HomeMy WebLinkAboutWQ0033677_More Information (Requested)_20191021ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
PAUL TAYLOR — HATCHERY MANAGER
CASE FARMS, LLC
5067 FOREMAN STREET
MORGANTON, NORTH CAROHNA 28655
Dear Mr. Taylor:
NORTH CAROLINA
Environmental Quality
October 21, 2019
Subject: Application No. WQ0033677
Additional Information Request
Case Farms — Morganton Hatchery
Wastewater Irrigation
Burke County
Division of Water Resources' Central and Regional staff has reviewed the application package
received August 13, 2019. However, additional information is required before the review may be
completed. Please address the items on the attached pages no later than the close of business on November
21, 2019.
Please be aware that you are responsible for meeting all requirements set forth in North Carolina
rules and regulations. Any oversights that occurred in the review of the subject application package are
still the Applicant's responsibility. In addition, any omissions made in responding to the outstanding items
in Sections A through P, or failure to provide the additional information on or before the above requested
date may result in your application being returned as incomplete.
Please reference the subject application number when providing the requested information. All
revised and/or additional documentation shall be signed, sealed and dated (where needed), with two paper
copies and one electronic copy submitted to my attention at the address below.
If you have any questions regarding this request, please do not hesitate to contact me at (919) 707-
3658 or ashley.kabat@ncdenr.gov. Thank you for your cooperation.
Sincerely,
>�V�
Ashley Kabat, Environmental Engineer
Division of Water Resources
cc: Asheville Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Gary S. MacConnell, PE — MacConnell & Associates, P.C. (Electronic Copy)
Permit Application File WQ0033677
R ��North Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 1 1617 Mail Service Center I Raleigh, North Carolina 27699-1617
NORTHCMOLINA
919.707.9000
Mr. Paul Taylor
October 21, 2019
Page 2 of 4
A. Cover Letter:
1. The Technical Memorandum submitted to Mikal Willmer of the Asheville Regional Office on
October 1, 2019 indicated that irrigation area in Zone 1 and Zone 2 was being removed due to a
setback violation for an onsite place of public assembly. Please be aware that a Non -Discharge
Wastewater System Waiver can be filled out and recorded with the Burke County Register of Deeds
to waive this setback.
B. Application Fee:
1. No Comments
C. Application:
The application must be signed in accordance with 15A NCAC 02T .0106(b), by the president or
vice-president of the company, or a signature authority delegation form shall be filled out
delegating Paul Taylor.
D. Property Ownership Documentation:
1. No Comments
E. Soil Evaluation:
1. No Comments
F. Agronomist Evaluation:
I. No Comments
G. Hydrogeologic Report:
1. A hydrogeologic report shall be prepared by a Licensed Geologist, Licensed Soil Scientist, or
Professional Engineer and shall be provided to the Division by the applicant for systems treating
industrial waste. This report shall include items listed in the WWIS 06-16 application, at a
minimum. [15A NCAC 02T .0504(e)]
2. Provide an analysis on the current monitoring well locations at this site in relation to the proposed
irrigation area. If the monitoring wells do not sufficiently capture the groundwater up -gradient and
downgradient of the wastewater application site, propose new well location(s). [15A NCAC 02T
.0504(e)]
H. Water Balance:
1. No Comments
Mr. Paul Taylor
October 21, 2019
Page 3 of 4
I. En2ineerin2 Plans:
1. Show the existing monitoring well locations on sheet C-104. [15A NCAC 02T .0504(d)]
2. Show a clearing, grubbing, and fill plan/notes in the Engineering Plans. It is unclear which areas
will be cleared, grubbed, and/or filled. Show all major surface diversion ditches to be filled. [15A
NCAC 02T .0504(c)]
A revised Engineering plan was sent to Mikal Willmer in the Asheville Regional Office on October
1, 2019 showing reduced irrigation area in Zones 5 and 6. If Zones 5 and 6 are being reduced in
size, all applicable materials related to the irrigation area sizing shall be modified (i.e. cover letter,
application, water balance, engineering specifications, engineering calculations, and site map). A
signed, sealed, and dated full-size and half-size plan set shall also be submitted with the updated
modifications.
J. Specifications:
1. Provide further specifications on the earthwork that will occur in the irrigation area. It is unclear
if fill material will be provided inside the wetted area boundary or if it will only be used to fill
ditches in the unsuitable areas. [15A NCAC 02T .0504(c)]
2. Specify if the woods will be thinned and lanes installed per the Soil Scientist's recommendation.
[15A NCAC 02T .0504(c)]
3. It is unclear if the existing pump controls the existing irrigation area and the proposed pump
controls the proposed irrigation area. Multiple pumps shall be provided wherever pumps are used.
Either provide calculations showing that one pump has the ability to irrigate all zones, provide a
third pump for back-up, or apply for Alternative Design Criteria for lack of pump duality. [15A
NCAC 02T .0505(k)]
K. En2ineerina Calculations:
1. No Comments
L. Site Map:
1. Show the existing monitoring well locations on sheet C-104. [15A NCAC 02T .0504(d)]
M. Power Reliability Plan:
1. No Comments
N. Operation & Maintenance Plan:
1. No Comments
Mr. Paul Taylor
October 21, 2019
Page 4 of 4
O. Residuals Management Plan:
1. No Comments
P. Additional Documentation:
➢ Certificate of Public Convenience and Necessity:
1. N/A
➢ Existing Permit:
1. No Comments
➢ Final Environmental Document:
1. N/A
➢ Floodway Regulation Compliance:
1. N/A
➢ Operational Agreements:
1. N/A
➢ Threatened or Endangered Aquatic Species Documentation:
1. No Comments
➢ Wastewater Chemical Analysis: