HomeMy WebLinkAboutNC0000396_Compliance Evaluation Inspection_20200625 (2)DocuSign Envelope ID: 923D92A1-05C2-4619-BC96-5ACE9142E8D8
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 u 3 I NC0000396 111 121 20/06/11 I17 18 LB] 19 I s I 201
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
70 J 71 L72 Ln73 74 79 I I I I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
07:OOAM 20/06/11
20/05/01
Asheville Steam Electric Power Plant
46 Duke Energy Ln
Exit Time/Date
Permit Expiration Date
Arden NC 28704
11:OOAM 20/06/11
23/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Mariea H Keezel/ORC/541-498-2662/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
William A Phipps,200 Cp L Dr Arden NC 28704//828-687-5201/8286875204
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Facility Site Review
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim DWR/ARO WQ/828-296-4665/
6/2 5/2020
D11u3lg1e1 by:
1w,ai lkum
E08281105A3GA418...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
D Sg tlb
6/25/2020
C
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 923D92A1-05C2-4619-BC96-5ACE9142E8D8
NPDES yr/mo/day Inspection Type (Cont.)
NC0000396 I11 12I 20/06/11 117 18 IBI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim performed a Bioassay Compliance Inspection on June 9 and June 11, 2020 at the Duke
Energy Asheville facility. Also present were Theresa Williams (Duke EHS Professional, BORC), Maria
Keezel (Duke ORC) and Matthew Fields (Anchor QEA, BORC). Split sampling was performed for the
chronic Ceriodaphnia dubia multiple -dilution toxicity test. The aquatic toxicity test grab samples were
taken from the stilling pond that discharges to Outfall 001 on the French Broad River. Toxicity test
resulted in a pass, and test information is as follows.
Test Type 3-Brood Ceriodaphnia dubia chronic pass -fail
Test Results Pass
Test Concentrations 1.8%
Control Survival 100%
Control Mean Reproduction 20.92 neonates
Test Treatment Survival 91.7%
Treatment Mean Reproduction 20.82 neonates
First Sample pH 8.44 SU
First Sample Conductivity767 micromhos/cm
First Sample TRC <0.1 mg/L
Second Sample pH 8.03 SU
Second Sample Conductivity 831 micromhos/cm
Second Sample TRC 0.12 mg/L
Test results for the above samples indicate that the effluent would not be predicted to have water
quality impacts on the receiving water. These samples were split and sent to Environmental Testing
Solutions, Inc. The test performed by ETS also resulted in a pass. No violations of permit
requirements or applicable regulations were observed during this inspection.
Page#
DocuSign Envelope ID: 923D92A1-05C2-4619-BC96-5ACE9142E8D8
Permit: NC0000396
Inspection Date: 06/11/2020
Owner -Facility: Asheville Steam Electric Power Plant
Inspection Type: Bioassay Compliance
Yes No NA NE
Page#