compliant with all effluent limits and monitoring requirements of the NPDES.permit. The inspection findings are detailed below and an inspection checklist is attached for your records. I. Permit The NPDES permit expired on August 31, 2011. It is expected that the individual permit will be reissued in the near future. Please continue operating under the expired permit until reissuance. H. Self -Monitoring Proeram The monthly self -monitoring reports (DMR's) were reviewed for the period January 2014 through October 2014. The facility was found to be compliant with the final NPDES effluent limits for the above period (See data summary attached). In regards to the permit monitoring requirements, it was noted that all sampling was performed per the frequencies specified in the permit. III. Flow Measurement The NPDES permit contains two outfalls. Outfall #002 (north lagoon) is the primary discharge point and flow is measured- using a Siemens ultrasonic meter and parshall flume. Outfall #001 (south lagoon) only discharges if solids are being removed from the north lagoon. Flow at this outfall is estimated by measuring water height in the flume. At present, the NPDES permit specifies instantaneous flow monitoring at both outfalls. As discussed during the inspection, the next permit will specify continuous flow recording. This will require that flow values from oufall 4002 be recorded daily on the DMR. IV. Sludge Handlinge and Disposal Solids from the settling ponds are periodically removed every three or more years by dewatering with portable centrifuges. The dewatered sludge is disposed of at the City of High Point landfill. 450 West Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 Phone: 336-776-9800 \ Internet: www.ncwaterclualitV.org An Equal Opportunity\ Affirmative Action Employer —Made in part by recycled paper Mr. Wendell Pickett Page 2 January 15, 2015 V. Operations and Maintenance The facility was competently operated and maintained. No problems or concerns were noted. VI. Facility Site Review The wastewater treatment components consist of the following: two 10 MG settling basins (operated in series), tablet dechlorinator unit and effluent flow measurement. The system discharges daily through outfall #002. VII. Records/Reports A review of the facility files found the operators records to be thorough and maintained according to the permit. A comparison of the October 2014 self -monitoring report with the corresponding operator records showed that all field measurements (turbidity, pH and flow) were transcribed onto the DMR correctly. VIH. Effluent/Receivin2 Waters The system discharges into an unnamed tributary to Richland Creek, class "WS-IV *" waters in the Cape Fear River Basin. The effluent was clear on the day of the inspection. Our office appreciates your efforts to comply with the NPDES permit. Should you have any questions concerning this report, please contact Mike Mickey or me at (336) 771-5000. Sincerely, // - Sherri V. Knight, PE Assistant Regional Supervisor Water Quality Regional Operations Section Division of Water Resources cc: Central Files W115-R IM City of High Point — Frank L. Ward WFP NPDES Permit No. NCO081256 Self -Monitoring Data Summary January 2014 — October 2014 Parameters Monthly Avg, Permit Limit Monthly Avg. Limit Violations per DMR Daily Maximum Permit Limit Daily Max. Limit Violations per DMR Flow (MGD) - NA - NA TSS (mg/L) 130.0 None 45.0 None Set. Solids (ml/L) 0.1 None 0.2 None Turbidity (NTU) - NA - NA R. Chlorine (ug/L) - NA 17.0* None Aluminum (ug/L) - NA - NA T. Nitrogen (mg/L) - NA - NA T. Phosphorus(mg/L) - NA - NA *TRC values reported below 50 ug/L are considered compliant. 3 Permit: NCO081256 Owner - Facility: Frank L. Ward WTP Inspection Date: 01/13/2015 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new 0 ❑ ❑ ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ M ❑ ❑ Is access to the plant site restricted to the general public? ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: A review of the monthly self-monitorinq reports for the period January 2014 through October 2014 showed the Ward WFP to be compliant with all effluent limits and monitoring_ requirements of the NPDES permit. The NPDES permit expired on 8/31/11. The City of High Point submitted a renewal request to DWR on February 28, 2011. It is expected that the individual permit will be reissued in the near future. Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ■ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Wastewater from the WTP process is generated from "sludge blowdown" from the upflow clarifier along with filter backwash from the filters. There are two 10 MG settling basins that are operated in series. Outfall #002 (north lagoon) is the primary discharge point and has a tablet dechlorinator unit and ultrasonic flow meter. A discharge from outfall #001 (south lagoon) only occurs when accumulated solids in the north lagoon are been removed using portable centrifuges (typically once every 3 or more years). De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ' ❑ Is storage appropriate for cylinders? ❑ ❑ ® ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ ■ ❑ Comment: Are the tablets the proper size and type? M ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 6 Comment: There are six dechlorination tubes at outfall # 002. Outfall #001 (currently valved off) has a single dechlorination tube in a manhole iust before the outfall. If outfall #001 is activated, the facility also dechlorinates the influent to the south lagoon. 'Page# 3 i 1 / Permit: NC0081256 Owner - Facility: Frank L. Ward WTP Inspection Date: 01/13/2015 Inspection Type: Compliance Evaluation Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0❑ ❑ ❑ Is flow meter calibrated annually? N •❑ ❑ ❑ Is the flow meter operational? 0❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: The permit currently requires weekly -instantaneous flow measurement. The reissued Permit will require continuous flow recording. A siemens ultrasonic meter with parshall flume is used to measure flow at outfall #002 (north lagoons For outfall #001 (south lagoon),,_ flow is estimated by measuring the water height at the parshall flume Please note that the reissued permit will require documentation of an annual calibration of the flow device The average daily discharge volume from the Ward WFP for 1/14-10/14 was approximately 1.25 MGD Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ E ❑ Comment: The treated effluent is discharged into a tributary of Richland Creek class "WS-IV*" waters in the Cape Fear River Basin. The discharge from outfall #002 was clear on the day of the inspection. Page# 4 Mickey, Mike From: Mickey, Mike Sent: Friday, January 09, 2015 9:16 AM To: Iwendell.pickett@highpointnc.gov' Subject: Ward WTP Attachments: NCG590000 WTP General Permit.pdf, Technical Bulletin.pdf Wendell —Bob I and will see you 10:30-ish next Tuesday. I just need to seethe October DMR and walk to lagoons/dechlor/flow meter. I will let Bob explain the renewal/NCG59 process. I have attached the new NCG590000 general permit and the technical bulletin for your information. They can also be obtained at the link below in the paragraph about the general permit. http://Portal.ncdenr.org/web/wq/­swb/`­`ps/`npdes Unfortunately, Item A.2(f) of the WTP general permit states the following: Whole Effluent Toxicity (WET) test results for the past three years shall be reviewed for existing or expanding Conventional WTPs applying for coverage under this general permit. Thanks, Mike. Mike.Mickev@NCDENR.gov NC DENR Winston-Salem Regional Office Division of Water Resources — Water Quality Programs 450 W. Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 (336) 776-9697 Please note new address and telephone number. E-mail correspondence to and from this address maybe subject to the North Carolina Public Records Law and may be disclosed to third parties. Mickey, Mike From: Mickey, Mike Sent: Wednesday, January 07, 2015 2:27. PM To: Carter, Jenifer Subject: FW: NCG590000 - WTP FYI — Conversion at renewal. It is in the permit under Part 1.A(3). From: Hennessy, John Sent: Wednesday, January 07, 2015 2:17 PM To: Weaver, Charles; Grzyb, Julie Cc: Mickey, Mike Subject: RE: NCG590000 Due to the existing staffing levels and current permitting volume, it was our intention to process these on their original renewal schedule. I hope this answers everyone's questions. Please let me know if you have any questions, or require any additional information. Thanks. From: Weaver, Charles Sent: Wednesday, January 07, 2015 2:01 PM To: Hennessy, John; Grzyb, Julie Cc: Mickey, Mike Subject: FW: NCG590000 know that we won't require a fee to modify existing NC00 permits to NCG59. However, are we allowing changeovers before a permit is due for renewal? Let me know, and I'll forward the answer to Mike. From: Mickey, Mike Sent: Tuesday, January 06, 2015 4:26 PM To: Weaver, Charles Subject: NCG590000 Charles —I assume existing WTP's that meet the criteria will be moved to the new general permit at renewal. If a facility wants to transfer in mid -permit cycle, can they go ahead and submit Short Form C — WTP without a fee? Will it be processed? Thanks, Mike. M i ke. M i ckey @ N CD E N R.gov NC DENR Winston-Salem Regional Office Division of Water Resources —Water Quality Programs. 450 W. Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 (336) 776-9697 Please note new address and telephone number. E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. NCO081266 , Monitoring Violation Frank L. Ward WTP v \ vv--�av -j NCO081256 Frank L. Ward WTP Monitoring Violation Frequency €Aluminum, `0! Violation 2014i 5001 ..- --- - ..----------'— -------- Total (as Al) --- - - t— Frequency I 3 Violation p w 2014 5 001 _ t Chlorine, Total Residual j0! _.