HomeMy WebLinkAboutNC0029980_Regional Office Historical File Pre 2016AT
NCDENR
North Carolina Department of Environment and Natural Resources
Pat McCrory Donald van der Vaart
Governor Secretary
August 11, 2015
Mr. James A. Smith, V.P.
MillerCoors, LLC
863 East Meadow Road
Eden, NC 27288-3636
SUBJECT: Compliance Evaluation Inspection
MillerCoors WWTP — Eden, NC
NPDES Permit No. NCO029980
Rockingham County
Dear Mr. Smith:
On August 6, 2015, Lon Snider of this office, met with Matt Toms to perform a Compliance
Evaluation Inspection of the NPDES wastewater discharge from the MillerCoors industrial
Wastewater Treatment Plant located in Eden, NC. The treatment system was found to be compliant
with all effluent limits and monitoring requirements of the NPDES permit. The inspection findings
are detailed below and an inspection checklist is attached for your records.
I. Permit
The current NPDES permit expires on April 30, 2017. Please note that upon renewal, it is expected
that the permit will require MillerCoors to begin submitting monthly self -monitoring reports
(DMRs) electronically per the new EPA rule which mandates NPDES permittees to electronically
submit DMRs. Information on the eDMR process along with the eDMR Registration form can be
found at the following link: http://portal.ncdenr.org/web/wq/admin/bog/ipu/edmr.
II. Self-Monitorina Proaram
The monthly DMRs were reviewed for the period July 2014 through April 2015. The facility was
found to be in compliance with all effluent permit limits. In regards to the permit monitoring
requirements, it was noted that all sampling was being performed per the frequencies specified in
the permit.
III. Flow Measurement
The NPDES permit requires continuous flow recording as well as an annual calibration of the flow
measuring device. The daily effluent flow values reported on the DMRs are measured using an
ultrasonic flow meter with parshall flume. The meter was last calibrated by MillerCoors staff on
June 29, 2015. Additionally, it was noted that flow proportional composite effluent samples are
collected per Part II, Section A of the permit.
450 West Hanes Mill Road, Suite 300, Winston-Salem, NC 27105
Phone: 336-776-9800 \ Internet: www.ncwatercluality.org
An Equal Opportunity \ Affirmative Action Employer — Made in part by recycled paper
Mr. Smith
MillerCoors
Page 2 of 2
IV. Sludge Handling and Disposal
Solids handling consists of two aerobic digesters and a belt press. The dewatered residuals are
distributed under non -discharge permit No. WQ0001347 issued by the Division of Water
Resources.
V. Operations and Maintenance
The facility was well operated and maintained. No problems pertaining to O&M were noted.
VI. Facility Site Review
The existing 5.2 MGD treatment system consists of the following components: influent screw type
lift station, manual bar screen, grit chamber, aeration basins, secondary clarifiers, polishing lagoons,
effluent pump station and effluent flow meter. Please refer to the attached inspection checklist for
specific comments on each system component.
NIL Records/Reports
A comparison of the November and December 2014 DMRs with the corresponding laboratory
results from Meritech indicated that the values were transcribed correctly. The operator's records
for pH, dissolved oxygen and temperature values measured on -site were also checked.
VHI. Effluent/Receiving Waters
The system discharges into the Dan River, class "C" waters in the Roanoke River Basin. The
effluent discharge is submerged in the river and could not be observed.
Our office appreciates the conscientious effort by MillerCoors staff to comply with the
NPDES permit. Should you have any questions concerning this report, please contact Lon Snider or
me at (336) 776-9800.
Sincerely,
Sherri V. Knight, PE
Assistant Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources
cc: Central Files
WSRO
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO029980 I11 12 15/08/06 17 18 L,j 19 I c I 201 I
211111 1 1 I I I I II 111I I I I I I I I I I I I I I I I I I I I II I I I I I �6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 CIA — — — —Reserved-----------
67 70 � I 71 � 72 73 L L74 75 LLj80
L� L� I I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:45AM 15/08/06
12/06/01
MillerCoors LLC
Exit Time/Date
Permit Expiration Date
863 E Meadow Rd "
11:15AM 15/08/06
17/04/30
Eden NC 272883636
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Matthew Stuart Toms/ORC/336-627-1009/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Eric G Tillman,863 E Meadow Rd Eden NC 27288JEH & S
No
Representative/336-627-2136/
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement E Operations 8 Maintenance Records/Reports
Self -Monitoring Program 0 Sludge Handling Disposal N Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Lon Snider WSRO WQ//336-776-9701/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type 1
31 NCO029980 I11 121 15ro8/06 I17 18 I'
Section D: Summary of Finding/Comments (Attach additionalsheetsof narrative and checklists as necessary)
Page#
Permit: NCO029980 Owner -Facility: MillerCoors LLC
Inspection Date: 08/0612015 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
Yes No
NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The current permit expires April 30, 2017.
Facility only treats industrial wastewater.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
M
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Facility has a field certification #5107 for on site testing of DO PH and temp. All other
parameters are analyzed by Meritech Labs.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
M
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Page# 3
Permit: NCO029980
Inspection Date: 08/06/2015
Owner -Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Record Keepinq
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ M ❑
Comment: Comparison of the November & December 2014 DMR data with the lab and operators
records showed no transcription errors.
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
❑
❑
0
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
❑
0
Comment: There are 2 screw pumps. It only takes one to handle the incoming flow. Permitte is looking
at upgrading this to pumps in the future.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
M
❑
❑
❑
Is the screen free of excessive debris?
M
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
M
❑
❑
❑
Page# 4
Permit: NCO029980 Owner -Facility: MillerCoors LLC
Inspection Date: 08/06/2015 Inspection Type: Compliance Evaluation
Bar Screens Yes No NA NE
Comment:
Grit Removal
Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
❑ ❑ ❑
Is the grit free of excessive odor?
0
❑ ❑ ❑
# Is disposal of grit in compliance?
N
❑ ❑ ❑
Comment:
Aeration Basins
Yes
No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
E
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
0
❑
Are the diffusers operational?
E
❑
❑
❑
Is the foam the proper color for the treatment process?
S
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
0
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
N
Comment:
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
E
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
E
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
S
❑
❑
❑
Is the site free of excessive floating sludge?
N
❑
❑
❑
Is the drive unit operational?
N
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Page# 5
Permit: NCO029980 Owner -Facility: MillerCoors LLC
Inspection Date: 08/06/2015 Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth) 0 ❑ ❑ ❑
Comment: Two out of the four clarifiers were in service.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
❑
❑
❑
Comment:
Solids Handlinq Equipment
Yes No NA NE
Is the equipment operational?
0
❑
❑
❑
Is the chemical feed equipment operational?
0
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
0
❑
❑
❑
Is the site free of sludge buildup on belts and/or rollers of filter press?
M
❑
❑
❑
Is the site free of excessive moisture in belt filter press sludge cake?
N
❑
❑
❑
The facility has an approved sludge management plan?
0
❑
❑
❑
Comment: Single belt press for dewaterin
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
N
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: Temp on sampler was 4.6 C
Flow Measurement - Effluent Yes No NA NE
Page# 6
Permit: NCO029980
Inspection Date: 08/06/2015
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
Owner -Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑
Comment: The flow meter is calibrated by MillerCoors staff. Last calibration was conducted on June 29
2015.
Lagoons Yes No NA NE
Type of lagoons? Facultative
# Number of lagoons in operation at time of visit? Z
Are lagoons operated in?
Series
# Is a re -circulation line present?
❑
M
❑
❑
Is lagoon free of excessive floating materials?
M
❑
❑
❑
# Are baffles between ponds or effluent baffles adjustable?
❑
❑
M
❑
Are dike slopes clear of woody vegetation?
M
❑
❑
❑
Are weeds controlled around the edge of the lagoon?
M
❑
❑
❑
Are dikes free of seepage?
M
❑
❑
❑
Are dikes free of erosion?
0
❑
❑
❑
Are dikes free of burrowing animals?
M
❑
❑
❑
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple
M
❑
❑
❑
locations?
# If excessive algae is present, has barley straw been used to help control the growth?
M
❑
❑
❑
Is the lagoon surface free of weeds?
M
❑
❑
❑
Is the lagoon free of short circuiting?
M
❑
❑
❑
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ❑
Comment: The effluint pipe is a submerged pipe in the Dan River.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and M ❑ ❑ ❑
sampling location)?
Page# 7
Permit: NC0029980
Inspection Date: 08/06/2015
Upstream / Downstream Samplinq
Owner -Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: Permittee only conducts upstream and downstream sampling during the months of June
July, August and September.
Page#
NCDENR
North Carolina Department of Environment and Natural Resources
Pat McCrory
Governor
May 23, 2014
Mr. James A. Smith, V.P.
MillerCoors, LLC
863 East Meadow Road
Eden, NC 27288-3636
SUBJECT: Compliance Evaluation Inspection
MillerCoors WWTP — Eden, NC
NPDES Permit No. NCO029980
Rockingham County
Dear Mr. Smith:
John E. Skvarla, III
Secretary
On May 21, 2014, Mike Mickey and Lon Snider of this office, along with Louis Salguero
from EPA, met with Matt Toms, Rodney Isley and Drew Lucas to perform a Compliance Evaluation
Inspection of the NPDES wastewater discharge from the MillerCoors industrial Wastewater
Treatment Plant located in Eden, NC. The treatment system was found to be compliant with all
effluent limits and monitoring requirements of the NPDES permit. The inspection findings are
detailed below and an inspection checklist is attached for your records.
I. Permit
The current NPDES permit expires on April 30, 2017. Please note that upon renewal, it is expected
that the permit will require MillerCoors to begin submitting monthly self -monitoring reports
(DMRs) electronically per the new EPA rule which mandates NPDES permittees to electronically
submit DMRs. Information on the eDMR process along with the eDMR Registration form can be
found at the following link: http://portal.ncdenr.org/web/wq/admin/bog/ipu/edmr.
II. Self -Monitoring Program
The monthly DMRs were reviewed for the period April 2013 through March 2014. The facility was
found to be in compliance with all effluent permit limits (see data summary attached). In regards
to the permit monitoring requirements, it was noted that all sampling was being performed per the
frequencies specified in the permit.
III. Flow Measurement
The NPDES permit requires continuous flow recording as well as an annual calibration of the flow
measuring device. The daily effluent flow values reported on the DMRs are measured using an
ultrasonic flow meter with parshall flume. The meter was last calibrated by MillerCoors staff on
April 28, 2014. Additionally, it was noted that flow proportional composite effluent samples are
collected per Part II, Section A of the permit.
N.C. Division of Water Resources
585 Waughtown Street, Winstion-Salem, NC 27107
Phone: 336-771-5000 \ Internet: www.ncwaterquality.org
An Equal Opportunity 1 Affirmative Action Employer — Made in part by recycled paper
Mr. James A. Smith
Page 2
May 23, 2014
IV. Sludge Handling and Disposal
Solids handling consists of two aerobic digesters and a belt press. The dewatered residuals are
distributed under non -discharge permit No. WQ0001347 issued by the Division of Water
Resources.
V. Operations and Maintenance
The facility was well operated and maintained. No problems pertaining to O&M were noted.
VI. Facility Site Review
The existing 5.2 MGD treatment system consists of the following components: influent screw type
lift station, manual bar screen, grit chamber, aeration basins, secondary clarifiers, polishing lagoons,
effluent pump station and effluent flow meter. Please refer to the attached inspection checklist for
specific comments on each system component.
VII. Records/Reports
A comparison of the March 2014 DMR with the corresponding laboratory results from Meritech
indicated that the values were transcribed correctly. The operator's records for pH, dissolved
oxygen and temperature values measured on -site were also checked. With the exception of one
dissolved oxygen value, these values were transcribed correctly onto the DMR. Two dissolved
oxygen values are taken daily and the average is reported on the DMR. On March 30, 2014, the
two effluent dissolved oxygen values were measured as 4.9 and 5.3 mg/L, while an average of 5.4
mg/L was incorrectly reported on the DMR. The remainder of the facility files were found to be
thorough and complete.
