SUBJECT: Compliance Inspection Report
New Bern WWTP
NPDES WW Permit No. NCO025348
Craven County
Dear Mr. Hartman:
The North Carolina Division of Water Resources conducted an inspection of the New Bern WWTP on
6/23/2020. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NCO025348. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required. The facility was found to be compliance with NPDES permit #NCO025348 and
has passed the toxicity test. The results of the toxicity test are included.
If you should have any questions, please do not hesitate to contact Paul Mays with the Water Quality
Regional Operations Section in the Washington Regional Office at 252-948-3940 or via email at
paul. mays@ncdenr.gov.
ATTACHMENTS
Cc: Laserfiche
Sincerely,
Paul Mays, Environmental Specialist 1
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
eo Cff t N _ a+t _ p s l t fl ±. p q ri t± }.ga�ifw 34o ussn .;t ..ar_ha IH s gto.. 4±nt as. ^a PSSP,
Division of Water Resources
July 7, 2020
MEMORANDUM
To: David May
Water Quality Regional Operations, WaRO
Through: Cindy A. Moore (',—
Supervisor, Aquatic Toxicology Branch (ATB)
From: Lorimar S. Henning AH
Environmental Specialist Il, Aquatic Toxicology Branch (ATB)
Subject: Whole effluent toxicity test results
New Bern WWTP
NPDES Permit # NCO025348/001
Craven County
The aquatic toxicity test using a composite sample of effluent discharged from the New Bern
WWTP has been completed. New Bern WWTP has a permitted effluent discharge of 7.0 million
gallons per day (MGD) entering Neuse River. Whole effluent samples were collected on June 23
by Robbie Bullock for use in an acute Mysidopsis bahia pass -fail toxicity test. The test using
these samples resulted in a pass. Toxicity test information follows.
Test Type
Test Concentration
Test Result
Control Survival
Test Treatment Survival
Sample pH
Sample Conductivity
Sample Total Residual Chlorine
Acute 24-hour Mysidopsis bahia pass -fail
90%
Pass
100%
100%
8.28 SU
37,700 micromhos/cm
<0.1 mg/L
Test results for the above sample indicate that the effluent would not be predicted to have water
quality impacts on receiving water. Please contact us if you have any questions or if further effluent
toxicity monitoring is desired. We may be reached at (919) 743-8401.
Basin: Neuse River
cc: Robbie Bullock (WaRO)
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 le I 3 I NCo025348 I11 121 20/06/23 117 181Q1 191 a 201 I
21111111111111111111111111111111111111111111 f6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
72 ti 731 174 7 I I I I I80
67L --------- - 1 701L, J 1 711n liL -1 I I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Dale
POTW name and NPDES oermit Number)
10:OOAM 20/06/23
13/12/01
New Bern WWTP
307 Glenburnie Dr
Exit Time/Date
Permit Expiration Date
New Bern NC 28560
11:30AM 20/06/23
18/06/30
Name(s) of Onsite Representative(s)Rtles(s)/Phone and Fax Number(s)
Other Facility Data
///
Tony Randall Hawkins/ORC/252-639-7556/
Name, Address of Responsible OfficialMtle/Phone and Fax Number
Contacted
Walter B Hartman,PO Box 1129 New Bern NC 285631129/City
Manager/252-636-4014/2526361848 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Sludge Handling Dispo: 0 Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Robert E Bullock DWR/Division of Water Quality/252-948-3924/
Paul M Mays DWRNVARO WQ/252-948-3940/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO025348 I11 12I 20/06/23 17 18 1 o I
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 6/23/2020 at 10:OOam Paul Mays and Robbie Bullock from the Washington Regional Office
conducted a Bioassay Compliance Inspection of New Bern WWTP.
All required records and documents were examined for compliance of permit #NC0025348. February
2020 DMR and corresponding lab data was reviewed by Paul Mays. No discrepancies were found
between the lab data and data reported on the DMR. The DMR was complete, all required the data wa:
present and reported at the frequency required by permit #NC0025348. The ORC visitation log, annual
compliance report and a copy of the permit were also readily available for review. The staff were very
helpful and provided all the required documents, records, and data for the inspection.
The facility was well kept and clean. All units were operational and well maintained by staff. The only
possible concern were some grease particles present in the secondary clarifiers during the inspection.
Regardless, the effluent looked good and no major issues were found.
Effluent and Influent Flow Meters were calibrated on 8/20/2019
The permit expired Jun 30, 2018 and a new one is currently in draft
The facility passed the toxicity test.
The facility was found to be compliant with permit #NC0025348
Page#
Permit: NCO025348
Inspection Date: 06/23/2020
Owner - Facility: New Bem WWTP
Inspection Type: Bioassay Compliance
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Facility was clean and grounds were well maintained.