�. { 'µ :Frequency E anion 2014k001 �Frequ Flow, in conduit or thru treatment plant0! r�c .,.2 Volalicn 014[ 5 001 ;Solids, Settleable0! NCO081671 Lake Townsend WTP Limit Violation Daily Minimum i Not Reached 20 I --- tWe_e_kly ��- �� _ ?Microgram sper Liter Microgram-- 1-2014 Weekly is per Liter (Million Gallons per 1-2014 'Weekly ;Day 1 ]Milliliters , f-2014 Weekly per Liler _, -3.333333 Mickey, Mike From: Sent: To: Subject: BIMS has been corrected. CHW Weaver, Charles Thursday, January 16, 2014 9:17 AM Mickey, Mike RE: NCO081256 - High Point Ward WTP From: Mickey, Mike Sent: Wednesday, January 15, 2014 1:20 PM To: Weaver, Charles Subject: NCO081256 - High Point Ward WTP Charles - The "Details 2" tab shows a permitted flow of 10 MGD. There is no flow limit in their permit (which is what the outfall tab correctly shows). Can the 10,000,000 be deleted from the Details tab? This is where Environmental Sciences looks up flow limits. Thanks, Mike. Related Permits MI Publish r outfall r "'el[s r Sites r Comments r History r inspections r Incidents r Enforceni Details I r7Deta€€s 2 Billing r Class.JDesig. r Events r Reg. Activities r Structures r Affiliat Permit: C(i481256 Version. .fD Status: Expired Application Signed By: kobert W_ P€ckett SignersTitle: Water Treatment Plant Superintendent I; Application Processor: Frances Candelaria Mike Mickey Mike.Mickev@NCDENR.eov NC Division of Water Resources 585 Waughtown Street Winston-Salem, NC 27107 Phone: (336) 771-4962 FAX: (336) 771-4630 E-mail correspondence to and from this address may be subject to the North Permit Reporting Suspension Periods As -Built Flow. l t?Q©D 1 d Mickey, Mike From: Weaver, Charles Sent: Tuesday, December 10, 2013 10:31 AM To: Mickey, Mike Subject: RE: City of High Point - Ward WTP - NCO081256 Like me, Bob is buried under a mountain of work. Some things just aren't getting done. He was ordered to develop a General Permit for discharges from reuse systems. That ate a lot of time. He was also the ROC for 3 regions until this week. He has been busy, as we all have. All four of us [Maureen, Joe, Bob, me] have backlogged renewals due to the overall volume of work and the reduced staff in our Unit. We started out with seven people in 2004. That has been cut to five, and Derek [occupying the 5th seat] isn't doing renewals yet. I'm sure that if High Point had expressed great concern, Bob would have prioritized their renewal. I wish I had a better answer for you, but that's how things are. CHW Messages sent to or from this address are subject to the North Carolina Public Records Law. From: Mickey, Mike Sent: Tuesday, December 10, 2013 8:51 AM To: Weaver, Charles Subject: FW: City of High Point - Ward WTP - NCO081256 Charles - Is this all on Bob (see below) or is there a reason I should cut him some slack? Mike. From: Mickey, Mike Sent: Tuesday, December 10, 2013 8:26 AM To: Basinger, Corey Subject: FW: City of High Point - Ward WTP - NCO081256 FYI - The Ward WTP renewal has been in Raleigh for 34 months. This week will be my second inspection where they will ask about a the status. Customer Service? I think not. Mike. From: Sledge, Bob Sent: Tuesday, December 10, 2013 5:56 AM To: Mickey, Mike Subject: RE: City of High Point - Ward WTP - NCO081256 Hi Mike, This one's still all on me. I apologize for any problems it's creating. I need to get in touch with Mr. Pickett and work this one through. I'll give you a call later this morning. :•. ti Mickey, Mike From: Mickey, Mike Sent: Tuesday, December 10, 2013 8:36 AM To: 'wendell.pickett@highpointnc.gov' Subject: FW: City of High Point - Ward WTP - NCO081256 Wendell —Just an FYI on the NPDES permit renewal status, or lack thereof. Just 34 months and counting. See you Thursday @ 9 am. Mike. Mike Mickey Mike.Mickev@NCDENR.eov NC Division of Water Resources 585 Waughtown Street Winston-Salem, NC 27107 Phone: (336) 771-4962 FAX: (336) 771-4630 From: Sledge, Bob Sent: Tuesday, December 10, 2013 5:56 AM To: Mickey, Mike Subject: RE: City of High Point - Ward WTP - NCO081256 Hi Mike, This one's-stil all on me. I apologize for any problems it's creating. I need to get in touch with Mr. Pickett and work this one through. I'll give you a call later this morning. we From: Mickey, Mike Sent: Monday, December 09, 2013 4:05 PM To: Sledge, Bob Subject: RE: City of High Point - Ward WTP - NCO081256 Bob — I'm inspecting the Ward WTP this week. Thought I would check again on the status on their renewal request. Thanks, Mike. Facility: Frank l.._ Ward INTP Owner: Cityof.High Point — Dates — Issued: 0810912006 Effective: 0910/12006 Expire: 0813'112011 Drig issued: 03102/1992 Statutory: 0/10612006 Inactive: 1 is From: Sledge, Bob Sent: Friday, To: Weaver, Charles; Mickey, Mike Subject: RE: City of High Point - Ward WTP - NCO081256 Hi Mike, That's one that's become hung up. We've got a few facilities pushing back on the requirements in the WTP policy and I'm trying to be reasonable and consistent with about a half dozen of them. I'll try to get it moving next week. Bob S From: Weaver, Charles Sent: Friday, January 27, 2012 1:59 PM To: Mickey, Mike Cc: Sledge, Bob Subject: RE: City of High Point - Ward WTP - NCO081256 Bob Sledge has that one. The application arrived here on No idea why it doesn't show up in BIMS. CHW From: Mickey, Mike Sent: Friday, January 27, 2012 1:41 PM To: Weaver, Charles Subject: City of High Point - Ward WTP - NCO081256 Charles — Can you remind me who is assigned the renewal for the above WTP. BIMS does not show a log in date for the renewal application. Thanks, Mike. Mike Mickey Mike.MickeV@NCDENR.gov NC Division of Water Quality 585 Waughtown Street Winston-Salem, NC 27107 Phone: (336) 771-4962 FAX: (336) 771-4630 INCDENR North Carolina Department of Environment and Natural Resources Beverly Eaves Perdue Governor Mr. Wendell Pickett Water Treatment Plant Superintendent City of High Point P.O. Box 230 High Point, NC 27261 Division of Water Quality Charles Wakild, PE Director February 3, 2012 SUBJECT: Compliance Evaluation Inspection Frank L. Ward Water Filtration Plant — City of High Point NPDES Permit No. NCO081256 Guilford County Dear Mr. Pickett: Dee Freeman Secretary On February 2, 2012, Mike Mickey of this office met with you to perform a Compliance Evaluation Inspection on the NPDES wastewater discharge from the Frank L. Ward Water Filtration Plant (WFP). This type of inspection consists of two basic parts: an in office file review and an on -site inspection of the treatment facility. The inspection found the Ward WFP to be in complete compliance with the NPDES permit. The attached EPA inspection form notes the eight (8) areas that were, evaluated for this inspection. The findings and observations are outlined below: I. Permit The City of High Point submitted a permit renewal request that was received in our Central Office on February 28, 2011. The NPDES permit expired on August 31, 2011. Please continue to operate under the expired permit until the permit is reissued. II. Self -Monitoring Program The monthly self -monitoring reports (DMR's) were reviewed for the period January 2011 through December 2011. The facility was found to be in complete compliance with final NPDES effluent limits for the above period (See data summary attached). In regards to the permit monitoring requirements, it was noted that all sampling was performed per the frequencies specified in the permit. Ill. Flow Measurement The WFP facility has two separate outfalls, each with a parshall flume. The NPDES permit currently requires instantaneous flow monitoring, however, the permit prohibits a simultaneous discharge from both -outfalls. The effluent flow from outfall #001/south lagoon is simply estimated using the parshall flume. Effluent flow from the outfall #002/north lagoon is measured using an ultrasonic meter at this parshall flume. North Carolina Division of Water Quality, Winston-Salem Regional Office Location: 585 Waughtown St. Winston-Salem, North Carolina 27107 Phone: 336-771-5000 \ FAX: 336-7714630 \ Customer Service:1-877-623-6748 Internet: www.ncwaterquality.org NorthCarolina ,,vatmally An Equal Opportunity \ Affirmative Action Employer Mr. Wendell Pickett Page 2 February 3, 2012 IV. Sludge Handling and Disposal Solids from the settling ponds are periodically removed every two to three years by dewatering with portable centrifuges. The dewatered sludge is then disposed of at the City of High Point landfill. V. Operations and Maintenance The facility appeared to be competently operated and maintained. No problems or concerns were noted. VI. Facility Site Review The existing NPDES wastewater treatment components consist of the following: two 10 MG settling basins (operated in series or separately), tablet dechlorination and effluent flow measurement. VII. Records/Reports A review of the facility files indicates that all records are being maintained according to the permit. A comparison of the November and December 2011 self -monitoring reports with the corresponding laboratory data sheets showed that all values were transcribed onto the DMR's correctly. Vill. Effluent/Receiving Waters The system discharges into an unnamed tributary to Richland Creek, class "WS-IV *" waters in the Cape Fear River Basin. The effluent was crystal clear on the day of the inspection. Should you have any questions concerning this report, please contact Mike Mickey or me at (336) 771-5000. Sincerely, W. Corey Basinger Regional Water Quality Supervisor Surface Water Protection Section cc: Central Files City of High Point — Frank L. Ward WFP NPDES Permit No. NCO081256 Self -Monitoring Data Summary January 2011 — December 2011 Parameters Monthly Avg. Permit Limit Monthly Avg. Limit Violations per DMR Daily Maximum Permit Limit Daily Max. Limit Violations per DMR Flow (MGD) - NA - NA TSS (mg/L) 30.0 None 45.0 None Set. Solids (ml/L) 0.1 None 0.2 None Turbidity (NTU) - NA - NA R. Chlorine (ug/L) - NA 17.0 None Aluminum (ug/L) - NA - NA T. Nitrogen (mg/L) - NA - NA T. Phosphorus(mg/L) - NA - NA United States Environmental Protection Agency Form Approved. EPA Washington, D.C.20460 OMB No.2040-0057 Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 I N I 2 15 I 11 NCO081256 111 121 12/02/02 117 181 C I 19101 20I Remarks 211 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I _[_]6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA --------------- —---------- Reserved --------------------- 67I 169 701 I 711 I 721 N I 73 LJJ 74 751 I I I I I I 180 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) Frank L. Ward WTP 09:00 AM 12/02/02 06/09/01 Exit Time/Date Permit Expiration Date 2011 E Kivett Dr High Point NC 27260 09:50 AM 12/02/02 11/08/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Robert Wendell Pickett/ORC/336-883-3410/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Chris Thompson,PO Box 230 High Point NC 27261//336-883-3215/3368833149 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit E Flow Measurement ® Operations & Maintenance ® Records/Reports Self -Monitoring Program E Sludge Handling Disposal Facility Site Review ■ Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Michael M Mickey WSRO WQ//336-771-50001 Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date VV21' ..2�✓t��K "fldf5) A0 f2- EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page # 1 Permit: NCO081256 Inspection Date: 02/02/2012 o..