VIII. Effluent/Receiving Waters
The system discharges into the Dan River, class "C" waters in the Roanoke River Basin. The
effluent discharge is submerged in the river and could not be observed.
Our office appreciates the conscientious effort by MillerCoors staff to comply with the
NPDES permit. Should you have any questions concerning this report, please contact Mike Mickey
or me at (336) 771-5000.
Sincerely,
Sherri V. Knight, PE
Assistant Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources
cc: Andrew Lucas (via email: Andrew.Lucas@MillerCoors.com)
Louis Salguero/EPA (via email: Salguero.Louis@epa.gov)
Central Files
WSRO
Data Summary
MillerCoors WWTP — Eden, NC
NPDES Permit No. NCO029980
Self -Monitoring Data Summary
April 2013 — March 2014
Parameters
Monthly Avg.
Permit Limit
Monthly Avg. Limit
Violations per DMR
Daily Maximum
Permit Limit
Daily Max. Limit
Violations per DMR
Flow (MGD)
5.2
None
-
NA
BOD (Ibs/day)
1,648
None
3,990
None
TSS (Ibs/day)
2,429
None
5,855
None
NH3-N (mg/L)
-
NA
-
NA
pH (S.U.)
-
NA
(6.0-9.0) range
None
Chronic Toxicity
P/F @ 2.1 %
None
-
NA
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 L2 1�531 NCO029980 111 121 14/05/21 17 18U 19L20L1
Remarks
211111111111111IIIIIIIIIIIIIIIIIIIIIIIIIIIIIII1116
Inspection Work Days Facility Self -Monitoring Evaluation Rating 61 QA — -------Reserved --
6769 70I 5 I 71 U 72 73I '( 74 751 I I I I I I 180
+--' W
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Entry Time/Date
Permit Effective Date
MillerCoors LLC
12:50 PM 14/05/21
12/06/01
Exit Time/Date
Permit Expiration Date
863 E Meadow Rd
Eden NC 272883636
02:50 PM 14/05/21
17/04/30
Name(s) of Onsite Representabve(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
/n
Matthew Stuart Toms/ORC/336-627-1009/
Rodney Lane Isley//336-627-2354 /
Name, Address of Responsible Officialfritle/Phone and Fax Number
Andrew C Lucas,863 E Meadow Rd Eden NC 272883636//336-627-2592/ Contacted
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement . 0 Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Sludge Handling Disposal 0 Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Michael M Mickey WSRO WQ//336-771-4962/
Signature f Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
� y- y
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
11
Or
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 05/21/2014 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
❑ ❑ 0 ❑
Is the facility as described in the permit?
❑ ❑ ❑
# Are there any special conditions for the permit?
❑ ❑ ❑
Is access to the plant site restricted to the general public?
0 ❑ ❑ ❑
Is the inspector granted access to all areas for inspection?
0 ❑ ❑ ❑
Comment: The current NPDES permit expires on April 30, 2017. At renewal it is
expected that the permit will require MillerCoors to submit monthly self -monitoring
reports (DMRs) electronically per the new EPA rule mandating NPDES permittees to
electronically submit DMRs.
As part of this inspection the DMRs for the period April 2013 through March 2014 were
reviewed. The MillerCoors WWTP was found to be compliant with all effluent permit
limits. Additionally, it was noted that all monitoring was performed per the frequencies
specified in the permit.
The WWTP treats industrial wastewater only. All domestic wastewater is routed to the
City of Eden POTW.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ■ ❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? ■ ❑ ❑ ❑
# Is the facility using a contract lab? 0 ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? E ❑ ❑ ❑
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ■ ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ E ❑
Comment: The MillerCoors faciltiy has field parameter certification (#5107) from the
Division for performing on -site testing of dissolved oxygen, pH and temperature. All
other parameters are analyzed by Meritech Labs (#165). As part of the inspection the
facility was asked to conduct a pH calibration, which was performed correctly.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? E ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ ❑ ❑ ❑
Judge, and other that are applicable?
Page # 3
Permit: NCO029980
Owner - Facility: MillerCoors LLC
Inspection Date: 05/21/2014 Inspection Type: Compliance Evaluation
11
Operations & Maintenance Yes No NA NE
Comment: The facility performs daily MLSS, settleability and sludge judge tests for
process control.
The 5.2 MGD industrial wastewater treatment facility consists of the following:
*influent screw lift pumps (2)
*manual bar screen
*grit chamber with mechanical removal
*influent flow meter (ultrasonic w/parshall flume)
*aeration basins (8)
*secondary clarifiers (4)
*polishing lagoons (2)
*sludge handling via aerobic digestors (2), belt filter press (1) and land application
*effluent pump station
*effluent settling basin
*effluent flow meter (ultrasonic w/parshall flume, used for DMR reporting)
Note: Part I.A.(3) of the permit contains a variance from the 24-hour staffing
requirement for facilities >5 MGD. The WWTP is normally staffed 24/7. However, per
the variance, on -site staffing is not required during periods of flow diversion to the 3.2
MGD holding basin (#4 aeration), provided an ORC is on call, the WWTP is checked
every 8 hours and the screw pumps and aeration blowers are monitored by computer.
Record Keeping
Yes
No NA
NE
Are records kept and maintained as required by the permit?
■
❑ ❑
❑
Is all required information readily available, complete and current?
■
❑ ❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑ ❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑ ❑
❑
Is the chain -of -custody complete?
■
❑ ❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑ ❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑ ■
❑
Page # 4
Or
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 05/21/2014 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? ■ ❑ ❑ ❑
Is the ORC visitation log available and current? ■ ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility classification? ■ ❑ ❑ ❑
Is a copy of the current NPDES permit available on site? ■ ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ■ ❑
Comment: A comparison of the March 2014 DMR with the certified laboratory sheets
from Meritech showed that all parameters were accurately transcribed onto the DMR.
The operator's records were also checked for pH, dissolved oxygen (D.O.) and
temperature. Two pH values are taken daily with the highest value reported on the
DMR. Two D.O. values are also taken daily and the average is reported on the DMR.
On March 30, 2014 the two effluent D.O. values were 4.9 and 5.3 mg/L, while an
average of 5.4 mg/L was incorrectly reported on the DMR. Please make sure that the
average D.O. value is reported correctly.
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? ■ ❑ ❑ ❑
Is the wet well free of excessive grease? ■ ❑ ❑ ❑
Are all pumps present? ■ ❑ ❑ ❑
Are all pumps operable? ■ ❑ ❑ ❑
Are float controls operable? ❑ ❑ ■ ❑
Is SCADA telemetry available and operational? ■ ❑ ❑ ❑
Is audible and visual alarm available and operational? ❑ ❑ ❑ ■
Comment: There are two screw pumps that are alternately operated (one can easily
handle the influent flow).
R�r Cnrnnnc Yes No NA NE
Type of bar screen
a.Manual
■
b.Mechanical
❑
Are the bars adequately screening debris?
■
0110
Is the screen free of excessive debris?
■
❑ ❑
❑
Is disposal of screening in compliance?
■
❑ ❑
❑
Is the unit in good condition?
■
❑ ❑
❑
Page # 5
Permit: NCO029980
Inspection Date: 05/21/2014
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
11
Bar Screens
Yes
No NA NE
Comment: The single manual bar screen is raked as needed.
Grit Removal
Yes
No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
■
Is the grit free of excessive organic matter?
■
❑ ❑ ❑
Is the grit free of excessive odor?
■
❑ ❑ ❑
# Is disposal of grit in compliance?
■
❑ ❑ ❑
Comment: There is a single grit chamber with mechanical scrapes. The grit is
augered into the on -site dumpster.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
■
❑ ❑ ❑
Are surface aerators and mixers operational?
❑
❑ ■ ❑
Are the diffusers operational?
■
❑ ❑ ❑
Is the foam the proper color for the treatment process?
■
❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface?
■
❑ ❑ ❑
Is the DO level acceptable?
❑
❑ ❑ ■
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑ ❑ ■
Comment: There are eight aeration basins. Basins 6, 7, and 8 were in operation.
Basins 1, 2, and 3 were out of service. Basin 4 is used for emergency diversion and
holding of influent.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
■
❑ ❑ ❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
■
❑ ❑ ❑
Are weirs level?
■
❑ ❑ ❑
Is the site free of weir blockage?
■
❑ ❑ ❑
Is the site free of evidence of short-circuiting?
■
❑ ❑ ❑
Is scum removal adequate?
■
❑ ❑ ❑
Page # 6
Pr
Permit: NCO029980
Inspection Date: 05/21/2014
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Secondary Clarifier
Yes
No
NA NE
Is the site free of excessive floating sludge?
■
❑
❑ ❑
Is the drive unit operational?
■
❑
❑ ❑
Is the return rate acceptable (low turbulence)?
■
❑
❑ ❑
Is the overflow clear of excessive solids/pin floc?
■
❑
❑ ❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
■
❑
❑ ❑
Comment: There are four circular secondary clarifiers. Clarifiers 3 and 4 were in
service. Clarifiers 1 and 2 were out of service.
Aerobic Digester
Yes No
NA
NE
Is the capacity adequate?
■ ❑
❑
❑
Is the mixing adequate?
■ ❑
❑
❑
Is the site free of excessive foaming in the tank?
❑ ❑
❑
■
# Is the odor acceptable?
■ ❑
❑
❑
# Is tankage available for properly waste sludge?
■ ❑
❑
❑
Comment: There are two aerobic digesters at the solids handling building. The facility
holds non -discharge permit No. WQ0001347 for the distribution of "Farm On" waste
products of exceptional quality (503 Exempt).
Solids Handling Equipment
Yes No
NA NE
Is the equipment operational?
■ ❑
❑ ❑
Is the chemical feed equipment operational?
■ ❑
❑ ❑
Is storage adequate?
■ ❑
❑ ❑
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
■ ❑
❑ ❑
Is the site free of sludge buildup on belts and/or rollers of filter press?
■ ❑
❑ ❑
Is the site free of excessive moisture in belt filter press sludge cake?
■ ❑
❑ ❑
The facility has an approved sludge management plan?
■ ❑
❑ ❑
Comment: There is a single belt filter press for dewatering. Polymers are added prior
to the press. Two plate presses are also availble if needed.
Pump Station - Effluent
Yes No
NA NE
Is the pump wet well free of bypass lines or structures?
■ ❑
❑ ❑
Are all pumps present?
■ ❑
❑ ❑
Are all pumps operable?
■ ❑
❑ ❑
Are float controls operable?
■ ❑
❑ ❑
Page # 7
Permit: NCO029980
Inspection Date: 05/21/2014
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Pump Station - Effluent Yes No NA NE
Is SCADA telemetry available and operational? ❑ ❑ ■ ❑
Is audible and visual alarm available and operational? ❑ ❑ ■ ❑
Comment: The effluent pump station has three pumps and is located adjacent to the
polishing lagoons. The effluent is pumped back from the polishing ponds to the settling
basin prior to the parshall flume at the WWTP. The effluent then flows by gravity to the
Dan River.
Effluent Sampling
Yes
No NA NE
Is composite sampling flow proportional?
■
❑ ❑ ❑
Is sample collected below all treatment units?
■
❑ ❑ ❑
Is proper volume collected?
■
❑ ❑ ❑
Is the tubing clean?
❑
❑ M ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
■
❑ ❑ ❑
Is the facility sampling performed as required by the permit (frequency, sampling type representative)?
■
❑ ❑ ❑
Comment: The facility uses a flow through dipper -type refrigerated composite
sampler. Flow proportional composite samples are collected. The refrigeration
temperature was 1.6 degrees centigrade.
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
■
❑ ❑ ❑
Is flow meter calibrated annually?
■
❑ ❑ ❑
Is the flow meter operational?
■
❑ ❑ ❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑ ■ ❑
Comment: Effluent flows are reported on the DMR using an ultrasonic meter with
parshall flume. The meter was last calibrated by MillerCoors staff on April 28, 2014.
Lagoons
Yes No NA NE
Type of lagoons?
Facultative
# Number of lagoons in operation at time of visit?
2
Are lagoons operated in?