Record Keeping
Yes
No
NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
0
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc 0 ❑ ❑ ❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Page# 3
Perrnit: NCO025348 Owner -Facility: New Bern WWTP
Inspection Date: 06/23/2020 Inspection Type: Bioassay Compliance
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? 0 ❑ ❑ ❑
Comment: Feb 2020 DMR was reviewed with corresponding lab data. No discrepancies were found
between lab data and DMR. Additionally, all data on the DMR was reported at the frequency
required by the permit. All required documents/records were readily available for review and
well maintained.
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Influent Meter was calibrated 08/20/2019
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
Yes No NA NE
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Influent sampler is flow proportional and temperature was set to 3 degrees Celsius.
Bar Screens
Yes
No
NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
N
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Page# 4
Permit: NCO025348 Owner -Facility: New Bern WWTP
Inspection Date: 06/23/2020 Inspection Type: Bioassay Compliance
Grit Removal Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
0
❑
❑
❑
Is the grit free of excessive odor?
IN
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment: Dumpster disposal three times a week.
Oxidation Ditches
Yes
No
NA
NE
Are the aerators operational?
0
❑
❑
❑
Are the aerators free of excessive solids build up?
■
❑
❑
❑
# Is the foam the proper color for the treatment process?
M
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
M
❑
❑
❑
Are settleometer results acceptable (> 30 minutes)?
❑
❑
❑
0
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
N
❑
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
❑
❑
❑
Comment: Anoxic zone was 0.26 ppm and Aeration Basin was 1.25 ppm. Probes automatically operate
aerators to maintain DO levels through SCADA.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin Floc?
Is the sludge blanket level acceptable? (Approximately Y. of the sidewall depth)
I[�: C7: L•�:I d
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
Comment: The effluent looks good and the clarifier was in good working condition. However, some
grease particles were present. Sludge judge showed 3ft of sludge.
Page# 5
Permit: NCO025348 Owner -Facility: New Bern WwTP
Inspection Date: 06/23/2020 Inspection Type: Bioassay Compliance
Secondary Clarifier
Yes
No
NA
NE
Standby Power
Yes
No
NA
NE
Is automatically activated standby power available?
E
❑
❑
❑
Is the generator tested by interrupting primary power source?
0
❑
❑
❑
Is the generator tested under load?
0
❑
❑
❑
Was generator tested & operational during the inspection?
❑
❑
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
0
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
N
❑
❑
❑
Is the generator fuel level monitored?
0
❑
❑
❑
Comment
Sand Filters (Low rate)
Yes
No
NA
NE
(If pumps are used) Is an audible and visible alarm Present and operational?
0
❑
❑
❑
Is the distribution box level and watertight?
IN
❑
❑
❑
Is sand filter free of ponding?
N
❑
❑
❑
Is the sand filter effluent re -circulated at a valid ratio?
❑
❑
0
❑
# Is the sand filter surface free of algae or excessive vegetation?
0
❑
❑
❑
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
❑
❑
0
❑
Comment
Flow Measurement- Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: Flow Meter was calibrated on 8/20/2019
Effluent sampler is flow proportional and temperature was set to 3 degrees Celsius.
De -chlorination
Yes No
NA
NE
Type of system ?
Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
N ❑
❑
❑
Is storage appropriate for cylinders?
0 ❑
❑
❑
# Is de -chlorination substance stored away from chlorine containers?
0 ❑
❑
❑
Page# 6
Permit: NC0025348 Owner - Facility:
Inspection Date: 06/23/2020 Inspection Type:
New Bern WWTP
Bioassay compliance
De -chlorination
Yes
No
NA NE
Are the tablets the proper size and type?
❑
❑
0 ❑
Comment: Sodium bisulfate is used for de -chlorination.
Are tablet de -chlorinators operational?
❑
❑
0 ❑
Number of tubes in use?
Comment:
Disinfection -Liquid
Yes
No
NA
NE
Is there adequate reserve supply of disinfectant?
M
❑
❑
❑
(Sodium Hypochlorite) Is pump feed system operational?
0
❑
❑
❑
Is bulk storage tank containment area adequate? (free of leaks/open drains)
0
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment:
Pumps-RAS-WAS
Yes
No
NA
NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
■
❑
❑
❑
Comment
Solids Handling Equipment
Yes
No
NA NE
Is the equipment operational?
M
❑
❑
❑
Is the chemical feed equipment operational?
M
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
M
❑
❑
❑
Is the site free of sludge buildup on belts and/or rollers of filter press?
0
❑
❑
❑
Is the site free of excessive moisture in belt filter press sludge cake?
M
❑
❑
❑
The facility has an approved sludge management plan?
❑
❑
❑
0
Comment:
Page# 7