—oa Owner - Facility: Frank L. Ward WTP Inspection Type: Compliance Evaluation (If the present permit expires in 6 months or less). Has the permittee submitted a new application? ■ n ❑ n Is the facility as described in the permit? ■ n n n # Are there any special conditions for the permit? n ■ n n Is access to the plant site restricted to the general public? ■ n n n Is the inspector granted access to all areas for inspection? ■ n n n Comment: The City of High Point submitted a permit renewal application that was received in our Central Office on February 28, 2011. The previously active NPDES permit expired on August 31, 2011. The City of High Point is authorized to continue to operate under the expired permit until such time as the new permit is issued. Record Keeping Yes No NA Nt Are records kept and maintained as required by the permit? ■ n n n Is all required information readily available, complete and current? ■ n n n Are all records maintained for 3 years (lab. reg. required 5 years)? ■ n n n Are analytical results consistent with data reported on DMRs? ■ 110 Q Is the chain -of -custody complete? ■ n n n Dates, times and location of sampling ■ Name of individual performing the sampling ■ Results of analysis and calibration ■ Dates of analysis ■ Name of person performing analyses ■ Transported COCs ■ Are DMRs complete: do they include all permit parameters? ■ n n n Has the facility submitted its annual compliance report to users and DWQ? n ❑ ■ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? n n ■ n Is the ORC visitation log available and current? ■ n In n Is the ORC certified at grade equal to or higher than the facility classification? ■ n ❑ n Is the backup operator certified at one grade less or greater than the facility classification? ■ n n n Is a copy of the current NPDES permit available on site? ■ n n n Facility has copy of previous year's Annual Report on file for review? n ri ■ n Page # 3 10 Permit: NCO081256 Inspection Date: 02/02/2012 Record Keeping Owner - Facility: Frank L. Ward WTP Inspection Type: Compliance Evaluation Comment: All records are being maintained per the NPDES permit. A comparision of the November and December 2011 self -monitoring reports with the corresponding laboratory data showed that all values were transcribed onto the DMR's correctly. The facility also has the required field certification to perform testing of settleable solids and total residual chlorine for reporting on the DMR's. Operations & Maintenance Is the plant generally clean with acceptable housekeeping? Yes No NA NE Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge n n 0 n Judge, and other that are applicable? Comment: Wastewater from the WTP process is generated from "sludge blowdown" from the upflow clarifier and filter backwash from the filters. The NPDES wastewater treatment components consist of the following: two 10 MG settling basins (can be operated in series or separately), tablet dechlorination and two parshall flumes (one for each outfall). Solids are removed from the lagoons approximately every two to three years by a contractor that brings in portable centrifuges to dewater the accumulated solids. Disposal occurs at the High Point landfill. De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ■ n Is storage appropriate for cylinders? n n ■ n # Is de -chlorination substance stored away from chlorine containers? n n ■ n Are the tablets the proper size and type? ■ n n n Comment: Tablet dechorination tubes have been installed prior to each parshall flume. Are tablet de -chlorinators operational? ■ n n n Number of tubes in use? Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ■ n n n Is flow meter calibrated annually? n n n Is the flow meter operational? ■ n n n (If units are separated) Does the chart recorder match the flow meter? n n ■ Page # 4 Permit: NCO081256 Inspection Date: 02/02/2012 Flow Measurement - Effluent Owner - Facility: Frank L. Ward WTP Inspection Type: Compliance Evaluation Comment: The NPDES permit currently requires instantaneous flow measurement. Effluent flow from the north lagoon (outfall #002) is measured by an ultrasonic meter prior to the parshall flume. Effluent flow from the south lagoon (outfall #001) is estimated by measuring the water heigh at that parshall flume. Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: The treated effluent from the outfalls is discharged into an unnamed tributary of Richland Creek, Class WS-IV * waters of the Cape Fear River Basin. The effluent from outfall #002 was crystal clear on the day of the inspection. It should be noted that the permit prohibits the simultaneous discharge from both outfalls at the same time. Yes No NA NE ■nnn ■nnn nn■n Page # 5 Water Pollution Control System Operator Designation Form WPCSOCC NCAC 15A 8G .0201 Permittee Owner/Officer Name: �Ity of. RIO Po►ni_ Mailing Address: P.O. Box 2.30 City: R q P01 n t State: N Cr Zip: A? 2 � ` Phone #: (3.96) �Fe34.01 Email address: �& rry h o w k a h i •� �. p o l► n �- inc• R 01% Signature:71Z Date: i � � g ..........................................................................•;..........'.............................A.�...................t.. Facility Name: Frahk• L • %A itKOL �1liG��l`er f �- i A. 0 Pla Permit #: ! Y C. 00 9 12 SUBMIT A SEPARATE FORM FOR EACH TYPE SYSTEM! Facility Tvue/Grade: Biological W WTP Surface Irrigation . Physical/Chemical^ Land Application Collection System Operator in Responsible Charge (ORC) L Print Full Name: K O 6 e &-t W 'e nQe d., t P + e. Q.t 1� / Number: 4' -A 3 77 Work Phone #: k9.36 Date: i111 �•� �^ "1 certify thk-I'ag?ee4e Ly designation d�s the perator in Responsible Charge for the facility noted. I understand and will abide by the rules and regulations pertaining to the responsib' ies of the ORC as set forth in 15A NCAC 08G .0204 and failing to do so can result in Disciplinary Actions by the Water Pollution Control System Operators Certification Commission." ............................................................................................................................................. Back -Up Operator in Responsible +y Charge (BU ORC)*'"f Print Full Name: Ned- Henry O ri l e y 1" r. Certificate Type / Grade / Number: ?C' q rl q Work Phone #: (�3G) O O •3 Signature: 6Date: 1I i a—cl "1 certify that I agree to my designation as a Back-up Operator in Responsible Charge for the facility noted. I understand and will abide by the rules and regulations pertaining to the responsibilities of the.BU ORC as set forth in 15A NCAC 08G .0205 and failing to do so can result in Disciplinary Actions by the Water Pollution Control System Operators Certification Commission." .............................................................................................................................................. Mail or fax the original to: WPCSOCC, 1618 Mail Service Center, Raleigh, NC 27699-1618 Fax: 919.807.6492 Mail orfax a copy to the Asheville appropriate Regional Office: 2090 US Hwy 70 Swannanoa 28778 Fax: 828.299.7043 Phone: 828.296.4500 Washington 943 Washington Sq Mall Washington 27889 Fax: '252'946.9215 Phone: 252.946.6481 Fayetteville 225 Green St Suite 714 Fayetteville 28301-5043 Fax: 910,486.0707 Phone: 910.433.3300 Wilmington 127 Cardinal Dr Wilmington 28405-2845 Fax: 910.350.2018 Phone: 910.796.7215 Mooresville 610 B Center Ave Suite 301 Mooresville 28115 Fax: 704.663.6040 Phone: 704.663.1699 Winston-Salem 585 Waughtown St Winston-Salem 27107 Fax: 336.771.4631 Phone: 336.771.5000 Raleigh . 3800 Barrett Dr Raleigh 276,09 Fax: 919.571.4718 Phone:919.791,4200 Revised 10-2012 ben Primary I. cede psT I �0 RAG Tank � Tank Source 002-Combined Hes effluent in use) (AmmonlaforCl i DrambesXnatcunerdly Rwftbr r (se=ndary blea i for ChloankmXnotwrterMytouse) fbsh Mbt QAlum addfUon) Compliance sample Form G ik Holes Lake (Polymer) —� �_ (Caustic j- flnlshed water code 001 Pump Station 'k Process it (Fucride) Un cede 014 Upfrow Ciarlfrcafror, 4 - pumps Nan Comptterrce samples Secondary source Coeg_ Code 102 T soMW water cads 103 Chemical BuikTanhs �— Atrara inKw vMw Coda 00Q 1- 6,000 gal. Fluoride Tank 3-10,000 gal. Causlic Tank 1- 6,000 gal. Corrosion Inhibitor Tank -*-SeMd Wbgw 1- 2f1,000 gal. Alum Tank( underground) BbuDww —� !Ift 0 0 0� -10,000 gals_ Bulk Meec g3,, g ` s 400 tt I 6nwgertcylTempaay d�rarga �- �rrt pumps �� DSrant i I I �--= NORTH )I` I lf, �tB 6'PadaE . F&W CRY ar"kh Point GMEMICAL AC)pirlorj Weed Water Filtrafln Phmt IW5 ID 03-01-020 NC Oc�812,5Io F LOW VOLOIAES Mickey, Mike From: Sledge, Bob Sent: Friday, January 27, 2012 2:03 PM To: Weaver, Charles; Mickey, Mike Subject: RE: City of High Point - Ward WTP - NCOO81256 Hi Mike, That's one that's become hung up mostly because I hate doing these WTP permits. We've got a few facilities pushing back on the requirements in the WTP policy and I'm trying to be reasonable and consistent with about a half dozen of them. I'll try to get it moving next week. From: Weaver, Charles Sent: Friday, January 27, 2012 1:59 PM To: Mickey, Mike Cc: Sledge, Bob Subject: RE: City of High Point - Ward WTP - NC0O81256 Bob Sledge has that one. The application arrived here on 2/24/2011. No idea why it doesn't show up in BIMS. CHW From: Mickey, Mike Sent: Friday, January 27, 2012 1:41 PM To: Weaver, Charles Subject: City of High Point - Ward WTP - NCOO81256 Charles — Can you remind me who is assigned the renewal for the above WTP. High Point called wanting an update. BIMS does not show a log in date for the renewal application. Thanks, Mike. Mike Mickey Mike. Mickev@NCDENR.eov NC Division of Water Quality 585 Waughtown Street Winston-Salem, NC 27107 Phone: (336) 771-4962 FAX: (336) 771-4630 E-mail correspondence to and from this address maybe subject to the North Carolina Public Records Law and may be disclosed to third parties. W ` North Carolina Department of Environment and Natural Division of Water Quality Beverly Eaves Perdue Coleen H. Sullins Governor Director March 1, 2011 ROBERT W PICKETT WATER PLANT SUPERINTENDENT CHP WATER FILTRATION PLANT PO BOX 230 HIGH POINT NC 27261 RECEIVED N.C. Dept. of ENR mAR 0 7 2011 Resources Winston-Salem Regional Office Dee Freeman Secretary Subject: Receipt of permit renewal application NPDES Permit NCO081256 Frank L. Ward WTP Guilford County Dear Mr. Pickett: The NPDES Unit received your permit renewal application on February 28, 2011. A member of the NPDES Unit willreview your application. They will contact you if additional information is required to complete your permit renewal. You should expect to receive a draft permit approximately 30-45 days before your existing Permit expires. If you have any additional questions concerning renewal of the subject permit, please contact Bob Sledge at (919) 807-6398. Sincerely, st�� 'z �Pa� Dina Sprinkle Point Source Branch cc: CENTRAL FILES W�inst`."�le`mRegional Office/Surface Water Protection 17PDES Unit 1617 Mail Service Center, Raleigh, North Carolina 27699-1617 Location: 512 N. Salisbury St. Raleigh, North Carolina 27604 One Phone: 919-807-63001 FAX: 919-807-64921 Customer Service: 1-877-623-6748 NorthCarolina Internet: www.ncwaterquality.org �q An Equal Opportunity \ Affirmative Action Employer -,Robert Wendell Pickett Water Filtration Plant 2011 EAST KIVETT DRIVE HIGH POINT, NC 27260 NORTH CAROLINNS INTERNATIONAL CITYTm February 22, 2011 Division of Water Quality/NPDES Unit 1617 Mail Service Center Raleigh, NC 27699-1617 Subject: City of High Point Frank L. Ward Water Filtration Plant Permit Renewal Application NPDES # NC0081256, Guilford County To Whom It May Concern: The NPDES permit for the City of High Point Frank L. Ward Water Filtration Plant expires on August 31, 2011. In accordance with State and Federal regulations, the City is requesting NPDES renewal for the subject facility. This permit renewal application includes: Short Form C — WTP, map of exact location of outfalls, schematic of flows through the facility with chemical addition points and a copy of Solids Handling Plan. We look forward to working with you on the renewal of Frank L. Ward Water Filtration Plant's NPDES permit.. Please contact me at 336-883-3410 if you need any additional information. Sinc relyd, ! Robert W. Pickett Water Plant Superintendent Cc: Terry Houk, Assistant Director Public Services File rR FB , 4 Z011 L ILt 1 CHP Water Filtration Plant, P.O. 230, High Point, NC 27261 USA 336.883.3410 Fax:336.883.3109 ' • NPDES PERMIT APPLICATION - SHORT FORM C - WTP For discharges associated with water treatment plants Mail the complete application to: N. C. Department of Environment and Natural Resources Division of Water Quality / NPDES Unit 1617 Mail Service Center, Raleigh, NC 27699-1617 NPDES Permit Number INCO081256 If you are completing this form in computer use the TAB key or the up - down arrows to move from one field to the next. To check the boxes, click your mouse on top of the box. Otherwise, please print or type. 1. Contact Information: Owner Name Facility Name Mailing Address City State / Zip Code Telephone