Series
# Is a re -circulation line present?
❑
■ ❑ ❑
Is lagoon free of excessive floating materials?
■
❑ ❑ ❑
# Are baffles between ponds or effluent baffles adjustable?
❑
❑ ■ ❑
Are dike slopes clear of woody vegetation?
■
❑ ❑ ❑
'41
Page # 8
Or
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 05/2112014 Inspection Type: Compliance Evaluation
Lagoons
Yes No
NA
NE
Are weeds controlled around the edge of the lagoon?
0
O
0
O
Are dikes free of seepage?
0
❑
0
Are dikes free of erosion?
O
0
O
Are dikes free of burrowing animals?
0
0
0
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations?
0
Q
0
Q
# If excessive algae is present, has barley straw been used to help control the growth?
■
❑
0
Q
Is the lagoon surface free of weeds?
M
0
0
Is the lagoon free of short circuiting?
M
0
0
Q
Comment: The two lagoons (approx 4.8 acres each) are operated in series. Barley
straw is used in an attempt to control algae.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? ❑ 0 ❑ 0
Are the receiving water free of foam other than trace amounts and other debris? 0 O 0 0
If effluent (diffuser pipes are required) are they operating properly? ❑ 0 O 0
Comment: The effluent is discharged into the Dan River, class "C' waters in the
Roanoke River Basin. The effluent pipe is submerged and is not easily accessible.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? ■ 0 0 0
Comment: The permit requires instream monitoring for temperature and dissolved
oxygen in the Dan River during June, July, August and September. The upstream
sampling location is at the Hwy 14 bridge and the downstream sampling location is at
Hwy 700 bridge.
Page # 9
ppppppp,
Mickey, Mike
From: Mickey, Mike
Sent: Friday, May 23, 2014 1:11 PM
To: Isalguero.louis@epa.gov'
Subject: MillerCoors NPDES Insp Letter - NCO029980
Attachments: NJ_#5107_09_2013_FINAL.pdf; s165.06-f.doc; MillerCoors Inspection - NC0029980.pdf
Louis — Per your request, please find the NPDES inspection letter for MillerCoors attached. Additionally, please see the
email below regarding your question about laboratory inspections/data review. The other two attachments pertain to
lab inspections. If you have any laboratory questions, you can contact either Gary Francies or Dana Satterwhite. Their
contact information is listed in their respective emails that follow. Thanks, Mike.
Mike Mickey
Mike. MickevPNCDENR.eov
NC Division of Water Resources
585 Waughtown Street
Winston-Salem, NC 27107
Phone: (336) 771-4962
FAX: (336) 771-4630
From: Francies, Gary
Sent: Friday, May 23, 2014 11:00 AM
To: Mickey, Mike
Cc: Satterwhite, Dana
Subject: RE: MillerCoors / NCO029980
Mike
Dana asked me to follow up with you regarding your questions. Attached are the two last inspection reports you
requested. We are currently in the process of auditing Meritech right now — we were there on May 20rh and are
returning to finish the audit on Wednesday the 28`h. If you or EPA would like a copy of that report when it is completed
let us know and we can send it.
Regarding our paper trail process — when we perform an inspection at a facility like Miller/Coors we do not also travel to
the contract lab (Meritech) to review bench sheets. We do not have the staff levels that would allow us to do that. I
know that was done back in the day with the old Performance Audit Inspections (PAI) that we were sometimes asked to
assist Water Quality folks with, but it is not a routine part of a laboratory inspection and we have not had a request for
assistance in performing a PAI in years. We look at it like we are there to inspect that particular lab and that lab's
contract lab will be inspected independently .As you can see from the interval between inspections we are struggling to
keep our heads above water with inspection frequencies due to all the positions we have lost so that would be next to
impossible to incorporate into a routine laboratory inspection.
What we do at all facilities (not commercial labs) is review three random DMRs and we follow all the data points
produced by that lab (Miller/Coors) back to the bench sheets and the data from the contract lab (Meritech) we compare
the client report form from Meritech to the DMR and look for transcription errors etc. If we see something that raises a
major red flag we would follow up with the commercial lab — but not routinely.
When we inspect a commercial lab we try to randomly select a couple client report forms and follow the data back to
the bench sheets if time allows. If we get a request from data receivers — like you folks — or a client (Miller/Coors) to look
at specific data we always do that — usually independently of the normal audit process.
As far as a contact person for EPA — they can contact either me or Dana— contact information for both of us is below in
email string.
I hope that answers your questions — do not hesitate to follow up if you need more information
Hope you have a great holiday weekend
Gary
Gary Francies
gary.francies@ncdenr.gov
TA/Compliance Specialist
NC WW/GW Laboratory Certification
O: (828) 296-4677
F: (828) 299-7043
NC DENR/Division of Water Resources — Water Quality Programs
Water Sciences Section —Asheville Regional Office
2090 U.S. Highway 70
Swannanoa, NC 28778
http://Portal.ncdenr.org/web/wq/lab/cert
From: Satterwhite, Dana
Sent: Thursday, May 22, 2014 9:46 AM
To: Francies, Gary
Subject: FW: MillerCoors / NCO029980
fyi
Dana Satterwhite
dana.satterwhite@ncdenr.gov
Environmental Program Supervisor III
INC WW/GW Laboratory Certification Unit
0: (919) 733-3908 ext. 243
F: (919) 733-6241
NC DENR/Division of Water Resources
Water Sciences Section
1623 Mail Service Center
Raleigh, NC 27699-1623
http://i)ortal.ncdenr.org/web/wq/lab/cert
From: Mickey, Mike
Sent: Thursday, May 22, 2014 8:48 AM
To: Satterwhite, Dana
Subject: MillerCoors / NCO029980
Hi Dana — EPA audited our NPDES inspection process this week. I took them to MillerCoors yesterday for an
inspection. Can you help me with the following questions?
P p
pi) Copy of last Field Certification inspection for Miller (#5107). Miller said they were inspected recently, however, I
did not see an inspection in the intranet portal. Can you send me a copy?
2) Copy of last Meritech Labs (#165) Inspection. Nothing in the intranet portal. Has one been done
recently? Also, EPA wanted to know if the Meritech lab inspection would involve tracing bench data back to
Millers DMR. Is that done during a lab inspection?
3) EPA wanted a contact name in case they had a question about the lab inspection process. Who would that be?
Thanks, Mike.
Mike Mickey
Mike.Mickey@NCDENR.gov
NC Division of Water Resources
585 Waughtown Street
Winston-Salem, NC 27107
Phone: (336) 771-4962
FAX: (336) 771-4630
NGDENR
North Carolina Department of Environment and Natural Resources
Division of Water Resources
Water Quality Programs
Pat McCrory Thomas A. Reeder John E. Skvarla, III
Governor Director Secretary
November 1, 2013
5107
Mr. Drew Lucas
Miller Coors LLC.
863 East Meadow Road
Eden, NC 27288
SUBJECT: North Carolina Wastewater/Groundwater Laboratory Certification (NC WW/GW LC)
Maintenance Inspection
Dear Mr. Lucas:
Enclosed is a report for the inspection performed on September 24, 2013 by Nick Jones. Since
the finding(s) cited during the inspection were all corrected prior to the completion of the
enclosed report, a response is not required. The staff is commended for taking the initiative in
correcting the findings in such a timely manner. For certification maintenance, your laboratory
must continue to carry out the requirements set forth in 15A NCAC 2H .0800.
Copies of the checklists completed during the inspection may be requested from this office.
Thank you for your cooperation during the inspection. If you wish to obtain an electronic copy of
this report by electronic mail, or if you have questions or need additional information please
contact me at (828) 296-4677.
Sincerely,
Gary Francies
Technical Assistance/Compliance Specialist
Laboratory Section
Enclosure
cc: Master file, Nick Jones
DENR DWR WQP Laboratory Section NC Wastewater/Groundwater Laboratory Certification Branch
1623 Mail Service Center, Ralegh, North Carolina 27699-1623
Location: 4405 Reedy Creek Road. Ralegh, North Carolina 27607-6445
Phone: 919-733-39081 FAX: 919-733-6241
Internet: www.dwglab.org
An Equal Opporlunity k Affirmative Action Employer
LABORATORY NAME:
NPDES PERMIT #:
ADDRESS:
CERTIFICATE #:
DATE OF INSPECTION:
TYPE OF INSPECTION:
AUDITOR(S):
LOCAL PERSON(S) CONTACTED:
I. INTRODUCTION:
On -Site Inspection Report
Miller Coors LLC.
NCO029980
863 East Meadow Road
Eden, NC 27288
5107
September 24, 2013
Field Maintenance
Nick Jones
Drew Lucas
This laboratory was inspected by a representative of the North Carolina
Wastewater/Groundwater Laboratory Certification (NC WW/GW LC) program to verify its
compliance with the requirements of 15A NCAC 2H .0800 for the analysis of
environmental samples.
II. GENERAL COMMENTS:
The laboratory was clean and well organized. The facility has all the equipment necessary
to perform the analyses. Proficiency Testing (PT) samples have been analyzed for all
certified parameters for the 2013 proficiency testing calendar year and the graded results
were 100% acceptable.
Contracted analyses are performed by Meritech, Inc. (Certification #165).
Current quality assurance policies for Field Laboratories and approved procedures for
the analysis of the facility's currently certified parameters were provided at the time of
the inspection.
III. FINDINGS, REQUIREMENTS, COMMENTS AND RECOMMENDATIONS:
Comment: The laboratory needs to increase the documentation of purchased materials
and reagents. The Quality Assurances Policies for Field Laboratories document states: all
chemicals, reagents, standards and consumables used by the laboratory must have the
following information documented: Date Received, Date Opened (in use). Vendor. Lot
Number. and Expiration Date. A system (e.g., traceable identifiers) must be in place that
links standard/reagent preparation information to analytical batches in which the
solutions are used. Documentation of solution preparation must include the analyst's
initials, date of preparation, the volume or weight of standard(s) used, the solvent and
Page 2
#5107 Miller Coors LLC.
final volume of the solution. This information as well as the vendor and/or manufacturer,
lot number, and expiration date must be retained for chemicals, reagents, standards and
consumables used for a period of five years. Consumable materials such as PH buffers
and lots of pre -made standards are included in this requirement. The traceability log
supplied by the auditor during the inspection was implemented by laboratory personnel
before the conclusion of the inspection on 9/24/2013. No further response is
necessary for this finding.
IV. PAPER TRAIL INVESTIGATION:
The paper trail consisted of comparing field testing records and contract lab reports to
Discharge Monitoring Reports (DMRs) submitted to the North Carolina Division of Water
Resources. Data were reviewed for Miller Coors (NC0029980) for June, July and August
2013. No transcription errors were detected. The facility appears to be doing a good job
of accurately transcribing data.
V. CONCLUSIONS:
All findings noted during the inspection were adequately addressed prior to the
completion of this report. The inspector would like to thank the staff for its assistance
during the inspection and data review process. No response is required.
Report prepared by: Nick Jones Date: October 2, 2013
Report reviewed by: Tonja Springer Date: October 28, 2013
Mickey, Mike
From: Belnick, Tom
Sent: Wednesday, May 14, 2014 12:14 PM
To: Weaver, Charles; Mickey, Mike
Cc: Poupart, Jeff; Hennessy, John
Subject: RE: DWR's guidance for "Reduction of Monitoring Frequencies for Exceptionally
Performing Facilities"
Mike- we have not revisited this policy since implementation in late 2012. We wanted to get our feet wet with Major
Municipals, to see how big a workload this will be, and how much staff time it takes. It's something we can take a look
at, though we are presently short-staffed.
Tom Belnick
Supervisor, NPDES Complex Permitting Unit
NCDWR/Water Quality Programs
919-807-6390
E-mail correspondence to and from this address may be subject to the
North Carolina Public Records Law and may be disclosed to third parties
From: Weaver, Charles
Sent: Monday, May 12, 2014 8:25 AM
To: Mickey, Mike
Cc: Belnick, Tom
Subject: RE: DWR's guidance for "Reduction of Monitoring Frequencies for Exceptionally Performing Facilities"
SIC code 4952 is domestic wastewater treatment. Typically this policy is applied to municipal WWTPs (POTWs) only.
