Mr. Michael Walker, Secretary
Seagrove-Ulah Metropolitan Water District
P.O. Box 370
Seagrove, NC 27341
Subject: Compliance Evaluation Inspection
Seagrove-Ulah Metropolitan Water District WWTF Wastewater Irrigation System
Permit No. WQ0002648
Randolph County
Dear Mr. Walker:
On July 30, 2020, staff from the Division of Water Resources (DWR) performed a compliance
inspection of the Seagrove-Ulah Metropolitan Water District WWTF wastewater irrigation system.
This compliance inspection was conducted by DWR staff persons Caitlin Caudle and Patrick
Mitchell. Accompanying DWR staff on this inspection was Larry Chilton, ORC, and Russell
Welch, Back-up ORC. This inspection of the facility reflected compliance with permit No.
WQ0002648. The following items of concern were noted:
1) Per Permit Condition III.1 the facilities shall be properly maintained and operated at all
times. At the time of inspection, a water diversion ditch was noted to be clogged with debris
and sediment, resulting in over ground flow eroding a gravel drive leading to the sludge
basin. Please repair this diversion ditch and associated piping to prevent damage to
structures down gradient and limit impacts to septage trucks hauling solids from the
residuals basin.
2) Per Permit Condition III.6 irrigation equipment shall be tested and calibrated at least once
per permit cycle. Please calibrate the irrigation equipment by September 30, 2020 and
keep the records on file for at least five years.
3) In a review of select irrigation zones two sprinkler heads were not operating correctly.
Please ensure irrigation zones are being monitored to guarantee sprinkler heads are
working properly and necessary repairs are being made.
Please refer to the enclosed inspection report for additional comments and details from the
inspection. If you have any questions related to this inspection, please contact Ms. Caudle or me
D � North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office [ 450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
NOh �HCARO UHA
^^ •^^ma^� u�•i` r 336.776.9800
at the letterhead address and phone number, or by email at Ion.sniderkncdenr. og_v or
caitlin.caudle(cncdenr.gov. The Division would like to express appreciation for the care taken by
ORCs to maintain the wastewater and irrigation systems.
Sincerely,
ED''ocu SiTgnedl�by:
Li7�.
145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston Salem Regional Office
Division of Water Resources, NCDEQ
enc: Compliance Inspection Report
cc: Randolph County Health Department (Electronic)
Laserfiche File WQ0002648
WQROS WSRO Electronic Files
0A;�7HCRC)Li AD ���
D.po h ml of Erntrommml OualIt,
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 Hanes Mill Road, Suite 300 1 Winston-Salem, North Carolina 27103
336.776.9800
Compliance Inspection Report
Permit: WQ0002648 Effective: 10/01/15 Expiration: 09/30/20 Owner: Seagrove -Utah Metropolitan Water District
SOC: Effective: Expiration: Facility: Seagrove -Utah Metropolitan Water District WW
County: Randolph 770 NC Hwy 705 S
Region: Winston-Salem
Seagrove NC 27341
Contact Person: Larry Thomas Chilton Title: ORC
Phone: 336-215-3835
Directions to Facility:
from i-40/85 in greensboro, take US 220 south. Take exit 52 south to seagrove. At town of Seagrove turn left heading south on NC
Hwy 705
System Classifications: SI, WW2,
Primary ORC: Larry Thomas Chilton Certification: 28234 Phone: 336-215-3835
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 07/30/2020 Entry Time 10:15AM
Primary Inspector: Caitlin Caudle
Secondary Inspector(s):
Reason for Inspection: Routine
Permit Inspection Type: Wastewater Irrigation
Facility Status: 0 Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent
Treatment Flow Measurement -Water
Use Records
Treatment Lagoons
End Use -Irrigation
Treatment Flow Measurement
(See attachment summary)
Exit Time: 12:40PM
Phone: 336-776-9699
Inspection Type: Compliance Evaluation
Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Record Keeping
Treatment Activated Sludge Treatment Sludge Storage/Treatment
Treatment Clarifiers Treatment Disinfection
Storage
Page 1 of 6
Permit: WQ0002648 Owner - Facility: Seagrove -Utah Metropolitan Water District
Inspection Date: 07/30/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
On 7/30/2020 staff persons Caitlin Caudle and Patrick Mitchell conducted a routine compliance inspection. Accompanying
on the inspection was Larry Chilton, ORC and Russel Welch, BU-ORC. The facility was found to be compliant. The following
items of concern were noted:
• Two spray heads in soil sampling zone 1 were not operating correctly when a review of select irrigation zones was
conducted. Please ensure that all irrigation heads are functional and necessary repairs are made.
• A setback waiver will be required if a building close to the wastewater treatment plant is sold to a new owner. A copy of
the setback waiver was provided after the inspection via email.
• A storm water diversion ditch and associated underground piping were noted to need repair. The ditch appeared to be
clogging the pipe with sediment and debris, causing water to flow over ground and erode the driveway leading to the sludge
basin. This could impact septage trucks attempting to haul solids from the sludge basin, and potentially impact the down
gradient structures.
• A separate review of March and April's monthly self monitoring reports showed missing parameters and flow not being
monitored continuously. The permit requires reporting flow through the wastewater plant continuously and certain parameters
be sampled three or four times a year. Please report flow continuously on future NDMRs and monitor parameters at required
frequencies. This will be addressed in a separate correspondence.
• The irrigation system had not been calibrated to date. The permit requires irrigation systems to be calibrated once per
permit cycle. A calibration document was provided after the inspection via email, once the calibration is complete please
keep a copy with your records. A reminder the current permit expires September 30, 2020.
• Residuals removal records are kept with daily maintenance logs. Moving forward, please keep copies of the receipts
from the residual hauler.