Number Fax Number e-mail Address City of High Point Frank L. Ward WTP 2011 East Kivett Drive High Point North Carolina 27261 (336)883-3410 (336)883-3109 wendell.pickett@highpointnc.gov 2. Location of facility producing discharge: Check here if same as above Street Address or State Road City State / Zip Code County Guilford 3. Operator Information: Name of the firm, consultant or other entity that operates the facility. (Note that this is not referring to the Operator in Responsible Charge or ORC) Name City of High Point Mailing Address 2011 East Kivett Drive City High Point State / Zip Code North Carolina Telephone Number (336)883-3410 Fax Number (336)883-3109 4. Ownership Status: Federal ❑ State ❑ 5. Type of treatment plant: Private ❑ Page 1 of 4 C-WTP 03/05 ' • NPDES PERMIT APPLICATION - SHORT FORM C - WTP For discharges associated with water treatment plants ® Conventional (Includes coagulation, flocculation, and sedimentation, usually followed by filtration and disinfection) ❑ Ion Exchange (Sodium Cycle Cationic ion exchange) ❑ Green Sand Filter (No sodium recharge) ❑ Membrane Technology (RO, nanofiltration) Check here if the treatment process also uses a water softener ❑ 6. Description of source water(s) (i.e. groundwater, surface water) Surface, Two Lakes 1) High Point City Lake 2) Oak Hollow Lake 7. Describe the treatment process(es) for the raw water: Raw water is brought in from either lake into an upflow clarifier where alum and a polymer is added for coagulation and flocculation. Water is settled using a floc blanket. ®slater is then sent to the filters for filtration and disinfection. Caustic is added for pH control, Hydrofluosilic Acid is added for dental health and a corrision inhibtor is added for corrision contol. Water is then pumped to the distribution system. S. Describe the wastewater and the treatment process(es) for wastewater generated by the facility: Sludge blowdown from our treatment process and filter backwash is how our wastewater is generated. It is diverted into 2- 10 milliom gallon ponds for settling. 9. Number of separate discharge points: 2 Outfall Identification number(s) 001,002 10. Frequency of discharge: Continuous ® Intermittent ❑ If intermittent: Days per week discharge occurs: Duration: 11. Plant design potable flowrate 32 MGD Backwash or reject flow 1.0 MGD 12. Name of receiving stream(s) (Provide a map showing the exact location of each outfall, including latitude and longitude): unnamed tributary to Richland Creek, Discharge 001 - N35 58.053, W79 58.326, discharge 002 - N35 58.201, W79 58.317 Map attached. Page 2 of 4 C-WTP 03/05 NPDES PERMIT APPLICATION - SHORT FORM C e WTP For discharges associated with water treatment plants 13. Please list all water treatment additives, including cleaning chemicals, that have the potential to be discharged. Aluminum Sulfate Caustic soda ( Sodium Hydroxide) Bleach ( Sodium Hypochlorite) Polyphosphate Hydrofluosilic Acid Aqua Ammonia 14. Is this facility located on Indian country? (check one) Yes ❑ No 15. Additional Information: Provide a schematic of flow through the facility, include flow volumes at all points in the treatment process, and point of addition of chemicals. Solids Handling Plan 16. NEW Applicants Information needed in addition to items 1-15. New applicants must contact the NCDENR Customer Service Center. Was the Customer Service Center contacted? ❑ Yes ❑ No Analyses of source water collected Engineering Alternative Analysis Discharges from Ion Exchange and Reverse Osmosis plants shall be evaluated using a water quality model. 17. Applicant Certification I certify that I am familiar with the information contained in the application and that to the best of my knowledge and belief such information is true, complete, and accurate. North Carolina General Statute 143-215.6 (b)(2) provides that: Any person who knowingly makes any false statement representation, or certification in any application, record, report, plan, or other document files or required to be maintained under Article 21 or regulations of the Environmental Management Commission implementing that Article, or who falsifies, tampers with, or knowingly renders inaccurate any recording or monitoring device or method required to be_ operated or maintained under Article 21 or regulations of the Environmental Management Commission implementing that Article, shall be guilty of a misdemeanor punishable Page 3 of 4 C-WTP W/O NPDES PERMIT APPLICATION - SNORT FORM C - WTP For discharges associated with water treatment plants by a fine not to exceed $25,000, or by imprisonment not to exceed six months, or by both. (18 U.S.C. Section 1001 provides a punishment by a fine of not more than $25,000 or imprisonment not more than 5 years, or both, for a similar offense.) Page 4 of 4 C-WTP 03/05 G�oE-%--ric)N IE> — AODI:T3!c)N LWFUKMAL100 -,i .. . 11 `.- From 22k- PUMP Stamm ,a Primary caftoff Source 147-8amn.7 RMYMx /* Rom C I Ik 1-10110W Lake (Polymer) Pump sb�ftao cozb 014 i I 4 - pumps Secondary source r—Q--I L Chemical Bulk Tanks 1- 6,= gal, Flumide Tank 3- 10,00 gal. Causbc Tank 1- 6.= gal. Cormsbn InhbMor Tank 1- 20,000 gal. Alum Tank undeFgFound) io MG T.* \-—( 5MG Tank ih Mix -4AIum addition) Flacculabw (Caustic sod i Co k"7 in'ObRor) P Unit (Fucdde) U7- . Clarification r (rlleach) 000 3 - 10,= gals. E i Tanks 409ft EMM98MMOMPOM dirge 02cmd pumps � NORTH CMY of Nth Paint Wwd W~Ant F" to 62-41-020 NC 0018 12.56 I (Ammonia for mines)(not cutuently In uw) blea: I for Chlor&Wff=XndcummW in Compliance sample finished vvvier code 001 Pftn compliance samples rawwstw eMeD17 SGOW viater 0oft 103 4—fibla Mated w9w omb M Coag- Code 102 -4-FRIA; as* WOEM - cmcmc-AL AC)piricily MEMO J= LOW'VOLWAES Question 15) Addition Information City of High Point Frank L. Ward Water Filtration Plant Solids Handling Plan NCO081256 The Frank L. Ward Water Filtration Plant has (2) -10 million gallon settling ponds for alum sludge which includes process waste and filter backwash. Solids are accumulated for a period of about 2 years or until the ponds are approximately three quarters full. At this time, the City of High Point bids the sludge removal out and awards contract to low bidder. The company that wins the contract brings in portable centrifuges and dewaters the sludge which in turn is disposed of at the local landfill. _1 City of High Point Public Services Department PLANTS DIVISION P.ECEIVED N.C. Dent. of ENR NOV 0 12010 Winston-Salem October 28, 2010 Regional Office LCD6ENR f r Carter — Doi s3vn of Water Quality a�Iem Regional Office 585 Waughtown Street Winston Salem, NC 27107 Dear Mrs. Carter: NORTH CAROLINNS INTERNATIONAL CITY" Referencing our phone call and email communications on October 25th of this week, we are submitting data for a residual chlorine analysis reportedly performed on the sample for the Ward Filter Plant Washwater Recovery Basin Lagoon Effluent recognizing that the actual worksheet cannot be found. We are unsure of how it was lost and have been unable to recover it in our normal review process. We are sure the analysis was performed as the value was recorded for the person collecting the sample on his. chain -of - custody. The supporting email documentation of our communication and also with Gary Francis of the DWQ Certification Section in Raleigh is attached. Respectfully, William Frazier Lab Services Manager P.O.230, High Point, NC 27261 USA Phone:336.883.3410 Fax:336.883.3109 TDD:336.883.8517 w 1 w BILL FRAZIER From: Carter, Jenifer Oenifer.carter@ncdenr.gov] Sent: Monday, October 25, 2010 3:28 PM To: BILL FRAZIER Cc: Tedder, Steve; Francies, Gary Subject: RE: Cl2 for a DMR W I agree with Gary, that the data can be qualified on the DMR. Qualifying the data is acceptable for such rare occurrences. Obviously, if a pattern developed, that would be a different story. We would not determine whether or not a DMR is checked 'compliant' or'not compliant' on the DMR itself. That is up to the person signing the DMR. DWQ does make its own determination if sampling frequencies/limits were met when data is entered into our database, and that may or may not (but should) match which box is checked on the DMR. I hope that helps. Let us know if you have any questions. Jenifer Carter Before printing this email, please consider your budget and the environment. If you must print, please print only what you need and save ink with the free Eco-Font. NC DENR Winston-Salem Regional Office Division of Water Quality 585 Waughtown Street Winston-Salem, NC 27107 Voice: (336) 771-4957 FAX: (336) 771-4630 E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. From: BILL FRAZIER [mailto:bill.frazier@highpointnc.gov] Sent: Monday, October 25, 2010 3:10 PM To: Carter, Jenifer Subject: FW: Cl2 for a DMR Jenifer: It'll make the most sense read from the bottom up. Thanx for taking a look at this for me and I appreciate your leniency. bf From: Francies, Gary [mailto:gary.francies(�)ncdenr.govl Sent: Friday, October 22, 2010 10:19 AM To: BILL FRAZIER Subject: RE: Cl2 for a DMR. Bill Are you just making these up to test me or stretch my brain!!!! Just kidding. I would recommend you report the data and attach an explanation as to what happened — similar to what you have here — I agree I would not mark the DMR as non compliant — let the data receivers — that is WSRO make that determination — I don't think they would — it just needs to be qualified and explained. If you do not report it you could get a frequency violation and you actually did perform the analysis —you just lost the "proof" Take care and have a good weekend Gary Note: My email address has changed to gary.francies@ncdenr.gov E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. Gary Francies - Gary.Francies@ncdenr.gov North Carolina Dept. of Environment and Natural Resources Asheville Regional Office Division of Water Quality - Laboratory Certification 2090 U.S. 70 Highway Swannanoa, NC 28778 Tel: 828-296-4677 Fax: 828-299-7043 From: BILL FRAZIER Imailto:bill.frazier@highpointnc.govl Sent: Friday, October 22, 2010 9:44 AM To: Francies, Gary Cc: DAWN WILSON Subject: 02 for a DMR Gary: I wish I could explain it in some scientific way other than the full moon but I cannot. Bottom line: I have a missing residual chlorine worksheet. Here's the facts: - The analysis was done but the worksheet is gone - The data was transferred to the DMR as is our internal policy and the worksheet submitted for review. - The person collecting the actual sample transfers the reading as it happens to his COC for his personal knowledge. - The only place a handwritten reading exists is as transferred on that COC but no required certification documentation exists. - In a similar decision recently out of WSRO, data was allowed on a DMR without proper analytical documentation as there was supplementary documentation and qualified. The DMR was not marked as Non -compliant. Please tell me how you want us to handle it. Include the data or not. I'll let WSRO decide on whether it gets marked as N/C. bf °4 RECEIVED EFFLUENT S N.C. Deot of ENR NPDES PERMIT NO. NCO081256 DISCHARGE NO.002 MONTH September YE 2010 Winston-Salem FACILITY NAME Frank L. Ward WTP CLASS I COUNTY Guilford Regional C-ffrlce CERTIFIED LABORATORY (1) City of High Point Water Quality Laboratory CERTIFICATION NO. 55 (list additional laboratories on the backside/page 2 of this form) OPERATOR IN RESPONSIBLE CHARGE (ORC) Robert