However, my unit didn't develop that policy. Tom Belnick's unit did. I'll defer to him for a final decision.
CHW
From: Mickey, Mike
Sent: Friday, May 09, 2014 4:21 PM
To: Weaver, Charles
Subject: DWR's guidance for "Reduction of Monitoring Frequencies for Exceptionally Performing Facilities"
Charles — MillerCoors (NC0029980 - 5.2 MGD industrial) inquired about the above monitoring reductions. However, the
guidance says it is for facilities included in SIC 4952. Wouldn't that exclude MillerCoors? I don't think they receive any
domestic wastewater. Thanks, Mike.
Mike Mickey
Mike.Mickev@NCDENR.eov
NC Division of Water Resources
585 Waughtown Street
Winston-Salem, NC 27107
Phone: (336) 771-4962
FAX: (336) 771-4630
Mickey, Mike
From: Lucas, Drew <Andrew.Lucas@millercoors.com>
Sent: Friday, May 09, 2014 2:06 PM
To: Mickey, Mike
Subject: RE: NPDES Inspection Checklist
Thanks Mike. I appreciate it. See you on the 2152
Thanks,
Drew
0 Miltercoors
Andrew C. Lucas • Environmental & Sustainability Engineer / Sr. Process Leader — WWTP
MillerCoors • 863 E. Meadow Road • Eden, North Carolina • 27288
Andrew.Lucaso_MillerCoors.com • (336) 627-2592 • Cell (336) 932-2012
From: Mickey, Mike fmailto:mike. mickey@ncdenr.gov]
Sent: Friday, May 09, 2014 1:09 PM
To: Lucas, Drew
Subject: NPDES Inspection Checklist
Drew — Attached is a copy of the checklist for the inspection. Please let me know if you have any questions. Thanks,
Mike.
Mike Mickey
Mike.Mickev@NCDENR.eov
NC Division of Water Resources
585 Waughtown Street
Winston-Salem, NC 27107
Phone: (336) 771-4962
FAX: (336) 771-4630
E-mail correspondence to and from this address may be subject to the North
Carolina Public Records Law and may be disclosed to third parties.
1
North Carolina Emergency Management - EM43 Reporting Page 1 of 3
North Carolina Emergency Management - EM43 Reporting
Print IL Return To List
EM Level: NCEM Edited: Include in Report:
4 Yes Yes
Taken by: Date/Time Reported: Date/Time Occurred:
R Brown 12/28/2013 13:23:38 12/28/2013 01:00:00
Reported by: Agency: Phone:
Andrew Lucas Miller Coors 336-932-2012
County: City: Area:
Rockingham Eden 9
Street Address: Zip Code:
863 E Meadow Rd
Type: Wastewater
Animal Disease Event Type:
Complaint Event Type:
FNF Event Type:
HazMat Event Type:
Homeland Security Event:
Other Event Type:
Transportation Event Type:
Weather Event Type:
State Resource Request
EVENT TYPE
Bomb Threat Event Type:
Fire Event Type:
FNF Class:
HazMat Class:
Non-FNF Event:
SAR Type:
Wastewater Event Type:
Other
Weather Event Name:
HazMat Mode:
Non-FNF Event Type:
WMD Event Type:
Event Description:
Pump system failed wastewater flowed out of collection system and spilled to field and
into creek to retention pond none offsite, no drinking water, no fish kill 1000-10000 gallons
mechanical failure on pump has been fixed, no cleanup necessary. Industrial wastewater
from brewery
Filename:
Deaths: Injuries: Evacuation: Radius:
0 0 0 0
Responsible Party: Responsible Party Phone:
https://www.ncsparta.net/eoc7/boards/board.aspx?tableid=275&viewid=1011&... 12/30/2013
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Charles Wakild, P.E.
Governor Director
30 April 2012
MillerCoors, LLC
Attn: Mr. Andrew C. Lucas, Environmental, Health & Safety Representative
863 East Meadow Road
Eden, NC 27288
Subject: Compliance Evaluation Inspection
NPDES Permit NCO029980 &
NPDES General Stormwater Permit NCG060112
MillerCoors, LLC
Rockingham County
Dear Mr. Lucas:
Dee Freeman
Secretary
Mr. Mike Thomas of the Winston-Salem Regional Office of the North Carolina Division of Water
Quality conducted a compliance evaluation inspection of the. MillerCoors Brewery on 18 April 2011.
Your assistance and cooperation as well as that of Mr. Matt Toms was greatly appreciated. Inspection
findings are summarized below.
The facility is located at 863 Meadow Road, in Eden, in Rockingham County. Wastewater
produced at the facility is discharged to the Dan River, which is currently classified as . � waters
in the Roanoke River Basin. L
NPDES Permit NCO029980 Site Review
The facility is very well operated and maintained. At the time of inspection three of the eight
basins were offline and not in use. Two of these had been drained to repair leaks in the wall
separating the two basins and the third was not in use while maintenance is being performed on the
diffuser system. The facility still has more than adequate capacity to function properly while these
basins are offline.
The facultative lagoons were inspected and found to be in very good shape. No indications of
erosion or presence of burrowing animals was observed. During the inspection you inquired about the
ability to utilize polymer logs to help reduce suspended nutrients and control algal growth. To follow
up, Mr. Thomas spoke with Sergei Chernikov, with our Complex Permitting Unit, about using this
type of polymer. Please provide this office with a letter describing the product and its intended use for
our review. Additional sampling for toxicity may be required to determine your facilities ability to
use this product long term.
North Carolina Division of Water Quality, Winston-Salem Regional Office
Location: 585 Waughtown St Winston-Salem, North Carolina 27107 One
Phone: 336-771-50001 FAX: 336-77146301 Customer Service: 1-877-623-6748 NorthCarolina
Internet: www.ncwaterquality.org
�atura Y
An Equal Opportunity 1 Affirmative Action Employer
MillerCoors, LLC
Compliance Evaluation Inspections NCO029980 & NCG060112
4/30/2012
We appreciate your efforts to effectively operate and maintain this treatment system. No
additional response to this letter is required. If you have questions regarding the inspection or this
letter, please do not hesitate to contact Mr. Thomas or me at (336) 771-5000.
Sincerely,
W. Corey Basinger
Regional Supervisor
Surface Water Protection
Winston-Salem Region
Attachments:
1. BIMS Inspection Report
Cc: WSRO — SAT w/ atch
Central Files w/ atch
NPDES West Unit
F
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 I� 2 15I 11 NCO029980 111 121 11/04/18 117 18I CI 19I S I 20III
Remarks
2111111111111111111111111111111111111111111IIIII6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA --------------- —---------- Reserved —--------- ----------
67 I 169 701 I 711 I 72I N I 73 LU 74 751 III I I 1180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:00 AM 11/04/18
07/08/01
MillerCoors LLC
Exit Time/Date
Permit Expiration Date
863 E Meadow Rd
Eden NC 272883636
11.45 AM 11/04/18
12/04/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
Matthew Stuart Toms/ORC/336-627-1009/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Andrew C Lucas,863 E Meadow Rd Eden NC 272883636//336-627-2592/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance 0 Records/Reports
Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Michael S Thomas WSRO WQ///
Signature of Mana ement Q A Reviewer Agen+ccy//�Or�fftic{e//Phonne and Fax Nucmbberrs Date
iVf//4L "Gv""� —GJ�k /�lliLv ZD/L
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
Permit: NCO029980
Inspection Date: 04/18/2011
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Permit
(if the present permit expires in 6 months or less). Has the permittee submitted a new application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Yes No NA NE
Yes No NA NE
Yes No NA NE
Page # 3
C
Permit: NCO029980
Inspection Date: 04/18/2011
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Lagoons
Yes
No
NA
NE
Are dikes free of burrowing animals?
■
n
n
n
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations?
■
n
n
n
# If excessive algae is present, has barley straw been used to help control the growth?
n
n
■
Is the lagoon surface free of weeds?
■
n
n
n
Is the lagoon free of short circuiting?
■
n
n
n
Comment: ORC asked about using a polymer log to help control algal growth. See
inspection report for more details.
Pump Station - Effluent
Yes
No
NA
NE
Is the pump wet well free of bypass lines or structures?
■
n
n
n
Are all pumps present?
■
n
n
n
Are all pumps operable?
■
n
n
n
Are float controls operable?
■
n
n
n
Is SCADA telemetry available and operational?
■
n
n
n
Is audible and visual alarm available and operational?
■
n
n
n
Comment:
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
■
n
❑
n
Is the basin free of bypass lines or structures to the natural environment?
■
n
n
n
Is the basin free of excessive grease?
■
n
n
n
Are all pumps present?
■
n
n
n
Are all pumps operable?
■
n
■
n
Are float controls operable?
■
n
n
n
Are audible and visual alarms operable?
■
n
n
n
# Is basin size/volume adequate?
■
n
n
Comment:
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext.
Air
Type of aeration system
Diffused
Is the basin free of dead spots?
■
n
n
n
Are surface aerators and mixers operational?
n
n
■
n
Page # 5
Permit: NC0029980
Inspection Date: 04/18/2011
^ M-------
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment:
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Yes No NA NE
Page # 7
Compliance Inspection Report
Permit: NCG060112 Effective: 11/01/07 Expiration: 10/31/12 Owner: Millercoors LLC
SOC: Effective: Expiration: Facility: MillerCoors LLC
County: Rockingham 863 E Meadow Rd
Region: Winston-Salem
Eden NC 272883636
Contact Person: Andrew C Lucas Title: Phone: 336-627-2592
Directions to Facility:
System Classifications:
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 04/18/2012 EntryTime: 10:00 AM Exit Time: 11:45 AM
Primary Inspector: Michael S Thomas Phone:
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Food/Tobacco/Soaps/Cosmetics/Public Warehousing
Stormwater Discharge COC
Facility Status: ■ Compliant ❑ Not Compliant
Question Areas:
0 Storm Water
(See attachment summary)
Page: 1
Permit: NCG060112 Owner - Facility: Millercoors LLC
Inspection Date: 04/18/2012 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Stormwater Pollution Prevention Plan Yes No NA NE
Does the site have a Stormwater Pollution Prevention Plan?
■
n
n
n
# Does the Plan include a General Location (USGS) map?
■
n
Q
O
# Does the Plan include a "Narrative Description of Practices"?
■
n
n
n
# Does the Plan include a detailed site map including outfall locations and drainage areas?
■
n
n
n
# Does the Plan include a list of significant spills occurring during the past 3 years?
■
❑
n
n
# Has the facility evaluated feasible alternatives to current practices?
■
n
n
n
# Does the facility provide all necessary secondary containment?
■
n
n
n
# Does the Plan include a BMP summary?
■
n
Q
Q
# Does the Plan include a Spill Prevention and Response Plan (SPRP)?
■
n
n
n
# Does the Plan include a Preventative Maintenance and Good Housekeeping Plan?
■
n
n
n
# Does the facility provide and document Employee Training?
■
n
❑
n
# Does the Plan include a list of Responsible Party(s)?
■
n
n
# Is the Plan reviewed and updated annually?
■
n
n
n
# Does the Plan include a Stormwater Facility Inspection Program?
■
n
n
n
Has the Stormwater Pollution Prevention Plan been implemented?
■
n
n
n
Comment:
Qualitative Monitoring
Yes No
NA
NE
Has the facility conducted its Qualitative Monitoring semi-annually?
■
n
n
n
Comment:
Analytical Monitoring
Has the facility conducted its Analytical monitoring?
