United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0036641 20/07/09 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Fletcher Academy WWTP
185 Fletcher Academy Dr
Fletcher NC 28732
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:15AM 20/07/09 16/01/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Davis Allen James/ORC/828-697-0063/
Other Facility Data
11:30AM 20/07/09 20/12/31
Name, Address of Responsible Official/Title/Phone and Fax Number
David S Wack,PO Box 5440 Fletcher NC 287325440//828-687-5114/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Flow Measurement Operations & Maintenance Self-Monitoring Program Facility Site Review
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Lauren E Armeni DWR/ARO WQ/828-296-4500/
Daniel J Boss DWR/ARO WQ/828-296-4658/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: F83C2AC7-A5D0-4D70-8AFB-1768E03AD319
8/3/2020
8/3/2020
8/3/2020
NPDES yr/mo/day
20/07/09
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 7/9/2020 I (Daniel Boss) and Lauren Armeni conducted an inspection of the Fletcher Academy
WWTP. We met with Davis James (ORC), Juanita James, and two employees from Fletcher
Academy.
The clarification lagoons were covered with duckweed. Removal of the duckweed could help with
treatment of the wastewater.
Flow proportional composite sampling is required for several parameters, but only grab sampling is
being performed. Juanita claims a former inspector, Don Price, authorized this method of sampling for
all parameters. I could not find any evidence of such permission granted.
NC0036641 17 (Cont.)
Page#2
DocuSign Envelope ID: F83C2AC7-A5D0-4D70-8AFB-1768E03AD319
Permit:NC0036641
Inspection Date:07/09/2020
Owner - Facility:
Inspection Type:
Fletcher Academy WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Lagoons Yes No NA NE
Type of lagoons?Aerated
# Number of lagoons in operation at time of visit?1
Are lagoons operated in?Multicell
# Is a re-circulation line present?
Is lagoon free of excessive floating materials?
# Are baffles between ponds or effluent baffles adjustable?
Are dike slopes clear of woody vegetation?
Are weeds controlled around the edge of the lagoon?
Are dikes free of seepage?
Are dikes free of erosion?
Page#3
DocuSign Envelope ID: F83C2AC7-A5D0-4D70-8AFB-1768E03AD319
Permit:NC0036641
Inspection Date:07/09/2020
Owner - Facility:
Inspection Type:
Fletcher Academy WWTP
Compliance Evaluation
Lagoons Yes No NA NE
Are dikes free of burrowing animals?
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple
locations?
# If excessive algae is present, has barley straw been used to help control the growth?
Is the lagoon surface free of weeds?
Is the lagoon free of short circuiting?
The lagoon is divided into 2 aeration cells and 2 clarification cells. The clarification cells are
covered in duckweed. The DO was measured at 6.8 mg/L and pH was 7.2 in the first
aerated cell. The DO was <0.5 mg/L and the pH was 6.9 in the last clarification cell.
Comment:
Disinfection-Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?8
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Page#4
DocuSign Envelope ID: F83C2AC7-A5D0-4D70-8AFB-1768E03AD319
Permit:NC0036641
Inspection Date:07/09/2020
Owner - Facility:
Inspection Type:
Fletcher Academy WWTP
Compliance Evaluation
Effluent Sampling Yes No NA NE
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Grab sampling is being used for all parameters. The permit requires flow proportional
sampling.
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Could not access the outfall pipe.Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Multiple portable generators are available for use during a power interruption.Comment:
Page#5