W. Pickett GRADE I CERTIFICATION NO.27377 PERSON(S) COLLECTING SAMPLES per daily Chain of Custodf ORC PHONE (336) 883-3410 CHECK BOX IF ORC HAS CHANGED Mail ORIGINAL and ONE COPY to: 1� ej _ G ATTN: CENTRAL FILES ix _,�� / DIVISION OF WATER QUALITY (SICiNATM OF OPnATQR IN MVONSIBLE CHARGE) DATE 1617 MAIL SERVICE CENTER BY THIS SIGNATURE, I CERI PTliAT THIS REPORT IS RALEIGH NC 27699-1617 ACCURATE AND COMPLETE TO THE BEST OF MY KNOWLEDGE. _0mn • ••1111r Now @� 0'r • •• � I I I I 0 I I I 0�� ���@• ��®__MITI m, Monthly Limit DWQ Form MR-1 (11/04) Facility Status: (Please check one of the following) All monitoring data and sampling frequencies meet permit requirements (including weekly averages, if applicable) Compliant All monitoring data and sampling frequencies do NOT meet permit requirements F] Noncompliant The permittee shall report to the Director or the appropriate Regional Office any noncompliance that potentially threatens public health or the environment. Any information shall be provided orally within 24 hours from the time the permittee became aware of the circumstances. A written submission shall also be provided within 5 days of the time the permittee becomes aware of the circumstances. If the facility is noncompliant, please attach a list of corrective actions being taken and a time -table for improvements to be made as required by Part H.E.6 of the NPDES permit. "I certify, under penalty of law, that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who managed the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fines and imprisonment for knowing violations." f pepv Permittee (Please print or type) Signature of ittee** Date (Required unless submitted electronically) City of High Point - Public Services Dept. PO Box 230 - High Point, NC 27261 (336) 883-3279 terry.houk@highpointmLM August 31, 2011 Permittee Address Phone Number e-mail address Permit Expiration Date Certified Laboratory (2) Certified Laboratory (3) Certified Laboratory (4) Certified Laboratory (5) ADDITIONAL CERTIFIED LABORATORIES PARAMETER CODES Certification No. Certification No. Certification No. Certification No. Parameter Code assistance may be obtained by calling the NPDES Unit at (919) 733-5083 or by visiting the Surface Water Protection Section's web site at h2o.enr.state.nc.us/wqs and linking to the unit's information pages. Use only units of measurement designated in the reporting facility's NPDES permit for reporting data. * No Flow/Discharge From Site: Check this box if no discharge occurs and, as a result, there are no data to be entered for all of the parameters on the DMR for the entire monitoring period. ** ORC On Site?: ORC must visit facility and document visitation of facility as required per 15A NCAC 8G .0204. * * * Signature of Permittee: If signed by other than the permittee, then the delegation of the signatory authority must be on file with the state per 15A NCAC 2B .0506(b)(2)(D). Page 2 City of High, Point Public Services Department PLANTS DIVISION NORTH CAROLINNS INTERNATIONAL CITr October 28, 2010 Mrs. Jenifer Carter NCDENR — Division of Water Quality Winston Salem Regional Office 585 Waughtown Street Winston Salem, NC 27107 Dear Mrs. Carter: Referencing our phone call and email communications on October 25th of this week, we are submitting data for a residual chlorine analysis reportedly performed on the sample for the Ward Filter Plant Washwater Recovery Basin Lagoon Effluent recognizing that the actual worksheet cannot be found. We are unsure of how it was lost and have been unable to recover it in our normal review process. We are sure the analysis was performed as the value was recorded for the person collecting the sample on his chain -of - custody. The supporting email documentation of our communication and also with Gary Francis of the DWQ Certification Section in Raleigh is attached. Respectfully, William Frazier Lab Services Manager P.O.230, High Point, NC 27261 USA Phone:336.883.3410 Fax:336.883.3109 TDD:336.883.8517 BILL FRAZIER From: Carter, Jenifer Denifer.carter@ncdenr.gov] Sent: Monday, October 25, 2010 3:28 PM To: BILL FRAZIER Cc: Tedder, Steve; Francies, Gary Subject: RE: Cl2 for a DMR an I agree with Gary, that the data can be qualified on the DMR. Qualifying the data is acceptable for such rare occurrences. Obviously, if a pattern developed, that would be a different story. We would not determine whether or not a DMR is checked 'compliant' or'not compliant' on the DMR itself. That is up to the person signing the DMR. DWQ does make its own determination if sampling frequencies/limits were met when data is entered into our database, and that may or may not (but should) match which box is checked on the DMR. I hope that helps. Let us know if you have any questions. Jenifer Carter FA Before printing this email, please consider your budget and the environment. If you must print, please print only what you need and save ink with the free Eco-Font. NC DENR Winston-Salem Regional Office Division of Water Quality 585 Waughtown Street Winston-Salem, NC 27107 Voice: (336) 771-4957 FAX: (336) 771-4630 E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. From: BILL FRAZIER,[mailto:bill.frazier@highpointnc.gov] Sent: Monday, October 25, 2010 3:10 PM To: Carter, Jenifer Subject: FW: Cl2 for a DMR Jenifer: it'll make the most sense read from the bottom up. Thanx for taking a look at this for me and I appreciate your leniency. bf From: Francies, Gary [mailto:gaiy.francies@ncdenr.gov] Sent: Friday, October 22, 2010 10:19 AM 1 To: BILL FRAZIER Subject: RE: Cl2 for a DMR Bill Are you just making these up to test me or stretch my brain!!!! Just kidding. I would recommend you report the data and attach an explanation as to what happened — similar to what you have here — I agree I would not mark the DMR as non compliant — let the data receivers — that is WSRO make that determination — I don't think they would — it just needs to be qualified and explained. If you do not report it you could get a frequency violation and you actually did perform the analysis — you just lost the "proof' Take care and have a good weekend Gary Note: My email address has changed to gM.franciesP_ncdenr.gov E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. Gary Francies - Gary.Francies@ncdenr.gov North Carolina Dept. of Environment and Natural Resources Asheville Regional Office Division of Water Quality - Laboratory Certification 2090 U.S. 70 Highway Swannanoa, NC 28778 Tel: 828-296-4677 Fax: 828-299-7043 From: BILL FRAZIER jmailto:bill.frazierCd)highpointnc.govl Sent: Friday, October 22, 2010 9:44 AM To: Francies, Gary Cc: DAWN WILSON Subject: Cl2 for a DMR Gary: I wish I could explain it in some scientific way other than the full moon but I cannot. Bottom line: I have a missing residual chlorine worksheet. Here's the facts: - The analysis was done but the worksheet is gone - The data was transferred to the DMR as is our internal policy and the worksheet submitted for review. - The person collecting the actual sample transfers the reading as it happens to his COC for his personal knowledge. - The only place a handwritten reading exists is as transferred on that COC but no required certification documentation exists. - In a similar decision recently out of WSRO, data was allowed on a DMR without proper analytical documentation as there was supplementary documentation and qualified. The DMR was not marked as Non -compliant. Please tell me how you want us to handle it. Include the data or not. I'll let WSRO decide on whether it gets marked as N/C. bf Carter, Jenifer From: Tedder, Steve Sent: Tuesday, October 26, 2010 7:10 AM To: BILL FRAZIER Cc: Francies, Gary; Carter, Jenifer Subject: RE: C12 for a DMR Gary is right on the money. No one said we were going to be lenient, he just told you how to handle on the DMR. Tedder Just Kidding E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. Steve Tedder Steve.TedderPNCDENR.Rov NC DENR Division of Water Quality 585 Waughtown Street Winston-Salem, NC 27107 (336)-771-4950 Fax (336) 771-4630 From: Carter, Jenifer Sent: Monday, October 25, 2010 3:28 PM To: BILL FRAZIER Cc: Tedder, Steve; Francies, Gary Subject: RE: Cl2 for a DMR I agree with Gary, that the data can be qualified on the DMR. Qualifying the data is acceptable for such rare occurrences. Obviously, if a pattern developed, that would be a different story. We would not determine whether or not a DMR is checked 'compliant' or'not compliant' on the DMR itself. That is up to the person signing the DMR. DWQ does make its own determination if sampling frequencies/limits were met when data is entered into our database, and that may or may not (but should) match which box is checked on the DMR. I hope that helps. Let us know if you have any questions. Jenifer Carter Before printing this email, please consider your budget and the environment. If you must print, please print only what you need and save ink with the free Eco-Font. NC DENR Winston-Salem Regional Office Division of Water Quality 585 Waughtown Street Winston-Salem, NC 27107 Voice: (336) 771-4957 FAX: (336) 771-4630 E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties From: BILL FRAZIER [mailto:bill.frazier@highpointnc.gov] Sent: Monday, October 25, 2010 3:10 PM To: Carter, Jenifer Subject: FW: 02 for a DMR Jenifer: `� It'll make the most sense read from the bottom up. Thanx for taking a look at this for me and I appreciate your leniency. bf From: Francies, Gary [mailto:gary.francies@ncdenr.gov] Sent: Friday, October 22, 2010 10:19 AM To: BILL FRAZIER Subject: RE: 02 for a DMR mu Are you just making these up to test me or stretch my brain!!!! Just kidding. I would recommend you report the data and attach an explanation as to what happened — similar to what you have here — I agree I would not mark the DMR as non compliant — let the data receivers —that is WSRO make that determination — I don't think they would — it just needs to be qualified and explained. If you do not report it you could get a frequency violation and you actually did perform the analysis — you just lost the "proof' Take care and have a good weekend Gary Note: My email address has changed to gary.francies@,nedenr.gov E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties. Gary Francies - Gary.Francies@ncdenr.gov North Carolina Dept. of Environment and Natural Resources Asheville Regional Office Division of Water Quality - Laboratory Certification 2090 U.S. 70 Highway Swannanoa, NC 28778 Tel: 828-296-4677 r Fax: 828-299-7043 r' From: BILL FRAZIER [mailto:bill.frazier@highpointnc.gov] Sent: Friday, October 22, 2010 9:44 AM To: Francies, Gary Cc: DAWN WILSON Subject: 02 for a DMR Gary: I wish I could explain it in some scientific way other than the full moon but I cannot. Bottom line: I have a missing residual chlorine worksheet. Here's the facts: - The analysis was done but the worksheet is gone - The data was transferred to the DMR as is our internal policy and the worksheet submitted for review. - The person collecting the actual sample transfers the reading as it happens to his COC for his personal knowledge. - The only place a handwritten reading exists is as transferred on that COC but no required certification documentation exists. - In a similar decision recently out of WSRO, data was allowed on a DMR without proper analytical documentation as there was supplementary documentation and qualified. The DMR was not