# Has the facility conducted its Analytical monitoring from Vehicle Maintenance areas?
Comment:
Permit and Outfalls
# Is a copy of the Permit and the Certificate of Coverage available at the site?
# Were all outfalls observed during the inspection?
# If the facility has representative outfall status, is it properly documented by the Division?
# Has the facility evaluated all illicit (non stormwater) discharges?
Comment:
Yes No NA NE
■nnn
n n ■ n
Yes No NA NE
Page: 3
M I IerCoors M
863 E. MEADOW ROAD
EDEN, NC 27288-3636
.2100
i
www.MillerCoors.com
www.MillerCoors.com
September 24, 2012 N.C.DepL 0 ENR
CERTIFIED MAIL
SEP 2 7 2012
RETURN RECEIPT REQUESTED ; _ Winston-Saitiui
Mr. Mike S. Thomas
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Winston-Salem Regional Office
585 Waughtown Street
Winston-Salem, NC 27107
Attn: Central Files
1617 Mail Service Center
Raleigh, NC 27699-1617
RE: Follow-up Letter to Wastewater By -Pass Notification on 9/23/12 - MillerCoors LLC — Eden, NC (NPDES Permit #
NC0029980)
Dear Mr. Thomas:
This letter serves as follow-up written notification of a wastewater treatment system by-pass that occurred on
September 23, 2012 as reported to the Division of Water Quality verbally within 24 hours in accordance with our NPDES Permit.
On September 23, 2012, a wastewater by-pass occurred in the facility's wastewater treatment plant causing a minor amount of
wastewater to backflow to the drain system inside the Main Wastewater Building and to the asphalt area located adjacent to
the building. The incident occurred around 11:00AM and was caused by equipment failure (backup pump failed to start). The
backup diesel pump was in place at the time. The operator manually started and primed the pump after flow was established
and made the necessary reporting calls.
Upon discovery of the incident, the facility immediately took corrective measures in accordance with our Storm
Water Pollution Prevention Plan to ensure containment of the spilled material and prevent the material from being discharged
off -site. An assessment was made at downstream locations to ensure no off -site impact release or damage from the spilled
material.
Please contact me at (336) 627-2137 or at hassan.nunn@millercoors.com should you have any questions or comments
regarding this submittal.
Sincerely,
Hassan A. Nunn �L.lL1LCr.L (.,✓�
Environmental Coordinator
Cc: Jim Smith
Matt Toms
Mike Van Poots
Mike Lozano
Audrey Templeton — Milwaukee, WI
North Carolina Emergency Management - EM43 Reporting
Page 1 of 3
North Carolina Emergency Management - EM43 Reporting
Print [ Return To List
EM Level: NCEM Edited: Include in Report:
4 Yes Yes
Taken by: Date/Time Reported: Date/Time Occurred:
CTant 09/23/201211:09:00 09/23/201212:31:00
Reported by: Agency: Phone:
National Response Center National Response Center
County: City: Area:
Rockingham Eden 9
Street Address: Zip Code:
868 East Meadow Road
WI2101110V .1
Type: Wastewater
Animal Disease Event Type: Bomb Threat Event Type:
Complaint Event Type: Fire Event Type:
FNF Event Type: FNF Class:
HazMat Event Type: HazMat Class: HazMat Mode:
Homeland Security Event: Non-FNF Event: Non-FNF Event Type:
Other Event Type: SAR Type:
Transportation Event Type: Wastewater Event Type:
Sewage
Weather Event Type: Weather Event Name: WMD Event Type:
State Resource Request
Event Description:
Miller Coors Brewery reported a 100 gallon discharge of waste water from the brewery
onto the ground. No water sources were affected and clean up contractor was hired.
Attachment
Filename: NATIONAL RESPONSE CENTER.docx
Deaths: Injuries: Evacuation: Radius:
0 0 0 0
Responsible Party: Responsible Party Phone:
Point of Contact: Point of Contact Phone:
https://www.ncsparta.net/eoc7/boards/board.aspx?tableid=275&viewid=1011&u... 9/25/2012
Thomas, Mike
From:
Lucas, Drew [Andrew. Lucas@millercoors.com]
Sent:
Monday, February 20, 2012 9:52 AM
To:
Thomas, Mike
Cc:
Toms, Matthew
Subject:
Bypass Notification - MillerCoors - Eden, NC
Attachments:
image001.jpg
Mike,
We experienced a foaming event on 2/19/12 at approximately 2:0013M where high winds picked up heavy foam in our
#3 Diversion Basin and chunks of foam were carried out of the basin into the adjacent field next to the WWTP. This foam
was from a recent flow of waste beer that was diverted into our #3 basin per plant procedure. We immediately turned
off the aerators to this basin to reduce foaming and prevent further bypass. There was no evidence of the material
leaving the site and the rain/snow mix helped to knock down the foam as well. This issue has been resolved, however,
we are submitting this notice to serve as a bypass notification from the event. It is estimated that <10 gallons total of
foam was carried out of the basin. Please contact me at (336) 932-2012 if you have any questions regarding this issue.
Thanks,
Drew
MillerCoors-
Andrew C. Lucas • Environmental & Sustainability Engineer / WWT Process Leader
MillerCoors - 863 E. Meadow Road • Eden, North Carolina • 27288
Lucas.Andrew(&MillerCoors.com • (336) 627-2592 • Cell (336) 932-2012
1
Compliance Inspection Report
Permit: NCG060112 Effective: 11/01/07 Expiration: 10/31/12 Owner: Millercoors LLC
SOC: Effective: Expiration: Facility: MillerCoors LLC
County: Rockingham 863 E Meadow Rd
Region: Winston-Salem
Eden NC 272883636
Contact Person: Andrew C Lucas Title: Phone: 336-627-2592
Directions to Facility:
System Classifications:
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Certification: Phone:
Inspection Date: 05/18/2011 Entry Time: 10:00 AM Exit Time: 01:30 PM
Primary Inspector: Michael S Thomas Phone:
Secondary Inspectdr(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Food/Tobacco/Soaps/Cosmetics/Public Warehousing
Stormwater Discharge COC
Facility Status: ■ Compliant Q Not Compliant
Question Areas:
0 Storm Water
(See attachment summary)
Page: 1
Permit: NCG060112 Owner -Facility: Millercoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Page: 2
Permit: NCG060112 Owner - Facility: Millercoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Stormwater Pollution Prevention Plan Yes No NA NE
Does the site have a Stormwater Pollution Prevention Plan? Arib, n n
# Does the Plan include a General Location (USGS) map? �/' n n
# Does the Plan include a "Narrative Description of Practices'? r■ L) n n
# Does the Plan include a detailed site map including outfall locations and drainage areas? ' 3 n n
Does the Plan include a list of significant spills occurring during the past 3 years? �n n n
# Has the facility evaluated feasible alternatives to current practices? s1111 =' n n
# Does the facility provide all necessary secondary containment? 4- n n
oQ # Does the Plan include a BMP summary? n n
# Does the Plan include a Spill Prevention and Response Plan (SPRP)?
I a # Does the Plan include a Preventative Maintenance and Good Housekeeping Plan? n n
# Does the facility provide and document Employee Training? n n
JA` # Does the Plan include a list of Responsible Party(s)? ,I�'n n
# Is the Plan reviewed and updated annually? 470 n n
\, #Does the Plan include a Stormwater Facility Inspection Program?
*6,nn
Has the Stormwater Pollution Prevention Plan been implemented? —4n n n
Comment: Plan is reviewed annually and updated as needed. Facility is inspected
once a week to inspect stormwater measures.
Qualitative Monitoring Yes No NA NE
Has the facility conducted its Qualitative Monitoring semi-annually? n n n
Comment:
Analytical Monitoring Yes No NA NE
Has the facility conducted its Analytical monitoring? n n n
# Has the facility conducted its Analytical monitoring from Vehicle Maintenance areas?n n
Comment:
Yes No
Permit and Outfalls A NE
# Is a copy of the Permit and the Certificate of Coverage available at the site? ❑ n n
# Were all outfalls observed during the inspection? 0 n
# If the facility has representative outfall status, is it properly documented by the Division? n —
# Has the facility evaluated all illicit (non Stormwater) discharges? n n ❑
Comment: II
over ��w 444 - a 6) �'� �oGc x1t- . �v � Page: 3
-EFFLUENT
SETTLING
BASIN
CHEMICAL
NO.4
ADDITION
TANK
CHLORINE
N0.3
BLDG.
SAMPLING
CHAMBER
NO.2
NO�1
wlj - -- --
s__. u I 4
SECONDARY _
__. CLARIFIERS
00 2 3 BLOWER BLDG.
90' 01A
MAIN TREATMENT BLDG.
-INFLUENT PUMPING �' Jr 6 Mtl
& GRIT REMOVAL 5 t,00O/F T
4(,c.(o I it4
O(oAC,
SPLITTER BOX
N0.3rNO.5�NO.l,-NO.2r-NO.4
317 rn(�
NO. B
(.O 000 /F T
t3,'�3a1 �til
N0.7
O SSG PA-3 14
3 •5 �, c.
No. s
AERATION
BASINS
NO.5 0
2 � �'
EFFLUENT PUMP.
STATION/3 WAY
SPLITTER BOX —
PARALLEL MODE
SPLITTER BOX
lob
DRAIN PUMP STATION/
OUTLET CONTROL BOX
FIGURE i— i
PLANT PLOT PLAN
300 �
WEST
LAGOON
1.3 rmn/FT
qV(4 ScoPE
12c. �c.�%ICJ
15.2 m �7�i►,vcd
Su E
4,8Ae.
EAST
LAGOON
SERIES MODE
SPLITTER BOX
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 I NI 2 151 31 NCO029980 Ill 121 11/05/18 117 181 c 19 SI 20I I
_ t—s !_!
Remarks
21111111111111111111111111111111111111111111111-1-16
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA-----------Reserved----------
67I 169 701 I 71 UI 721 N I 73 W 74 751 I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:00 AM 11/05/18
07/08/01
MillerCoors LLC
Exit Time/Date
Permit Expiration Date
863 E Meadow Rd
Eden NC 272883636
01:30 PM 11/05/18
12/04/30
Name(s) of Onsite Representative(s)rritles(s)/Phone and Fax Number(s)
Other Facility Data
Matthew Stuart Toms/ORC/336-627-1009/
Name, Address of Responsible Officialfritle/Phone and Fax Number
Contacted
Andrew C Lucas,863 E Meadow Rd Eden NC 272883636//336-627-2592/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance 0 Records/Reports
Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Michael S Thomas WSRO WQ///
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers ate
I
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES yr/mo/day Inspection Type 1
3I NC0029980 111 12, 11/05/18 117 18ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
ati �a l► a.,,,.� AL; rPlp1l x4w,
Page # 2
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? '1111111Kn n ❑
Is all required information readily available, complete and current? In n n
Are all records maintained for 3 years (lab. reg. required 5 years)? n n n
Are analytical results consistent with data reported on DMRs? �n n n
Is the chain -of -custody complete? A(n n n
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters? f n n n
Has the facility submitted its annual compliance report to users and DWQ? /n n )w-n
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? *o n n
Is the ORC visitation log available and current? ■ n n n
Is the ORC certified at grade equal to or higher than the facility classification? �n n n
Is the backup operator certified at one grade less or greater than the facility classification? n n
Is a copy of the current NPDES permit available on site? n n
Facility has copy of previous year's Annual Report on file for review? ❑ n�n
Comment:
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ■ n n n
Are all other parameters(excluding field parameters) performed by a certified lab? ,■(a n n
# Is the facility using a contract lab? X011"n n n
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? ) n n n
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? n ❑ n�/
_ n n rl�
Incubator (BOD) set to 20.0 degrees Celsius +/ 1.0 degrees? _ _ _ ■
Comment:
Effluent Pipe Yes No NA NE
Page # 3
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
n n n ,1(
❑ Q ❑'k,
If effluent (diffuser pipes are required) are they operating properly?
Comment: The effluent discharge pipe was not evaluated during this inspection
however, observations of the high quality of the effluent gave me no indications that
there would be problems at the discharge.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Yes No NA NE
)1/0 00
Is flow meter calibrated annually? _.�, har`JO�'�s -jip �0 ��
�n n n
�n n n
Is the flow meter operational?
the flow meter?
❑ El
(If units are separated) Does the chart recorder match
Comment:
Operations & Maintenance
Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
■ ❑ ❑ Q
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge n n ■ n
Judge, and other that are applicable?
Comment:
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
n n ■ Q
■ Q n n
Is the facility as described in the permit?
