HomeMy WebLinkAboutNCS000581_MONITORING INFO_20190214ZTcJO
STORMWATER DIVISION CODING SHEET
NCS PERMITS
PERMIT NO.
NO 000
DOC TYPE
El FINAL PERMIT
MONITORING REPORTS
❑ APPLICATION
❑ COMPLIANCE
❑ OTHER
DOC DATE
0 � D I "I U�) I v
YYYYMMDD
(� DUKE
ENERGY®
ROGRESS
File: 12520 R
NC Division of Environmental Management
Division of Water Quality
ATTENTION: Central Files
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
Duke Energy Progress, LLC
Roxboro Stearn Electric Plant
1700 Dunrumay Road
Serwra, NC 27343
February 6, 2019
FES 14CENNzQ,�
0" 3scTloly
oN
Subject: Roxboro Steam Electric Generating Plant
National Pollutant Discharge Elimination System (NPDES) Number NCS000581
Stormwater Discharge Monitoring Report
Dear Sir or Madam:
In accordance with the NPDES Permit Number NCS000581 concerning the subject facility,
enclosed is the Quarterly Stormwater Discharge report for Duke Energy Progress, LLC. for the I `
monitoring period.
I certify, lender penalty of'law, that this document and all attachments were prepared raider my
direction or supervision in accordance with a system designed to assure that qualified personnel
properly gather- and evaluate the information submitted. Based on my inquiry of the person or
persons who manage the system, or those persons directly responsible for gathering the
lnfoi"matlon, the information submitted is, to the best of my knowledge and belief, true, accurate,
and complete. I am aware that there are significant penalties for submitting false information,
including the possibility of fines and irnprisornnent for kno►ving violations.
Please contact Ms. Lori Tollie at (336) 854-4916, if there are any questions. concerning the data in
this submittal.
Sincerely,
Jason Haynes- Manager
Roxboro Steam Electric Generating Plant
Enclosures
STORMWATER DISCHARGE OUTFALL (SDO)
MONITORING REPORT
Permit Number: NCS000581 SAMPLES COLLECTED DURING CALENDAR YEAR: _2019_
(This monitoring report shall be received by the Division no later than 30 days from
the date the facility receives the sampling results from the laboratory.)
FACILITY NAME Roxboro Electric Steam Plant
PERSON COLLECTING SAMPLE(S) Amber Sarver
CERTIFIED LABORATORY(S) Duke Analytical Lab Lab #_248
Roxboro Steam Electric Plant Lab
Part A: Specific Monitoring Requirements
COUNTY Person
PHONE NO. (336) 597-6100
SIGNATURE OF PERMITTEE OR DESIGNEE
REQUIRED ON PAGE 3.
Outfall
No.
Date
Sample Collected
00400
01119
00981
71901
01092
00530
Total
Rainfall"
pH3
Copper'
Total
Selenium
Total
Mercuryz
Total
Zinc'
Total
TSS
Non -Polar
Oil & Grease
mo/dd/ r
inches
Standard
m
m
m
m
MgA
m
Benchmark
6-9
0.010
0.056
N/A=
0.126
100
15
SW -A
1/3/2019
0.4
6.82
0.00759
<0.001
0.0000033
0.020
<5
<5
Outfall
Additional
Priority Pollutant Metals
00999
01079
00978
00998
01113
01118
01074
01114
01268
00982
No.
Boron$
Agt
As
Be
Cd'
Cr'
NO
Pb'
Sb
TI'
mg/I
mg/I
mg/1
mg/I
mg/I
mg/I
mg/1
mg/l
mg/I
mg/1
Benchmark
NIA(monitor only)
0.0003
0.34
0.065
0.003
0.9
0.335
0.075
0.09
N/A(monitor only)
SW -A
<0.05
<0.0002
<0.001
<0.001
<0.001
<0.001
0.00677
<0.001
<0.001
<0.0002
Footnotes: Permit # NCS000580 (Part 1I-Page 7 of 15)
4. For each sampled measureable storm event, the total precipitation must be recorded. An on -site rain gauge
Form SWU-247, last revised 21212012
Page I of 3
is required. Where isolated sites are unmanned for extended periods of time, a local rain gauge reading
may be substituted for an on -site reading.
5. These parameters shall be monitored only if coal or coal ash is transported through the drainage
areas of these outfalls during the semi-annual monitoring period in Table 2.
Footnotes : Permit # NCS000580 ( Part 11 Page 9 of 15 )
1. Hardness- dependent Benchmark based on translation of dissolved value into total recoverable with
an assumed hardness of 25 mg/1 and a total suspended solids (TSS) concentration of 10 mg/l.
2. Values above the North Carolina water quality standard for mercury (12 ng/l) should be noted on the
DM R but do not trigger Tier responses. Concentrations infield blanks or method blanks associated
with the sample may he subtracted from the results for that sample, as long as all documentation of the
adjustment is provided with the DMR.
3. If pH values outside this range are recorded in sampled stormwater discharges, but ambient
precipitation pH levels are lower, then the lower threshold of this benchmark range is the pH of the
precipitation (within instrument accuracy) instead of 6 S.U. Readings from an on -site or local rain
gauge (or local precipitation data) must be documented to demonstrate background concentrations
were below the benchmark pH range of 6- 9.
Does this facility perform Vehicle Maintenance Activities using more than 55 gallons of new motor oil per month? _yes X no
(if yes, complete Part B)
Part B: Vehicle Maintenance Activity Monitoring Requirements
Outfall
No.
Date
Sample
Collected
50050
00556
00530
00400
Total Flow
(if applicable)
Total
Rainfall
Oil & Grease
(if appl.)
Non -polar
O&GITPH
(Method 1664
SGT-HEM), if
appl.
Total
Suspended
Solids
pH
New Motor
Oil Usage
mo/dd/ r
MG
inches
m
mgA
unit
aUmo
Form SWU-247, last revised 21212012
Page 2 of' 3
STORM EVENT CHARACTERISTICS:
Date _11312019
Total Event Precipitation (inches): 0.4
Event Duration (hours): 6 (only if applicable — see permit.)
(if more than one storm event was sampled)
Date
Total Event Precipitation (inches):
Event Duration (hours): (only if applicable — see permit.)
Mail Original and one copy to:
Division of Water Quality
Attn: Central Files
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
"1 certify, under penalty of law, that this document and all attachments were prepared under my direction or supervision in accordance with a
system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person
or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the
best of my knowledge and belief, true, accurate, and complete. 1 am aware that there are significant penalties for submitting false information,
including the possibility of fines and imprisonment for knowing violations."
/ �—{I
(Date)
Form SWU-247. last remised 2/22012