marked as Non -compliant. Please tell me how you want us to handle it. Include the data or not. I'll let WSRO decide on whether it gets marked as N/C. bf 3 h NCDENR North Carolina Department of Environment and Natural Resources Division of Water Quality Beverly Eaves Perdue Coleen H. Sullins Governor Director 29 October 2009 Mr. Terry Houk, Assistant Director of Public Services City of High Point PO Box 230 High Point, NC 27261-0230 SUBJECT: Compliance Evaluation Inspection City of High Point — Frank L. Ward WTP NPDES Permit No. NCO081256 Guilford County Dear Mr, Houk: Dee Freeman Secretary A Compliance Evaluation Inspection (CEI) was performed on the City of High Point's Frank L. Ward water treatment plant on Wednesday, October 28, 2009 by Corey Basinger of the Winston-Salem Regional Office. Mr. Wendell Pickett, ORC represented the City for'the inspection. The inspection consisted of two parts: an on -site inspection of the treatment facility and a file review. The following are the findings from.the subject inspection. I. Permit The NPDES permit for the City of High Point's Frank L. Ward WTP became effective September 1, 2006 and expires on -:..August 31, 2011. II. Records/Reports A review of the laboratory reports and Discharge Monitoring Reports (DMRs) for the City of High Point's Frank L. Ward WTP revealed no discrepancy between the generated data and the data submitted to DWQ. A copy of the laboratory data is kept on file at the wastewater plant. Maintenance records are in the form of work orders and are kept at the Maintenance Dept. No deficiencies were noted with respect to the record keeping. I.II. Facility Site Review The Frank L. Ward WTP has two 10 million gallon settling lagoons (14 feet deep) in series that are used to treat the filter backwash from the clarifiers. The facility is currently permitted to discharge filter backwash wastewater to an unnamed tributary to Richland Creek from the following outfalls: 1) Outfall 001 — discharge from the South Lagoon 2) Outfall 002 —discharge from the North Lagoon IV. Effluent / Receiving Stream The WTP discharges to an unnamed tributary to Richland Creek (Class C waters in the Cape Fear River Basin). The receiving waters appeared clear of solids and debris on the date of the subject inspection. North Carolina Division of Water Quality, Winston-Salem Regional Office Location: 585 Waughtown St. Winston-Salem, North Carolina 27107 Phone: 336-771-50001 FAX: 336-771-46301 Customer Service: 1-877-623-6748 Internet: www.ncwaterquality.org An Equal Oppo,tunity k Aftinnative Action Employer One NorthCarohna Naturally City of High Point — Frank L. Ward WWTP Compliance Evaluation Inspection October 29, 2009 Page 2 of 2 V. Flow Measurement Flow is measured instantaneously at Outfall 001 with a Parshall flume. Flow is measured instantaneously at Outfall 002 using the rational method. VI. Self-Monitorina Program Effluent samples are collected at the specified locations depending upon which outfall is being used. Upstream and downstream samples are collected at the designated locations. All sampling locations are marked with metal poles with cleared access. All monitoring was performed in compliance with the NPDES Permit No. NC0081256. A review of the discharge monitoring reports (DMRs) for the time period of July 2008 through July 2009 demonstrated that the Frank L. Ward WTP experienced no effluent permit limit violations. VII. Laboratory The City of High Point Laboratory conducts all of the sample analyses. The laboratory was not reviewed at the time of the subject inspection. VIII. Operations and Maintenance Preventive maintenance schedules are set up based on manufacturers specifications and are printed out automatically once a month from the Central shop and given to the maintenance personnel at the Frank L. Ward WTP. Most maintenance work is performed by the mechanical and electrical personnel that are assigned to the WTP from the City's Maintenance Dept. Equipment operations are monitored using a SCADA system. IX. Sludge Utilization/Disbosal Sludge removal is expected to begin in early 2010. X. Other The last compliance inspection was conducted on October 31, 2007. If you have any questions or concerns regarding this report, please contact Corey Basinger at 336-771-4963 Sincerely, Steve W. Tedder Water Quality Supervisor Cc: Wendell Pickett, City of High Point, PO Box 230, HP, NC 27261 RHO' Central Files Form Approved OMB No.2040-0057 �A Approval Expires ' 8-31-98 United States Environmental Protection Agency Washington_ D.C.. 20460 Section A: National Data System Coding Transaction Code NPDES No. Yr/Mo/Day Inspection Type Inspector FacilityType N 5 NCO081256 09-10-28 C S 1 Facility Evaluation Rating BI QA ..........Reserved........... 5 N N_ Section B: Facility Data Name and Location of Facility Inspected: Entry Time: Permit Effective 0920 hrs. Date: Sept 1, 2006 City of High Point — Frank L. Ward Water Treatment Plant Exit Time: Permit Expiration 1020 hrs. Date: August 31, 2011 Name(s) of On -Site Representative(s): Title(s): Phone No(s): Mr. Robert W. (Wendell) Pickett ORC 336-883-3410 Name, Address of Responsible Official: Title: Assistant Director of Public Services Mr. Terry Houk City of High Point Phone No. 336-883-3109 Contacted? No PO Box 230 High Point, NC 27261 Section C: Areas Evaluated During Inspection • Permit • Flow Measurement • Operations/Maintenance • Records/Reports • Self -Monitoring Program • Sludge Handling/Disposal • Facility Site Review • Effluent/Receiving Waters Section D: Summary of Findings/Comments Permit..................................Current permit expires August 31, 2011. Records/Reports..................The� operators daily records are maintained as per permit conditions. Facility Site Review ............ No problems noted with respect to facility site review. Effluent/Receiving Waters.. No samples collected. Receiving stream showed no visible impact on date of inspection. Flow Measurement .............. Effluent flow is measured by the rational method and a parshall flume. Self -Monitoring Program.... The DMR's are submitted as required by NPDES permit Operations/Maintenance..... No problems were noted with respect to operations and maintenance. Sludge Disposal .................. Solids removal should begin in early 2010. (SEE DATA SUMMARY ATTACKED FOR THE PERIOD 07/08 — 07/09) Name s nd Signature(s) of Inspectors: Agency/Office/Telephone: DWQ / WSRO / (336)771-5000 Date: Signature of Revie er: Agency/Office: Date: �I%iL_ DWQ / WSRO / (336)771-5000 A, r Permit: NCO081256 Owner - Facility: Frank L. Ward WTP Inspection Date: 10/28/2009 Inspection Type: Compliance Evaluation Compliance Schedules Yes No NA NE Is there a compliance schedule for this facility? ■ Is the facility compliant with the permit and conditions for the review period? ■ n D n Comment: Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? ■ n n 0 Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ ❑ ❑ Judge, and other that are applicable? Comment: .. Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new application? O Q ® ❑ Is the facility as described in the permit? ®n # Are there any special conditions for the permit? p n Is access to the plant site restricted to the general public? Is the inspector granted access to all areas for inspection? ®� ❑ ❑ Comment: Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ® ❑ Q Cl Is all required information readily available, complete and current? ® n n ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ®n ❑ ❑ Are analytical results consistent with data reported on DMRs? ®� ❑ Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling ■ Results of analysis and calibration Dates of analysis ■ Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ® n ❑ 0 Has the facility submitted its annual compliance report to users and DWQ? ® ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? ® ❑ ❑ Q Page # 3 Permit: NCO081256 Owner - Facility: Frank L. Ward WTP Inspection Date: 10/28/2009 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Is the ORC visitation log available and current? ■ ❑ El C3 Is the ORC certified at grade equal to or higher than the facility classification? ■ n 0 n Is the backup operator certified at one grade less or greater than the facility classification? ■ n ❑ n Is a copy of the current NPDES permit available on site? ■ n ❑ n Facility has copy of previous year's Annual Report on file for review? ■ n n n Comment: Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ■ n n n Are the receiving water free of foam other than trace amounts and other debris? ■ Q n n If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ■ Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ■ Is flow meter calibrated annually? n n ■ n Is the flow meter operational? nn■n (If units are separated) Does the chart recorder match the flow meter? n n Comment: Flow measured using the rational method and a parshall flume. Lagoons Yes No NA NE Type of lagoons? Aerated # Number of lagoons in operation at time of visit? 2 Are lagoons operated in? Series # Is a re -circulation line present? 0 0 ■ Is lagoon free of excessive floating materials? ■ n n n # Are baffles between ponds or effluent baffles adjustable? ❑ n ® Q Are dike slopes clear of woody vegetation? ■ ❑ n n Are weeds controlled around the edge of the lagoon? ®n n n Are dikes free of seepage? ■ n n n Are dikes free of erosion? ■ n n n Are dikes free of burrowing animals? ■ n Q n # Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations? ■ n n n Page # 4 a Permit: NCO081256 Inspection Date: 10/28/2009 Owner- Facility: Frank L. Ward WTP Inspection Type: Compliance Evaluation Lagoons Yes No NA NE # If excessive algae is present, has barley straw been used to help control the growth? ❑ ❑ ■ ❑ Is the lagoon surface free of weeds? ®❑ n ❑ Is the lagoon free of short circuiting? ® ❑ ❑ ❑ Comment: Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ ■ ❑ Is sample collected below all treatment units? ■ ❑ n ❑ Is proper volume collected? ®❑ ❑ ❑ Is the tubing clean. n❑■❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? ■ n ❑ ❑ Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ®❑ ❑ ❑ Comment: Page # 5 RECEIVED N.C. Dept. of ENR City of High .Point A To C No. 081256A01 APR 2 5 Issued February 5, 2008 Winston-5alom Regional Office �`'"EB r - Engineer's Certification.? 1, (Y) I C-kC4e l ' ! , S 1 u, s h e r' , as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (periodically/weekly/full time) the construction of the modifications and improvements to the Frank L. Ward WTP, located on East Kivett Drive in Guilford County for City of High Point, hereby state that, to the best of my abilities, due care and diligence was used in the observation of the following construction: Installation of dechlorination system utilizing sodium sulfite pursuant to the fast track applicailon received on January 28, 2008, and in conformity with the Minimum Design Criteria for Dechl.orination Facilities. I certify that the construction of the above referenced project was observed to be built within substantial compliance and intent of the approved plans and specifications. 6< Z/ Signature��f!