HomeMy WebLinkAboutWQ0038695_NOV-2020-LM-0051_20200527ROY COOPER
Govemor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
Jeff Malarney
OBX Waterpark Adventure, LLC
13 Green Mountain
Cohoes, NY 12047
SUBJECT: NOTICE OF VIOLATION
NORTH CAROLINA
Environmental Quality
May 27, 2020
Tracking Number: NOV-2020-LM-0051
Permit No. WQ0038695
OBX Waterpark Adventure WWTP
Currituck County
Dear Mr. Malarney:
A review of the July 2019 Non -Discharge Monitoring Report (NDMR) for the subject facility revealed the
violation(s) indicated below:
Limit Exceedance Violation(s):
Sample Limit Reported
Location Parameter Date Value Value Type of Violation
001
BOD, 5-Day (20 Deg. C)
7/31/2019
10
21.5
Monthly Average Exceeded
(00310)
001
Coliform, Fecal MF, MFC Broth,
7/31/2019
14
1,097.77
Monthly Geometric Mean Exceeded
44.5 C (31616)
001
Nitrogen, Ammonia Total (as
7/31/2019
4
79.3
Monthly Average Exceeded
N) (00610)
001
Nitrogen, Total (as N) (00600)
7/31/2019
4
95.41
Monthly Average Exceeded
001
Phosphorus, Total (as P)
7/31/2019
2
9.86
Monthly Average Exceeded
(00665)
No rth Cam line Uepsft ent of Environmental Quality I Division of Water Resources
Washington Regional Off 1 943 Washington Square MMI I Washington, North Csm!ins 27339
k 252$46-643J.
Limit Exceedance Violation(s):
Sample
Limit Reported
Location
Parameter
Date
Value Value
Type of Violation
001
Solids, Total Suspended 7/31/2019
15 31.4
Monthly Average Exceeded
(00530)
Monitoring Violation(s):
Sample
Monitoring
Location
Parameter
Date
Frequency
Type of Violation
001
Flow, in conduit or thru treatment
7/1/2019
Continuous
Frequency Violation
plant (50050)
001
Flow, in conduit or thru treatment
7/2/2019
Continuous
Frequency Violation
plant (50050)
001
Flow, in conduit or thru treatment
7/9/2019
Continuous
Frequency Violation
plant (50050)
001
Flow, in conduit or thru treatment
7/16/2019
Continuous
Frequency Violation
plant (50050)
001
Flow, in conduit or thru treatment
7/22/2019
Continuous
Frequency Violation
plant (50050)
001
Flow, in conduit or thru treatment
7/23/2019
Continuous
Frequency Violation
plant (50050)
001
Flow, in conduit or thru treatment
7/30/2019
Continuous
Frequency Violation
plant (50050)
001
Flow, in conduit or thru treatment
7/31/2019
Continuous
Frequency Violation
plant (50050)
Remedial actions, if not already implemented, should be taken to correct any noted problems. The Division of
Water Resources may pursue enforcement actions for this and any additional violations. If the violations are of a
continuing nature, not related to operation and/or maintenance problems, and you anticipate remedial
construction activities, then you may wish to consider applying for a Special Order by Consent (SOC).
If you have any of the frequency violation/parameter missing documentation to report, please make the necessary
revisions (write revisions on the front page) to the original Non -Discharge Monitoring Report (NDMR) and return
the form(s) by email t0 Non-Discharge.Reports(a)_ncdenr.gov.
No rth Cam line Uepsft ent of Environmental Quslily I Division of Water Resources
Washington Regions) 4f :oe 1943 Washington Square MMI I Washington, North Cam!ins 27339
k 252$46-6431
If you have any questions concerning this matter or to apply for an SOC, please contact Sarah Toppen of the
Washington Regional Office at 252-948-3845.
Sincerely,
IzTl
Robert Tankard, Assistant Regional Supervisor
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
Cc: Laserfiche
No rth Cam line Uepsft ent of Environmental Quslily I Division of Water Resources
Washington Regions) 4f :oe 1943 Washington Square MMJ I Washington, North Cam!ins 27339
k 252$46-6431