# Are there any special conditions for the permit?
0 0 0
Is access to the plant site restricted to the general public?
■ n n n
Is the inspector granted access to all areas for inspection?
■ n n n
Comment: The current NPDES permit expires April 2012. Staff at the facility are
already preparing to submit a renewal.
Pumps-RAS-WAS
Yes No NA NE
■ n p n
Are pumps in place?
■ n n n
Are pumps operational?
■ n n n
Are there adequate spare parts and supplies on site?
Comment:
Yes No NA NE
Lagoons
Facultative
Type of lagoons?
Page # 4
Permit: NC0029980 Owner- Facility: MillerCoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation
Lagoon Yes No NA NE
# Number of lagoons in operation at time of visit? 2
Are lagoons operated in? Series
# Is a re -circulation line present?
❑
n
n
■
Is lagoon free of excessive floating materials?
■
n
n
n
# Are baffles between ponds or effluent baffles adjustable?
n
n
n
■
Are dike slopes clear of woody vegetation?
■
n
❑
n
Are weeds controlled around the edge of the lagoon?
■
n
n
❑
Are dikes free of seepage?
■
n
n
❑
Are dikes free of erosion? ■ n n n
Are dikes free of burrowing animals? ■ ❑ ❑ n
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations? n n n ■
# If excessive algae is present, has barley straw been used to help control the growth? ❑ n ■ n
Is the lagoon surface free of weeds? ■ n n ❑
Is the lagoon free of short circuiting? ■ n n n
Comment:
Pump Station - Effluent
Yes No
NA
NE
Is the pump wet well free of bypass lines or structures?
■ n
❑
❑
Are all pumps present?
■ ❑
n
❑
Are all pumps operable?
■ n
n
n
Are float controls operable?
■ n
n
n
Is SCADA telemetry available and operational?
■ ❑
n
n
Is audible and visual alarm available and operational?
■ ❑
Q
0
Comment:
Equalization Basins
Yes No
NA
NE
Is the basin aerated?
■ 0
O
Is the basin free of bypass lines or structures to the natural environment?
■ n
n
n
Is the basin free of excessive grease?
■ ❑
n
❑
Are all pumps present?
n o
■
n
Are all pumps operable?
n n
■
n
Page # 5
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation
Equalization Basins
Yes No NA
NE
Are float controls operable?
0 0 ■
Are audible and visual alarms operable?
❑ 0 ■
# Is basin size/volume adequate?
■ n 00
Comment:
Aeration Basins
Yes No NA
NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
■ 0 Q
Cl
Are surface aerators and mixers operational?
Cl n ■
Q
Are the diffusers operational?
■ ❑ ❑
❑
Is the foam the proper color for the treatment process?
■ n n
n
Does the foam cover less than 25% of the basin's surface?
■ ❑ 0
Q
Is the DO level acceptable?
Q ❑ Q
■
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Q
■
Comment:
Secondary Clarifier
Yes No NA
NE
Is the clarifier free of black and odorous wastewater?
■ ❑ Q
Is the site free of excessive buildup of solids in center well of circular clarifier?
■ ❑ 0
Q
❑ 0
C3
Are weirs level?
■ n n
❑
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
■ ❑ ❑
0
Is scum removal adequate?
■ Q 0
Is the site free of excessive floating sludge?
■ C1 n
0 Q
0
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
■ 0 0
0
Is the overflow clear of excessive solids/pin floc?
■ ❑ 0
0
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
■ n Q
n
Comment:
Bar Screens
Yes No NA NE
Type of bar screen
Page # 6
Permit: NC0029980 Owner - Facility: MillerCoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation
Bar Screens
Yes
No
NA NE
a. Manual
❑
b. Mechanical
■
Are the bars adequately screening debris?
■
n
n ❑
Is the screen free of excessive debris?
■
❑
130
Is disposal of screening in compliance?
■
❑
❑ ❑
Is the unit in good condition?
■
❑
❑ ❑
Comment:
Grit Removal
Yes
No
NA NE
Type of grit removal
a. Manual
❑
b. Mechanical
■
Is the grit free of excessive organic matter?
■
❑
❑ ❑
Is the grit free of excessive odor?
■
❑
❑ ❑
# Is disposal of grit in compliance?
■
❑
❑ ❑
Comment: At present grit is removed and landfilled off site. According to staff, plans
are in the works to send the grit to a commercial composting facility.
Page # 7
Updated July 23, 2010
Applied Polymer Systems, Inc.
Material Safety Data Sheet
1. IDENTIFICATION OF THE PRODUCT AND THE COMPANY
Product Name: APS 806 Pond Log®
Supplied: Applied Polymer Svstems, Inc.
519 Industrial Drive
Woodstock, GA 30189
Tel. 678494-5998
Fax. 678494-5298
www.siltstop.com
2. COMPOSITION/INFORMATION ON INGREDIENTS
Identification of the preparation: Anionic water-soluble Co -polymer gel
3. HAZARD IDENTIFICATION
Placement of these materials on wet surfaces to be walked on will create extremely slippery conditions.
4. FIRST AID MEASURES
Inhalation: None
Skin contact: Contact with wet skin could cause dryness and chapping. Wash hands with water and soap.
Use of gloves recommended.
Eye contact: Rinse thoroughly with plenty of water, including under the eyelids. Seek medical attention in
case of persistent irritation.
Ingestion: Consult a physician
S. FIRE -FIGHTING MEASURES
Suitable extinguishing media: Water, water spray, foam, carbon dioxide, dry powder.
Special fire -fighting precautions: Pond Logs that become wet render surfaces extremely slippery.
Protective equipment for firefighters: No special equipment required.
G. ACCIDENTAL RELEASE MEASURES
Personal precautions: No special precautions required.
Methods for cleaning up: Dry wipe as well as possible, Keep in suitable and closed containers for disposal.
After cleaning flush away traces with water.
%. HANDLING AND STORAGE
Handling: Avoid contact with skin and eyes. Wash hands after handling.
Storage: Keep in a cool, dry place.
Specializing in the Optimization of Water Treatment Systems, Flocculents, and Drill Fluids. Polyrrer
Characterization and Application for: Erosion Control. Acid Rock Drainage Mitigation, Solubilized
Metal Control, Pond Management Systems, and Dredging.
Updated July 23, 2010
8. EXPOSURE CONTROLS / PERSONAL PROTECTION
Engineering controls: Handle in dry areas. If this cannot be avoided use extreme caution once the log has become
wet.
Personal protection equipment
Respiratory Protection: None
Hand protection: Dry cloth, leather or rubber gloves.
Eye Protection: Safety glasses with side shields. Do not wear contact lenses.
Skin protection: No special protective clothing required.
Hygiene measures: Wash hands before breaks and at end of work day.
9. PHYSICAL AND CHEMICAL PROPERTIES
Form:
Granular semi -solid gel
Color:
Blue
Odor:
None
pH:
7.66
Melting point:
N/A
Flash point:
N/A
Vapor density:
N/A
10. STABILITY AND REACTIVITY
Stability: Product is stable, no hazardous polymerization will occur.
Materials to avoid: Oxidizing agents may cause exothermic reactions.
Hazardous decomposition products: Thermal decomposition may produce nitrogen oxides (NOx), carbon oxides.
11. TOXICOLOGICAL / ECOLOGICAL INFORMATION
Acute toxicity (EPA-821-R-02-012)
LC 50 (Survival) / Ceriodaphnia dubia / 48h / 673 ppm
NOAEC (Survival) / Ceriodaphnia dubia / 48h / 420 ppm
LC 50 / Oncorhynchus mykiss / 96h / 2928 ppm
Chronic toxicity (EPA-821-R-02-013)
IC 25 (Survival) / P. promelas / 7 day / 77.8 ppm
NOEC (Survival) l P. promelas / 7 day / 52.5 ppm
IC 25 (Growth) l P. promelas / 7 day / 50.1 ppm
NOEC (Growth) l P. promelas l 7 day / 52.5 ppm
IC 25 (Survival) / C. dubia / 7 day / 78.7 ppm
NOEC (Survival) / C. dubia /7 day / 52.7 ppm
IC 25 (Reproduction) / C. dubia / 7 day / 66.8 ppm
NOEC (Reproduction) / C. dubia / 7 day / 52.5 ppm
Bioaccumulation: The product is not expected to bioaccumulate.
Persistence / degradability: Not readily biodegradable: ( —85% after 180 days).
13. TRANSPORT AND REGULATORY INFORMATION
Not regulated by DOT, RCRA status -Not a hazardous waste
NFPA and HMIS ratings:
NFPA Health: 1 Flammability: 0 Reactivity: 0
HMIS Health 1 Flammability 0 Reactivity 0
Specializing in the Optimization of Water Treatment Systems, Flocculents, and Drill Fluids. Polymer
Characterization and Application for: Erosion Control, Acid Rock Drainage Mitigation, Solubilized
Metal Control, Pond Management Systems, and Dredging.
2
Thomas, Mike
From:
Lucas, Drew [Andrew. Lucas@millercoors.com]
Sent:
Friday, June 03, 2011 3:56 PM
To:
Thomas, Mike
Cc:
Toms, Matthew
Subject:
MiilerCoors - Eden, NC - pH excursion - 6/1/2011
Attachments:
image001.jpg
Mike,
As discussed via telephone, we had a daily pH excursion in our final effluent on 6/1/2011 that will be reported on
the June DMR submitted to NCDENR by July 31.
This was caused by higher ambient temperature causing increase in algae growth and alkalinity removal in the polishing
lagoons. Additionally, a plugged screen at the lagoon discharge (normally used as a precaution to keep leaves and debris
from effluent) decreased flow across the polishing lagoons. Normally, if a high pH is ever approached, standard procedure
is to open the blend valve (adding clarifier effluent water) to produce an acceptable final effluent pH. We do not have a
high pH in our clarifiers, but in our lagoons due to naturally occurring circumstances and blending of the effluent reduces
pH to acceptable levels.
A less experienced WWTP lab technician was on shift during the high pH timeframe. Although they have been thoroughly
trained, we have a couple of new operators at our WWTP that have not had exposure to this situation before and lack
experience, during the warmer months, to blend with clarifier water as necessary. We plan to reiterate this issue with our
WWTP operators to ensure a thorough understanding of standard procedures and monitoring requirements.
Corrective Actions include:
1.) Report non-compliance to NCDENR - COMPLETE
2.) Remove lagoon discharge screen during high temperature periods, whenever possible, to prevent plugging —
COMPLETE
3.) Re-train all WWTP operators to better understand pH monitoring, dissolved oxygen/alkalinity balance and effluent
blending strategy to prevent high pH situations - by 6/10/11
The pH excursion was a one-time occurrence and effluent pH was immediately corrected to acceptable levels upon
discovery of this issue. The above actions will prevent recurrence of this issue and ensure the facility maintains acceptable
pH levels in our effluent.
Please let me know if any questions or comments regarding this issue.
Regards,
Drew
Mille cros-
Andrew C. Lucas • Environmental & Sustainability Engineer
863 E. Meadow Road • Eden, North Carolina • 27288
Lucas.Andrew(WillerCoors.com • (336) 627-2592 • Cell (336) 932-2012
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Coleen H. Sullins Dee Freeman
Governor Director Secretary
23 May 2011
MillerCoors, LLC
Attn: Mr. Andrew C. Lucas, Environmental, Health & Safety Representative
863 East Meadow Road
Eden, NC 27288
Subject: Compliance Evaluation Inspection
NPDES Permit NCO029980 &
NPDES General Stormwater Permit NCG060112
MillerCoors, LLC
Rockingham County
Dear Mr. Lucas:
Mr. Mike Thomas of the Winston-Salem Regional Office of the North Carolina Division of Water Quality
conducted a compliance evaluation inspection of the MillerCoors Brewery on 18 May 2011. Your assistance
and cooperation as well as that of Mr. Matt Toms was greatly appreciated. Inspection findings are summarized
below.
The facility is located at 863 Meadow Road, in Eden, in Rockingham County. Wastewater produced at the
facility is discharged to the Dan River, which is currently classified as WS-IV waters in the Roanoke River
Basin.