�.,�Registration No. Date 7� Send to: Construction Grants & Loans DENR/DWQ 1633 Mail Service Center Raleigh, NC 27699-16 33 o?D5,?o r� 7 d Terry Houk Director of Water Resources City of High Point PO Box 230 High Point, North Carolina 27261 SUBJECT: Dear Mr. Houk: (p7z- Michael F. Easley, Governor William G. Ross Jr., Secretary North Carolina Department of Environment and Natural Resources February 5, 2008 Authorization to Construct A to C No. 081256AOI City of High Point Frank L. Ward WTP Dechlorination Facilities Guilford County Coleen H. Sullins, Director Division of Water Quality RECEItYED — N.C. Deot. o+ EEB 0 7 2008 Winston-S, Regional O-i A fast track application for Authorization to Construct dechlorination facilities was. received on January 28, 2008, by the Division. Authorization is hereby granted for the construction of modifications to the existing Frank L. Ward WTP, with discharge of backwash water into unnamed tributary to Richland Creek in the Cape Fear River Basin. This authorization results in no increase in design or permitted capacity and is awarded for the construction of the following specific modifications: Installation of a dechlorination system utilizing sodium sulfite pursuant to the fast track application received on January 28, 2008, and in conformity with the Minimum Design Criteria for Dechlorination Facilities. This Authorization to Construct is issued in accordance with Part III, Paragraph A of NPDES Permit No. NCO081256 issued August 9, 2006, and shall be subject to revocation unless the wastewater treatment facilities are constructed in accordance with the conditions and limitations specified in Permit No. NC0081256. In the event that the facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take iinmediate corrective action, including those as may be required by this Division, such as the construction of additional or replacement wastewater treatment or disposal facilities. The Winston-Salem Regional Office, telephone number (336) 771-5000 shall be notified at least forty-eight (48) hours in advance of operation of the installed facilities so that an on site NorthCarolina Naturally North Carolina Division of Water Quality t617 ivlail Service Center Raleigh, NC 27699-1617 Phone (919) 733-7015 Customer Service Internet: www.ncvaterguality.org 512 N. Salisbury St. Raleigh, NC 27604 FAX (919) 733-2496 1-877-623-6748 An Equal Opportunity/Affirmative Action Employer — 50% Recycled/10% Post Consumer Paper Mr. Houk February 5, 2008 Page 2 inspection can be made. Such notification to the regional supervisor shall be made during the normal office hours from 8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State Holidays. Pursuant to 15A NCAC 2H .0140, upon completion of construction and prior to operation of these permitted facilities, the completed Engineering Certification form attached to this permit shall be submitted to the address provided on the form. Upon classification of the facility by the Certification Commission, the Permittee shall employ a certified wastewater treatment plant operator to be in responsible charge (ORC) of the wastewater treatment facilities. The operator must hold a certificate of the type and grade at least equivalent to or greater than the classification assigned to the wastewater treatment facilities by the Certification Commission. The Permittee must also employ a certified back-up operator of the appropriate type and grade to comply with the conditions of T15A:8G.0202. The ORC of the facility must visit each Class I facility at least weekly and each Class Il, III and IV facility at least daily, excluding weekends and holidays, must properly manage the facility, must document daily operation and maintenance of the facility, and must comply with all other conditions of TI5A:8G.0202. A copy of the approved plans and specifications shall be maintained on file by the Permittee for the life of the facility. During the construction of the proposed additions/modifications, the permittee shall continue to properly maintain and operate the existing wastewater treatment facilities at all times, and in such a manner, as necessary to comply with the effluent limits specified in the NPDES Permit. You are reminded that it is mandatory for the project to be constructed in accordance with the North Carolina Sedimentation Pollution Control Act, and, when applicable, the North Carolina Dam Safety Act. In addition, the specifications must clearly state what the contractor's responsibilities shall be in complying with these Acts. Prior to entering into any contract(s) for construction, the recipient must have obtained all applicable permits from the State. Failure to abide by the requirements contained in this Authorization to Constrict may subject the Permittee to an enforcement action by the Division of Water Quality in accordance with North Carolina General Statute 143-215.6A to 143-215.6C. The issuance of this Authorization to Construct does not preclude the Permittee from complying with any and all statutes, rules, regulations, or ordinances which may be imposed by other government agencies (local, state, and federal) which have jurisdiction. 31 Mr. Houk February 5, 2008 Page 3 If you have any questions or need additional information, please do not hesitate to contact Cecil G. Madden, Jr., P.E. at telephone number (919) 715-6203. Sincerely, Coleen H. Sullins AR/cgm cc: Michael L. Slusher, P.E., Davis -Martin -Powell & Associates, High Point Guilford County Health Department <'�W s3 Qna egg a:ftfiee, Surface Water Protection Technical Assistance and Certification Unit Daniel Blaisdell, P.E. Point Source Branch, NPDES Program Cecil G. Madden, Jr., P.E. Anita E. Reed, P.E. ATC File City of High Point A To C No. 081256A01 Issued February 5, 2008 Engineer's Certification as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (periodically/weekly/full time) the construction of the modifications and improvements to the Frank L. Ward WTP, located on East Kivett Drive in Guilford County for City of High Point, hereby state that, to the best of my abilities, due care and diligence was used in the observation of the following construction: Installation of a dechlorination system utilizing sodium sulfite pursuant to the fast track application received on January 28, 2008, and in conformity with the Minimum Design Criteria for Dechlorination Facilities. I certify that the construction of the above referenced project was observed to be built within substantial compliance and intent of the approved plans and specifications. Signature Date Registration No. Send to: Construction Grants & Loans DENR/DWQ 1633 Mail Service Center Raleigh, NC 27699-1633 � O�p� W A (� 7 Mr. Terry Houk, Assistant Director of Public Services City of High Point PO Box 230 High Point, NC 27261-0230 SUBJECT: Compliance Evaluation Inspection City of High Point - Frank L. Ward WTP NPDES Permit No. NCO081256 Guilford County Dear Mr. Houk: Michael F. Easley, Governor William G. Ross Jr., Secretary North Carolina Department of Environment and Natural Resources 31 October 2007 Coleen H. Sullins, Director Division of Water Quality A Compliance Evaluation Inspection (CEI) was performed on the City of High Point's Frank L. Ward water treatment plant on Wednesday, October 31, 2007 by Corey Basinger of the Winston-Salem Regional Office. Mr. Wendell Pickett, ORC represented the City for the inspection. The inspection consisted of two parts: an on -site inspection of the treatment facility and a file review. The following are the findings from the subject inspection. I. Permit The NPDES permit for the City of High Point's Frank L. Ward WTP became effective September 1, 2006 and expires on August 31, 2011. II. Records/Reports A review of the laboratory reports and Discharge Monitoring Reports (DMRs) for the City of High Point's Frank L. Ward WTP revealed no discrepancy between the generated data and the data submitted to DWQ. A copy of the laboratory data is kept on file at the wastewater plant. Maintenance records are in the form of work orders and are kept at the Maintenance Dept. No deficiencies were noted with respect to the record keeping. III. Facility Site Review The Frank L. Ward WTP has two 10 million gallon settling lagoons (14 feet deep) in series that are used to treat the filter backwash from the clarifiers. The facility is currently permitted to discharge filter backwash wastewater to an unnamed tributary to Richland Creek from the following outfalls: 1) Outfall 001 —discharge from the South Lagoon 2) Outfall 002 — discharge from the North Lagoon IV. Effluent / Receiving Stream The WTP discharges to an unnamed tributary to Richland Creek (Class C waters in the Cape Fear River Basin). The receiving waters appeared clear of solids and debris on the date of the subject inspection. V. Flow Measurement Flow is measured instantaneously at Outfall 001 with a Parshall flume. Flow is measured instantaneously at Outfall 002 using the rational method. No°C Carolina Nturu!!y North Carolina Division of Water Quality 585 Waughtown Street Phone (336) 771-5000 Customer Service Winston-Salem Regional Office Winston-Salem, NC 27107 Fax (336) 771-4630 1-877-623-6748 Internet: www.ncwaterquality.org An Equal Opportunity/Affirmative Action Employer— 50% Recycledl10% Post Consumer Paper City of High Point — Frank L. Ward WWTP Compliance Evaluation Inspection October 31, 2007 Page 2 of 2 VI. Self -Monitoring Program Effluent samples are collected at the specified locations depending upon which outfall is being used. Upstream and downstream samples are collected at the designated locations. All sampling locations are marked with metal poles with cleared access. All monitoring was performed in compliance with the NPDES Permit No. NC0081256. A review of the discharge monitoring reports (DMRs) for the time period of August 2006 through August 2007 demonstrated that the Frank L. Ward WTP experienced no effluent permit limit violations. VII. Laboratory The City of High Point Laboratory conducts all of the sample analyses. The laboratory was not reviewed at the time of the subject inspection. VIII. Operations and Maintenance Preventive maintenance schedules are set up based on manufacturers specifications and are printed out automatically once a month from the Central shop and given to the maintenance personnel at the Frank L. Ward WTP. Most maintenance work is performed by the mechanical and electrical personnel that are assigned to the WTP from the City's Maintenance Dept. Equipment operations are monitored using a SCADA system. IX. Sludge Utilization/Disposal Sludge removal from both lagoon #1 was in progress during the inspection. Solids from lagoon #2 will be removed before the end of 2007. No problems were noted with respect to sludge disposal. X. Other The newly reissued permit includes a Total Residual Chlorine (TRC) limit of 17ug/L effective March 1, 2008. In order to meet this new TRC limit, the facility must have some means to dechlorinate. Currently, the only chlorinated water being discharged into the lagoons is filter backwash water. The City conducted a short term "pilot study" to assist in determining if the proposed system is capable of achieving compliance with the new TRC limit. Results of this study demonstrate that the system has consistently met the new TRC limit. All that remains to be completed is the submittal of an Authorization to Construct for the proposed system. Please provide a copy of this submittal to this Office. If you have any questions or concerns regarding this report, please contact Corey Basinger at 336-771-4963. S*in cerel , Steve W. Tedder Water Quality Supervisor Cc: Wendell Pickett, City of High Point, PO Box 230, HP, NC 27261 %dW R@.MV Central Files Form Approved OMB No.2040-0057 Approval Expires 8-31-98 United States Environmental Protection ABenev. Washineton. D.C.. 20460 Section A: National Data S stem'Coding Transaction Code NPDES No. Yr/Mo/Day' Inspection Type Inspector FacilityType N 5 NCO081256 07-10-31 C S 1 Facility Evaluation Rating BI QA ..........Reserved........... 