• Flow meters measuring influent flow are not included in the current permit description.
• An Operations and Management Plan was not present on site. An engineer has been hired to design an O&M plan that
better represents the current flow path and operations.
• The pumps meant to transfer effluent from the existing lagoon to the new lagoon are not connected to the new lagoon
Before operation of the new lagoon, the pipes connecting the pumps and new lagoon should be installed.
• The first splitter box receiving influential flow has two pipes open that lead directly to the effluent storage pond and to the
industrial treatment lines. These pipes could lead to potential bypasses of the treatment system during high flow events.
Staff appreciate the extra care taken by ORCs with the maintenance of the wastewater system and irrigation system.
Page 2 of 6
Permit: WQ0002648
Owner - Facility: Seagrove -Utah Metropolitan Water District
Inspection Date: 07/30/2020
Inspection Type: Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Activated Sludge Drip, LR
❑
Activated Sludge Spray, LR
❑
Infiltration System
❑
Reuse (Quality)
❑
Activated Sludge Spray, HR
❑
Recycle/Reuse
❑
Single Family Spray, LR
❑
Single Family Drip
❑
Lagoon Spray, LR
Treatment
Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? ❑ 0 ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) ❑ 0 ❑ ❑
Comment: There are two digestors and clarifiers listed in the permit, a 30,000 GPD and 60,000 GPD. The
60,000 GPD unit and associated components are nonoperational. There is also an influent flow
meter not listed in the permit. These missing and nonoperational components will be addressed
in the new permit.
Treatment Flow Measurement -Influent Yes No NA NE
Is flowmeter calibrated annually? ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment: The digital flowmeter measures daily flow on a 24 hr period, resetting around 3:30 - 4:00 PM. A
flowmeter with a chart is also present that registers GPM.
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ ❑
Comment: The flow rates are totaled daily by a meter.
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ ❑
Is flowmeter operating properly?
❑ ❑ ❑
Does flowmeter monitor continuously?
❑ ❑ ❑
Does flowmeter record flow?
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
❑ ❑ ❑
Page 3 of 6
Permit: WQ0002648 Owner - Facility: Seagrove -Utah Metropolitan Water District
Inspection Date: 07/30/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Comment: Effluent flow is measured using gallons of water irrigated.
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable? 0 ❑ ❑ ❑
Is the aeration basin thoroughly mixed? 0 ❑ ❑ ❑
Is the aeration equipment easily accessed? 0 ❑ ❑ ❑
Is Dissolved Oxygen adequate? ❑ ❑ ❑
Are Settleometer results acceptable? ❑ ❑ ❑
Is activated sludge an acceptable color? 0 ❑ ❑ ❑
Comment:
Treatment Clarifiers
Yes No NA NE
Are the weirs level?
❑ ❑ ❑
Are the weirs free of solids and algae?
❑ ❑ ❑
Is the scum removal system operational?
❑ ❑ ❑
Is the scum removal system accessible?
❑ ❑ ❑
Is the sludge blanket at an acceptable level?
❑
❑ ❑
Is the effluent from the clarifier free of excessive solids?
❑ ❑ ❑
Comment:
Treatment Sludge Storage/Treatment Yes No NA NE
Is the aeration operational? ❑ ❑ ❑
Is the aeration pattern even? ❑ ❑ ❑
If required, are Sanitary "Ts" present in tankage? ❑ ❑ 0 ❑
Comment: Sludge is removed every 1-2 weeks by wasting sludge from the clarifier and aeration basin. A
local septage hauler is utilized to remove the sludge from a -3,500 gallon basin.
Treatment Disinfection
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (-30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■❑❑❑
■❑❑❑
❑❑■❑
❑❑❑■
■❑❑❑
❑❑■❑
❑❑■❑
■❑❑❑
❑❑■❑
Page 4 of 6
Permit: WQ0002648 Owner - Facility: Seagrove -Utah Metropolitan Water District
Inspection Date: 07/30/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine
If UV, is the UV intensity adequate? ❑ ❑ 0 ❑
# Is it a dual feed system? ❑ ❑ 0 ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ 0 ❑
If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment:
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑ ❑ ❑
NDAR?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑ ❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑ ❑ ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
❑ ❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑ ❑ ❑
Is a copy of the SOC readily available?
❑
❑ ❑
No treatment units bypassed since last inspection?
❑ ❑ ❑
Comment: TDS November 2019
End Use-Irriqation Yes No NA NE
Are buffers adequate? 0 ❑ ❑ ❑
Page 5 of 6
Permit: WQ0002648 Owner - Facility: Seagrove -Utah Metropolitan Water District
Inspection Date: 07/30/2020 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Is the cover crop type specified in permit?
0
❑ ❑ ❑
Is the crop cover acceptable?
0
❑ ❑ ❑
Is the site condition adequate?
0
❑ ❑ ❑
Is the site free of runoff / ponding?
0
❑ ❑ ❑
Is the acreage specified in the permit being utilized?
0
❑ ❑ ❑
Is the application equipment present?
0
❑ ❑ ❑
Is the application equipment operational?
❑
0 ❑ ❑
Is the disposal field free of limiting slopes?
0
❑ ❑ ❑
Is access restricted and/or signs posted during active site use?
❑
❑ ❑
Are any supply wells within the CB?
❑
0 ❑ ❑
Are any supply wells within 250' of the CB?
❑
0 ❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Is municipal water available in the area?
❑
❑ ❑
# Info only: Does the permit call for monitoring wells?
0
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
0
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
0
❑ ❑ ❑
Are monitoring wells damaged?
❑
❑ ❑
Comment: Two sprinkler heads in the tested irrigation lanes were noted to need repair.
The entire 40 acres
is not utilized during each irrigation event.
Page 6 of 6