HomeMy WebLinkAboutWQCSD0632_Inspection_20200501Compliance Inspection Report
Permit:WQCSD0632 Effective:06/09/15 Expiration:Owner :Aubrey Lewis Deaver
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Henderson
Asheville
Aubrey Lewis Deaver
Effective:Expiration:Facility:High Vista Falls
Title:Phone:828-884-9772
Secondary ORC(s):
Phone:Certification:Primary ORC:
System Classifications:
On-Site Representative(s):
Related Permits:
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
05/01/2020 11:00AM 11:50AM
Daniel J Boss 828-296-4658
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Follow-up
Deemed permitted collection system management and operation
Collection System Inspect Non Sampling
Question Areas:
Miscellaneous Questions Manholes
(See attachment summary)
Page 1 of 3
DocuSign Envelope ID: 9C49CEEC-165C-42A8-93C0-C2DA92A8B48F
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQCSD0632
05/01/2020 Collection System Inspect Non Sampling
Aubrey Lewis Deaver
Follow-up
Inspection Summary:
On 5/1/2020 I (Daniel Boss) met with Aubrey Deaver Jr for a follow up inspection of the High Vista Falls collection system.
During my last inspection, we thought we had located a source of I&I into the collection system at a property located on
Round Robin Lane Vista Falls Rd. Mr. Deaver said that he had followed up on that investigation and inspected the line,but
no source of I&I was found.
Mr. Deaver told me that he has been making lots of visits to the High Vista Falls subdivision to inspect the manholes during
both wet and dry weather. The only potential source of I&I that he has found recently is a line from the High Vista
clubhouse. During a rain event Mr. Deaver said the 6 inch line from the clubhouse was flowing at least half full, and there
were only 3 cars in the clubhouse parking lot. During this inspection we again inspected these lines and there was no flow
at all. There was no rain the day of this inspection. This may be indicating that the clubhouse is a source of inflow into the
collection system, but more investigation needs to be done by A&D Water Service to verify.
We encountered at least 5 buried manholes on our walks through the previously suspected I&I section at Round Robin Lane
and Vista Falls Rd, and the line up to the clubhouse. All manholes in the collection system need to be uncovered and
accessible. A&D Water Service should contact the HOA and residents to inform them that burying manholes is not an
acceptable practice.
Page 2 of 3
DocuSign Envelope ID: 9C49CEEC-165C-42A8-93C0-C2DA92A8B48F
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQCSD0632
05/01/2020 Collection System Inspect Non Sampling
Aubrey Lewis Deaver
Follow-up
Manholes Yes No NA NE
Please list the Manholes Inspected:
Several manholes along the clubhouse wastewater line and Devonshire Dr and Fairway Falls Rd.
Are manholes accessible?
# Are manhole covers/vents above grade?
Are manholes free of visible signs of overflow?
Are manholes free of sinkholes and depressions?
Are manhole covers present?
# Are manholes properly seated?
# Are manholes in good condition?
# Are inverts in good condition?
Is flow unrestricted in manholes?
Are manholes free of excessive amounts of grease?
Are manholes free of excessive roots?
Are manholes free of excessive sand?
Are manhole vents screened?
Are vents free of submergence?
Are manholes free of bypass structures or pipes?
About 5 of the manholes we located were buried and inaccessible.Comment:
Page 3 of 3