NPDES Permit NCO029980 Site Review
The facility is very well operated and maintained. At the time of inspection three of the eight basins were
offline and not in use. Two of these had been drained to repair leaks in the wall separating the two basins and
the third was not in use while maintenance is being performed on the diffuser system. The facility still has
more than adequate capacity to function properly while these basins are offline.
The facultative lagoons were inspected and found to be in very good shape. No indications of erosion or
presence of burrowing animals was observed.
The sludge handling facilities were inspected and found to be very well maintained and operated. The
facility has a 90 thousand gallon sludge tank where sludge is held before going to the sludge press. The
resulting product is then land applied offsite.
Effluent flow is measured and flow proportional samples are collected through a sampler located in the
basement of the treatment building. Temperature in the sampler was below the required 6°C specified in the
permit. The flow meter is calibrated as required by the permit.
North Carolina Division of Water Quality, Winston-Salem Regional Office
Location: 585 Waughtown St. Winston-Salem, North Carolina 27107 One
Phone: 336-771.50001 FAX: 336-77146301 Customer Service: 1-877.623-6748 NorthCarolina
Internet: www.ncwaterquality.org Natura!lY
An Equal Opportunity 1 Affirmative Action Employer
LC
nP_-
co Evaluation Inspections NCO029980 & NCG060112
/2011
Pa.c 2
Documentation Review
Mr. Thomas evaluated laboratory data during the inspection. Operation logs were reviewed and found to
meet all requirements. Scheduled maintenance at the plant is managed through an electronic database that
produces work orders when maintenance is due. Comparison of available lab reports and field monitoring data
with discharge monitoring reports (DMR) showed no concerns or errors. Chain of custody records were
available and complete. The visitation and operation/maintenance logs were reviewed and found to be complete
and current. All required lab testing for the facility, is conducted by Men itech. MillerCoors has a current field
laboratory certification for dissolved oxygen, pH and temperature.
MillerCoors, LLC, had no effluent limit violations or monitoring violations the past twelve months. No
annual report is required for this facility.
The facility operates 24 hours a day 7 days a week with a total of six operators (two per shift). The
assigned Operator in Responsible Charge, Mr. Toms, as well as, the other operators has the appropriate, current
certifications to operate the facility.
NPDES General Stormwater Permit NCG060112
Site Review
The entire manufacturing plant was very clean and well maintained. No issues were observed at the time of
inspection. All secondary containment measures were in place and secured with appropriate locks. Minor
erosion was noted at the outfalls located near the constructed wetlands adjacent to NC HWY 770. The erosion
can likely be managed by reducing the frequency and intensity of mowing around the concrete structures and
along the stream banks.
The Stormwater Pollution Prevention Plan (SP3) was found to meet all requirements. The plan is reviewed
annually and updated as needed. Training sessions are conducted annually for current staff and new hires
receive training as part of their orientation. Both analytical and qualitative monitoring are being conducted per
the permit and no readings above permit benchmarks has occurred. MillerCoors, LLC has representative
outfall status that allows monitoring of only one of the four stormwater discharge outfalls. Mr. Thomas found
no reason to reconsider this status and therefore it will remain in effect for the time being.
We appreciate your efforts to effectively operate and maintain this treatment system. No additional
response to this letter is required. If you have questions regarding the inspection or this letter, please do not
hesitate to contact Mr. Thomas or me at (336) 771-5000.
Sincerely,
W. Corey Basinger
Regional Supervisor
Surface Water Protection
Winston-Salem Region
Attachments:
1. BIMS Inspection Report
Cc: WSRO — SWP w/ atch
Central Files w/ atch
NPDES West Unit
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
EPA
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 INI 2 31 N00029980 I11 121 11/05/18 117 181CI 19Ic1 20I I
LJ L=! !
Remarks
2111111111111111111111111111111111111111111111 M6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA --Reserved
67I 169 70U 71 U 72IJ 73I I 174 751 I I I I I Li 80
--� W
Section B: FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
MillerCoors LLC
10:00 AM 11/05/18
07/08/01
Exit Time/Date
Permit Expiration Date
863 E Meadow Rd
Eden NC 272883636
01:30 PM 11/05/18
12/04/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Matthew Stuart Toms/ORC/336-627-1009/
Name, Address of Responsible Officiallfitle/Phone and Fax Number
Contacted
Andrew C Lucas,863 E Meadow Rd Eden NC 272883636//336-627-2592/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance N Records/Reports
Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Michael S Thomas WSRO WQ///
' , 'e-
r+
'/ 5
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers ate
mac- � - - D4W -
8
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES yr/mo/day Inspection Type
1
3I 11 NCO029980 1 121 11/05/18 Icy 18ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page # 2
PPFP
Perm
it: NCO029980 Owner -Facility: MillerCoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
Cl
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
■
❑
❑
❑
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
■
❑
❑
❑
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
Cl
❑
■
❑
Comment:
Laboratory
Yes No
NA
NE
Are field parameters performed by certified personnel or laboratory?
■ ❑
❑
❑
Are all other parameters (excluding field parameters) performed by a certified lab?
■ ❑
❑
❑
# Is the facility using a contract lab?
■ ❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
■ ❑
❑
❑
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑ ❑
❑
■
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑ ❑
❑
■
Comment:
Effluent Pipe
Yes No
NA
NE
Page # 3
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? ❑ ❑ ❑ ■
Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ ■
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ❑ ■
Comment: The effluent discharge pipe was not evaluated during this inspection
however, observations of the high quality of the effluent gave me no indications that
there would be problems at the discharge.
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? ■ ❑ ❑ ❑
Is flow meter calibrated annually? ■ ❑ ❑ ❑
Is the flow meter operational? ■ ❑ ❑ ❑
(If units are separated) Does the chart recorder match the flow meter? ■ ❑ ❑ ❑
Comment:
Yes No NA NE
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ❑ ❑ ■ ❑
Judge, and other that are applicable?
Comment:
Yes No NA NE
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Is the facility as described in the permit?
# Are there any special conditions for the permit?
■ ❑ ❑ ❑
Is access to the plant site restricted to the general public?
■ ❑ ❑ ❑
Is the inspector granted access to all areas for inspection?
■ ❑ ❑ ❑
Comment: The current NPDES permit expires April 2012. Staff at the facility are
already preparing to submit a renewal.
Yes No NA NE
Pumps-RAS-WAS
■ ❑ ❑ ❑
Are pumps in place?
■ ❑ ❑ ❑
Are pumps operational?
■❑❑❑
Are there adequate spare parts and supplies on site?
Comment:
Yes No NA NE
Lagoons
Facultative
Type of lagoons?
Page # 4
P r-
Permit: NCO029980
Inspection Date: 05/18/2011
Lagoons
# Number of lagoons in operation at time of visit?
Are lagoons operated in?
# Is a re -circulation line present?
Is lagoon free of excessive floating materials?
# Are baffles between ponds or effluent baffles adjustable?
Are dike slopes clear of woody vegetation?
Are weeds controlled around the edge of the lagoon?
Are dikes free of seepage?
Are dikes free of erosion?
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Are dikes free of burrowing animals?
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations?
# If excessive algae is present, has barley straw been used to help control the growth?
Is the lagoon surface free of weeds?
Is the lagoon free of short circuiting?
Comment:
Pump Station - Effluent
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
2
Series
■ ❑ ❑ ❑
■❑❑n
■000
■000
■ O O O
■❑❑n
Yes No NA NE
Page # 5
Permit: NCO029980
Inspection Date: 05/18/2011
Owner -Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Equalization Basins
Yes No NA NE
Are float controls operable?
0 0 ■
Are audible and visual alarms operable?
❑ n Q ■
# Is basin size/volume adequate?
■ n 00
Comment:
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
■ n p n
Is the basin free of dead spots?
Are surface aerators and mixers operational?
❑ ❑ ■
Are the diffusers operational?
■ ❑ Q ❑
Is the foam the proper color for the treatment process?
■ Q ❑ 0
Does the foam cover less than 25% of the basin's surface?
■ ❑ C1 ❑
Q ❑ ❑ ■
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑ ■
Comment:
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
■ 0 Q 0
Is the site free of excessive buildup of solids in center well of circular clarifier?
■ 0 Q
O Q ❑
Are weirs level?
■ ❑ Q Q
Is the site free of weir blockage?
■ ❑ 0 11
Is the site free of evidence of short-circuiting?
■ 0 ❑ 0
Is scum removal adequate?
Is the site free of excessive floating sludge?
■ ❑ Q
■
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
■
Is the overflow dear of excessive solids/pin floc?
■ n Ci Cl
Is the sludge blanket level acceptable? (Approximately '/< of the sidewall depth)
■ C1 n El
Comment:
Yes No NA NE
Bar Screens
Type of bar screen
Page # 6
Permit: NC0029980
Inspection Date: 05/18/2011
Bar Screens
a.Manual
b.Mechanical
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment: At present grit is removed and landfilled off site. According to staff, plans
are in the works to send the grit to a commercial composting facility.
Yes No NA NE
■
■nnn
■nn❑
■nnn
■ ❑ ❑ ❑
Page # 7
ppppppr,
Permit: NCG060112
SOC:
County: Rockingham
Region: Winston-Salem
Compliance Inspection Report
Effective: 11/01/07 Expiration: 10/31/12 Owner: Millercoors LLC
Effective: Expiration: Facility: MillerCoors LLC
863 E Meadow Rd
Contact Person: Andrew C Lucas
Directions to Facility:
System Classifications:
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Title:
Inspection Date: 05/18/2011 Entry Time: 10:00 AM
Primary Inspector: Michael S Thomas
Secondary Inspector(s):
Eden NC 272883636
Phone: 336-627-2592
Certification
Exit Time: 01:30 PM
Phone:
Phone:
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Food/Tobacco/Soaps/Cosmetics/Public Warehousing
Stormwater Discharge COC
Facility Status: ■ Compliant ❑ Not Compliant
Question Areas:
Storm Water
(See attachment summary)
Page: 1
Permit: NCG060112 Owner -Facility: Millercoors LLC
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Page: 2
Permit: NCG060112 Owner - Facility: Millercoors LLC
Pr
Inspection Date: 05/18/2011 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Stormwater Pollution Prevention Plan
Yes
No
NA
NE
Does the site have a Stormwater Pollution Prevention Plan?
■
❑
❑
❑
# Does the Plan include a General Location (USGS) map?
■
n
❑
❑
# Does the Plan include a "Narrative Description of Practices"?
■
n
❑
❑
# Does the Plan include a detailed site map including outfall locations and drainage areas?
■
❑
❑
❑
# Does the Plan include a list of significant spills occurring during the past 3 years?
■
n
❑
❑
# Has the facility evaluated feasible alternatives to current practices?
■
❑
❑
❑
# Does the facility provide all necessary secondary containment?
■
❑
Cl
❑
# Does the Plan include a BMP summary?
■
❑
❑
❑
# Does the Plan include a Spill Prevention and Response Plan (SPRP)?
■
❑
❑
❑
# Does the Plan include a Preventative Maintenance and Good Housekeeping Plan?
■
❑
❑
❑
# Does the facility provide and document Employee Training?
■
❑
❑
❑
# Does the Plan include a list of Responsible Party(s)?
■
❑
❑
❑
# Is the Plan reviewed and updated annually?
■
13
❑
❑
# Does the Plan include a Stormwater Facility Inspection Program?
■
n
❑
❑
Has the Stormwater Pollution Prevention Plan been implemented?
■
❑
❑
❑
Comment: Plan is reviewed annually and updated as needed. Facility is inspected
once a week to inspect stormwater measures.
Qualitative Monitoring
Yes
No
NA
NE
Has the facility conducted its Qualitative Monitoring semi-annually?