4 N N Section B: Facility Data Name and Location of Facility Inspected: Entry Time: Permit Effective 1020 hrs. Date: Sept 1, 2006 City of High Point — Frank L. Ward Water Treatment Plant Exit Time: Permit Expiration 1105 hrs. Date: August 31, 2011 Name(s) of On -Site Representative(s): Title(s): Phone No(s): Mr. Robert W. (Wendell) Pickett ORC 336-883-3410 Name, Address of Responsible Official: Title: Assistant Director of Public Services Mr. Terry Houk City of High Point Phone No. 336-883-3109 Contacted? No PO Box 230 High Point, NC 27261 Section C: Areas Evaluated During Inspection • Permit • Flow Measurement 4 Operations/Maintenance • Records/Reports • Self -Monitoring Program • Sludge Handling/Disposal • Facility Site Review • Effluent/Receiving Waters Section D: Summary of Findings/Comments Permit..................................Current permit expires August 31, 2011. Records/Reports ..................The operators daily records are maintained as ,per permit conditions. Facility Site Review ............ No problems noted with respect to facility site review. Effluent/Receiving Waters.. No samples collected. Receiving stream showed no visible impact on date of inspection. Flow Measurement .............. Effluent flow is measured by the rational method and a parshall flume. Self -Monitoring Program.... The DMR's are submitted as required by NPDES permit Operations/Maintenance..... No problems were noted with respect to operations and maintenance. Sludge Disposal .................. Solids removal in progress during inspection. Should be complete with both lagoons by end of 2007. (SEE DATA SUMMARY ATTACHED FOR THE PERIOD 08/06 - 08/08) Name(s) and Signature(s) of Inspectors: Agency/Office/Telephone: Date: DWQ / WSRO /'(336)771-5000 Signature of Re ewer: Agency/Office: Date: DWQ / WSRO / (336)771-5000 r '8 Permit: NCO081256 Inspection Date: 10/31/2007 Owner- Facility: Frank L. Ward WTP Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? ■ R R R Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ Judge, and other that are applicable? Comment: Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new application? ❑ ❑ ■ ❑ Is the facility as described in the permit? ■ ❑ R ❑ # Are there any special conditions for the permit? ■ ❑_ R ❑ Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? ■ ❑ ❑ ❑ Comment: TRC limit to take effect 3/1/08 Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ® ❑ ❑ R Is all required information readily available, complete and current? ■ R R R Are all records maintained for 3 years (lab. reg. required 5 years)? ®❑ R R Are analytical results consistent with data reported on DMRs? ®❑ R ❑ Is the chain -of -custody complete? ®R R R Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration ■ Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit. parameters? ® ❑ R ❑ Has the facility submitted its annual compliance report to users and DWQ? ®❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? ® R R R Is the ORC visitation log available and current? ■ ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? R R R Is the backup operator certified at one grade less or greater than the facility classification? ®❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ®❑ ❑ ❑ Page # 3 Permit: NC0081256 Owner - Facility: Frank L. Ward WTP Inspection Date: 10/3112007 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for'review? ■ ❑ ❑ ❑ Comment: Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ■ ❑ n n Are the receiving water free of foam other than trace amounts and other debris? ■ ❑ ❑ n If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ® ❑ Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ ■ ❑ Is flow meter calibrated annually? ❑ ❑ ■ ❑ Is the flow meter operational? ❑ ❑ ■ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ n ■ o Comment: flow measured using the rational method and a Pars hall flume Lagoons Yes No NA NE Type of lagoons? Aerated # Number of lagoons in operation at time of visit? 2 Are lagoons operated in? Series # Is a re -circulation line present? ❑ ❑ ® n Is lagoon free of excessive floating materials? ■ ❑ ❑ ❑ # Are baffles between ponds or effluent baffles adjustable? n n ■ n Are dike slopes clear of woody vegetation? m ❑ ❑ n Are weeds controlled around the edge of the lagoon? e n n n Are dikes free of seepage? ■ n In n Are dikes free of erosion? ■ ❑ n n Are dikes free of burrowing animals? ■ n n n # Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations? ®❑ n In # If excessive algae is present, has barley straw been used to help control the growth? ❑ ❑ ■ ❑ Is the lagoon surface free of weeds? ® ❑ n n Is the lagoon free of short circuiting? ■ ❑ n n Page # 4 I Permit: NCO081256 Inspection Date: 10/31/2007 Owner- Facility: Frank L. Ward WTP Inspection Type: Compliance Evaluation Lagoons Yes NO NA NL Comment: solids being removed from lagoon during inspection. Will continue until both lagoons are cleaned out. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? n n ■ n Is sample collected below all treatment units? ■ n n n Is proper volume collected? ■ ❑ ❑ ❑ Is the tubing clean? n n ■ Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)? ■ Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ■ ❑ ❑ Comment: Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? ■ ❑ ❑ ❑ Comment: Page # 5 ' d 6415 Old Plank Road, High Point, NC 27265 (336) 886-4821 o Fax (336) 886-4458 - www.dmp-inc.com FZ8CEfvED N.C. Dept of ENR Winston-Salem Reoional Office Ms. Anita Reed NCDENR-CG&L 1633 Mail Service Center Raleigh, NC 27699-1633 Dear Ms. Reed: January 25, 2008 Re: City of High Point, NC Frank L. Ward WTP DMP E-4240 BF Transmitted with this letter are two copies of the Dechlorination Facilities Fast Track ATC package on behalf of the City of High Point. This is for the Water Plant's backwash lagoon effluent as described in the application. If you have any questions, or need additional information, please give me a call. Sincerely, DAVIS=Sluer, LL & ASSOCIATES Micha M LS/ CADocuiruents and 367\D0csyCGL1,3867 reuse Cornet(,nts Jan2008.doc c: Mr. Terry .ftHouk (encl DE 'Nint STaI file North Carolina Division Of Water Quality Construction Grants & Loans Section Dechlorination Facilities Fast -Track Authorization To Construct (ATC) Application Cover (To Be Used On and After August 1, 2007) INSTRUCTIONS: Indicate that you have included the following list of required application package items by signing your initials in the space provided next to each item. Failure to submit all required items will lead to return of the permit application. A. Application Form - Submit one original and one copy of the completed and appropriately executed application form. Any changes to this form will result in the application being returned. The Division of Water Quality (the Division) will only accept application packages that have been fully completed with all applicable items addressed. You DO NOT need to submit detailed plans and specifications at this time. Plans and specifications shall be maintained on -site. B. Certification Form - Submit the completed engineers certification form signed and sealed by a professional engineer registered in the state of North Carolina. C. Designated Representative - If the application is being filed by a party other than the owner, a letter from the owner designating the applicant as his/her authorized representative must be included. D. Read, understood, and followed the Dechlorination System Minimum Design Criteria (adopted 4/18/03 and as subsequently amended). The completed application package should be sent to the following address: North Carolina Division Of Water Quality Construction Grants & Loans Section By U.S. Postal Service: By Courier/Special Delivery: 1633 Mail Service Center 2728 Capital Blvd Raleigh, NC 27699-1633 Raleigh, NC 27604 Phone: (919) 715-6203 Fax: (919) 715-6229 For more information, visit our website at http://www.nccgl.neVEngineering/plans.htmi North Carolina Division Of !:dater Quality Construction Grants & Loans Section Dechlorination Facilities Fast -Track Authorization To Construct (ATC) Application Form (To Be Used On and After August 1, 2007) Date: 1/24/2008 Permittee/Owner Name: City of High Point Contact Person: Robert Pickett, ORC Address: PO Box 230 High Point, NC 27261 Telephone Number: (336) 883-3417 I NPDES Permit Number: NCO081256 Facility Name: Frank L.' Ward WTP Facility Address (Physical Location): 2011 East Kivett Drive High Point, NC County project is located in: Guilford Name of receiving stream: unnamed tributary to Richland Creek Name of river basin: Cape Fear Professional Engineer of Record: Michael L. Slusher Engineering Firm: Davis -Martin -Powell & Associates Address: 6415 Old Plank Road High Point, NC 27265 Telephone Number: (336)886-4821 Date Issued: 9/1/2006 Project Description: Installation of Tablet Dechlorination Equipment on existing backwash waste lagoon discharges Type of dechlorinating agent used (chemical): Sodium Sulfite (Na2SO3) If other, please specify: i North Carolina Division Of Water Quality Construction Grants & Loans Section ®echiorination Facilities Fast -Track Authorization To Construct (ATC) Certification (To Be Used On and After August 1, 2007) Professional Engineer's Certification: I, Michael L. Slusher, attest that this application for Frank L. Ward-WTP Dechlorination has been reviewed by me and is accurate, complete, and consistent with the information in the engineering plans, calculations, and all other supporting documentation. I further attest that the proposed design has been prepared in accordance with all applicable regulations and Minimum Design Criteria for Dechlorination Facilities, adopted April 18, 2003. Although certain portions of this submittal package may have been prepared by other professionals, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the proposed design. NOTE: In accordance with NC General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. Furthermore, failure to design the above referenced facilities in accordance with Minimum Design Criteria for Dechlorination Facilities and good engineering practice could subject you to —disciplinary action by the North Carolina Board for Professional Engineers and Land Surveyors. North Carolina Professional Engineer's seal, signature, and date: � ° dry' 'yu ' Yef•' {g y SAL — Signature: ��;',•.: „cPfxb�0r>� Date: January 23, 2008 Registration No.: 20590'�'o�an ^�?' Applicant's Certification: I, Terry Houk, attest that this application for Frank L. Ward WTP Dechlorination has been reviewed by me and is accurate and complete to the best of my knowledge. By signing this certification I certify that facilities have been designed in accordance with Minimum Design Criteria for Dechlorination Facilities, adopted April 18, 2003, and commit to insure construction proceeds in accordance with said criteria. NOTE: In accordance with NC General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. Signature: _17Date: )^�d I. v