HomeMy WebLinkAboutNC0088668_Inspection_20200724United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO088668 I11 121 20/07/21 I17 18LC I 19 Ls_] I 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n,J I I I 71 I 74 79 I I I I I I I80
701� I 711 L
LJ L
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
11:20AM 20/07/21
16/12/01
Engelhard WTP
N Lake Rd
Exit Time/Date
Permit Expiration Date
Engelhard NC 27824
12:OOPM 20/07/21
21/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Not Required/ORC/919-807-6353/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Clint Berry,PO Box 66 Swanquarter NC 27885//252-926-6455/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
7/24/2020
Robert DWR/Division of Water Qua Iity/252-948-3924/
[E[[Bullock
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
Nco088668 I11 12I 20/07/21 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The review period for this inspection was July 2018 through May 2020. There were no violations over
the review period.
The February 2020 eDMR was spot checked for accuracy. The upstream and downstream samples
for Turbidity was reported on the DMR as mg/I with the lab result as ppt. The February 2020 eDMR
needs to be revised and resubmitted.
The facility was judged to be Compliant with NPDES permit NC0088668.
Page#
Permit: NCO088668
Inspection Date: 07/21/2020
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Owner -Facility: Engelhard WTP
Inspection Type: Compliance Evaluation
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment: The current permit is set to expire on November 30, 2021.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification
Is a copy of the current NPDES permit available on site?
Yes
No
NA
NE
■
❑
❑
❑
❑
❑
❑
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ■ ❑ ❑
■ ❑ ❑ ❑
El
El
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ❑
Page# 3
Permit: NCO088668
Inspection Date: 07/21/2020
Owner -Facility: Engelhard WTP
Inspection Type: Compliance Evaluation
Record Keeping
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
❑ ❑ ■ ❑
Comment: The February 2020 eDMR was spot checked for accuracy. The upstream and downstream
samples for Turbidity was reported on the DMR as mq/I with the lab result as ppt. The
February 2020 eDMR needs to be revised and resubmitted.
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Hyde County is field parameter certified. Toxicity sample is sent to Environmental Testing_
Solutions and all other samDles are sent to Environment 1 for analvsis.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: The effluent flow meter was calibrated on October
Environmental.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
2019 by Delta S
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: Samples are grab as stated in the NPDES permit.
Effluent Pipe
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
Yes No NA NE
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
Page# 4
Permit: NC0088668 Owner -Facility: Engelhard WTP
Inspection Date: 07/21/2020 Inspection Type: Compliance Evaluation
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
0
❑
❑
❑
Comment: No adverse conditions were noticed from the shore.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, an( 0 ❑ ❑ ❑
sampling location)?
Comment:
Page# 5