■
fl
❑
❑
Comment:
Analytical Monitoring Yes No NA NE
Has the facility conducted its Analytical monitoring? ■ ❑ ❑ ❑
# Has the facility conducted its Analytical monitoring from Vehicle Maintenance areas? ■ ❑ ❑ ❑
Comment:
Permit and Outfalls
Yes
No
NA
NE
# Is a copy of the Permit and the Certificate of Coverage available at the site?
■
Cl
❑
❑
# Were all outfalls observed during the inspection?
■
n
n
Q
# If the facility has representative outfall status, is it properly documented by the Division?
■
n
❑
Cl
# Has the facility evaluated all illicit (non stormwater) discharges?
■
❑
❑
❑
Comment:
Page: 3
Thomas, Mike
From: Lucas, Drew [Andrew. Lucas@millercoors.com]
Sent: Monday, December 06, 2010 5:47 PM
To: Thomas, Mike
Subject: MillerCoors - Eden, NC - Leaking Aeration Basin
Attachments: image001.jpg
Mike,
As discussed during our recent telephone conversation, the MillerCoors — Eden, NC facility made notification to NCDENR
in accordance with our NPDES Permit regarding a leak in our #2 Aeration Basin that was discovered on Tuesday,
11/30/2010. The basin was leaking underneath the unit and into our internal stormwater conveyance ditch. Samples
were taken at the discharge of our retention pond located downstream of the stormwater conveyance ditch to verify no
off -site discharge or impacts took place during this event. Samples for COD and pH were verified to be within normal
parameters during and after the incident.
The following corrective actions are planned to prevent further issue in the #2 basin:
1.) Empty #2 Aeration Basin to prevent further leakage — COMPLETE
2.) Lower the wastewater level in #3 Aeration Basin to prevent leakage through crack in adjoining wall into #2
Aeration Basin —COMPLETE
3.) Remove #2 Aeration Basin from service and install pump system to remove all residual wastewater and/or rain
water from unit —COMPLETE
4.) Investigate location of leak in floor and wall of #2 Aeration Basin — IN PROGRESS
5.) Procure quotes for cleanout and repair of #2 Basin — IN PROGRESS
6.) Repair #2 Aeration Basin and restore to normal operation —Scheduled for early 2011(unit will remain out of
service until repairs are complete)
As previously mentioned, the #2 Aeration Basin has been completely emptied to prevent further leakage. This unit will
remain out of service until repairs can be made. The facility will continue to closely watch this unit to ensure no influent
or leakage occurs during the repair timeframe. Please contact me at (336) 627-2592 or at
Lucas.Andrew@MillerCoors.com if you should have questions or comments regarding this submittal.
Regards,
Drew Lucas
MillerCoors LLC — Eden Brewery
omilwcoom-
Andrew C. Lucas + EH&S Representative
863 E. Meadow Road • Eden, North Carolina • 27288
Lucas.Andrew(a)MillerCoors.com • (336) 627-2592 • Cell (336) 932-2012
�2- 1 t, _4 1\ h w 5 b �e n r-G. r�ec� C I ev- 0t.z1, -��- o�k-
M i I IerCoors
September 27, 2010
CERTIFIED MAIL
Mr. Mil s
Surface Water Quality Division
North Carolina Department of Environment and Natural Resources
Winston-Salem Regional Office
585 Waughtown Street
Winston-Salem, NC 27107-2241
Dear Mr. Thomas:
863 E. MEADOW ROAD
EDEN, NC 27288-3636
336.627.2100
www.MillerCoors.com
EqSEP
EC ;_i1- -2 9 2010
RE: MillerCoors LLC — Eden Brewery — NPDES Permit #NC0029980
Notification of Missed Sample for August 2010
This letter serves as follow-up to our notification via telephone on September 23, 2010 of a missed
sample for the MillerCoors Eden Brewery located at 863 East Meadow Road, Eden, NC 27288 located in
Rockingham County (NPDES Permit #NC0029980). It was discovered on September 23, 2010, during preparation
and review of the August DMR, that a sample had been inadvertently missed for the week of August 9, 2010. The
missed sample was for ammonia and is a weekly monitoring requirement per our NPDES Permit. This requirement
is not associated with an existing numerical discharge limit and is for monitoring purposes only. This sample was
missed due to human error as a part-time employee was responsible for weekly sampling during this timeframe
and failed to take the required sample. This issue was also missed by supervisory personnel and our contract
laboratory. Upon discovery of this omission, the facility immediately worked to take corrective actions and prevent
recurrence.
Samples taken during the week before and after the missing sample period show no indication of
variability for ammonia within the facility's wastewater discharge and it is expected that all ammonia sampling
results would be similar within this timeframe. This is also supported by consistent operation of the facility's
wastewater plant with no issues and low variability within the discharge characteristics during this timeframe. As a
result, this sample would have not contributed any change in information to the existing, large quantity of data
collected by the facility for the monitoring -only requirement for ammonia.
As previously discussed, the facility took immediate corrective actions to prevent recurrence of this issue.
Internal notifications were immediately performed in accordance with the facility's reporting structure and a plan
has been implemented to ensure thorough review on a weekly basis of all scheduled samples in accordance with
PP
VLetterto Mr. Mike Thomas— NCDENR-DWQ
September 27, 2010
the facility's NPDES Permit. Specifically, the facility has developed a procedure to ensure part-time employees are
not involved with sampling as they could lack experience and routine to ensure consistent adherence to
monitoring requirements. Instead, only experienced, full-time employees will be assigned to compliance sampling
activities and a review of all chain of custodies and sampling schedule will take place each week by the Operator -in
Responsible Charge (ORC). Additionally, an automated, electronic reminder system has been implemented to
ensure this review occurs on a consistent basis each week to make certain all samples are collected within the
required timeframes. This automated system also notifies plant supervision and environmental management
personnel for additional follow-up and as backup to ORC review. Additional corrective actions include retraining of
wastewater treatment plant employees on compliance sampling schedules and requirements and further
discussion with our contract laboratory to ensure the facility is immediately notified of any known, missed
samples.
MillerCoors LLC is committed to minimizing environmental impact and ensuring compliance with our
permit limits and conditions at all times. The Eden Brewery strives to continuously improve our environmental
management system to go beyond compliance. The above corrective actions have already been implemented at
the facility and we are confident these additional tasks will prevent recurrence of this issue. Please feel free to
contact me at (336) 627-2592 or via e-mail at andrew.lucas@millercoors.com should you have any questions or
comments regarding this submittal.
Sincerely,
Andrew C. Lucas
EH&S Representative
MillerCoors Eden Brewery
cc: Mike Van Poots — Technical Services Manager
Jim Smith — Brewery Vice President and Plant Manager
Matt Toms — Operator -in -Responsible Charge
Audrey Templeton — Corporate EH&S - Milwaukee, WI
MilleriGoors-
May 26, 2010
CERTIFIED MAIL
RETURN RECEIPT REQUESTED
WPCSOCC
1618 Mail Service Center
Raleigh, NC 27699-1618
RECEIVED
N.C. Deot. of ENR
MAY 2 8 2010
Winston-Salem
Regional Office
863 E. MEADOW ROAD
EDEN, NC 27288-3636
336.627-2100
www.MillerCoors.com
RE: MillerCoors LLC — Eden Brewery - NPDES Permit #NC0029980
Change in Operator -in -Responsible Charge (ORC) Status
Dear Sir or Madam
Please find attached a copy of the Water Pollution Control System Operator Designation Form for
the MillerCoors LLC facility located in Eden, NC. The status of our Operator -in -Responsible
Charge is changing from Mr. Harry D. Hudgins (WW4 #14105) to Mr. Matthew S. Toms (WW4
#994245). Also enclosed is a copy of the notification of removal of ORC status as submitted by
Harry D. Hudgins as he will no longer serve as ORC at this facility, effective May 27, 2010. Mr.
Hudgins has retired from MillerCoors and will be replaced by Mr. Toms after completion of the
current transition period. If you have any comments or questions regarding this submittal, please
contact me at (336) 627-2592 or via e-mail at Lucas. Andrew aiMillerCOOrS com.
Sincerely,
n
Andrew C. Lucas
EH&S Representative
cc fRonBoone�WQ - Winston-Salem Regional Office
=ith
Van Poots
Audrey Templeton — Milwaukee. WI
PV -
Water Pollution Control System Operator Designation Form
WPCSOCC
NCAC 15A 8G .0201
7V1 �Lc dk-C<ra Re-, i zcc_ - Ear $fix y
PermitteeOwner/Officer
GName: /,q _64- A tfitcs7y 1 f�Genv- /ll+o ,, V c,; �--
Mailing Address: O 4 S E. A xy,
City: ttoLe, State: nlC Zip: Z 744P-
Signature:
Phone #: (714 ) 6 Z 7 . z,-r o-e
Date:- 5 2 tG z'/ !]
..............................................................................................................................................
Facility Name: �%i.L6Lid^tp.i LLB Permit #: /VC o o Z99dn
! SUBMIT A SEPARATE FORM FOR EACH TYPE OF SYSTEM!
Facility Type & Grade:
Biological WWTP
Physical/Chemical
Collection System
Type Grade Type Grade
`i Surface Irrigation N/A
Land Application N/A
....................................................................................................................................
Operator in Responsible Charge (ORC) ----
Print Full Name: 4/ r2Vf;,,, -� �N?,trT- Za_g y
Certificate Type / Grade / Number: h)W41 9-- Zqg Work Phone #: (334 ) 617 ,-,?Z{l i
Signature: _M -_% - 1-3 OVI-. Date: S-'74- to
"I certify that I agree to my designation as the Operator in Responsible Charge for the facility noted. I understand and will abide by the
rules and regulations pertaining to the responsibilities of the ORC as set forth in 15A NCAC 08G .0204 and failing to do so can result in
Disciplinary Actions by the Water Pollution Control System Operators Certification Commission"
.....................................................................................................................................
Back -Up OperatorinResponsible Charge (BU ORC)
Print Full Name: J& bLy U-i To.4j rS
Certificate Type / Grade / Number: LU W y ! q l 5 Work Phone #: (334 ) 417 .2.TSi(
Signature: - Date: •Sy-44-10
A certify that I agree to my Vignation as a Back-up Operator in Responsible Charge for the facility noted. I understand and will abide by
the rules and regulations pertaining to the responsibilities of the BU ORC as set forth in 15A NCAC 08G .0205 and failing to do so can
result in Disciplinary Actions by the Water Pollution Control System Operators Certification Commission."
..............................................................................................................................
Mail or Fax to: WPCSOCC
1618 Mail Service Center
Raleigh, NC 27699-1618
Fax: 919n33-13M
(See next page for designation of additional back-up operators, Designation of more than one back-up operator is optional.)
Revised 8.2007
PV
Harry D. Hudgins
4958 Morgan Ford Road
Ridgeway, VA 24148
276-956-4813
WPCSOCC
1618 Mail Service Center
Raleigh, NC 27699-1618
Fax: 919-733-1338
Effective May 27, 2010 I will no longer be the ORC for MillerCoors
Wastewater Plant (Permit # NC0029980)
Thank you,
C I,,
Harry D. Hudgins
Cc: Ron Boone
Winston-Salem Region Office
585 Waughtown Street
Winston Salem, NC 27107-2241
Fax: 336-771-4630
rv�
863 E. MEADOW ROAD
� EDEN, NC 27288-3636
.2100
M iI IerCoors M www.MillerCoors.com
www.MillerCoors.com
RECEIVED
N.C. Dept. of ENR
APR 0 5 2010
March 31, 2010 ; Winston-Salem
Regional Office
CERTIFIED MAIL
RETURN RECEIPT REQUESTED
Ron Boon
o ina Department of Environment and Natural Resources
Division of Water Quality
Winston-Salem Regional Office
585 Waughtown Street
Winston-Salem, NC 27107
RE: Follow -Up Letter to Wastewater Spill Notification on 03/27/2010
MillerCoors, LLC - Eden, NC
Dear Mr. Boone:
This letter serves as follow-up written notification of a wastewater spill that occurred on
March 27, 2010 as reported to the Division of Water Quality (via NC Emergency Operations
Center) verbally within 24 hours of the event. On Saturday, 3/27/2010 at approximately 12:30 PM,
the facility released a small quantity of sludge supernatant (treated wastewater) from our filter
press/sludge storage building towards our stormwater ditch. This was caused by an abnormal
batch of wet sludge being dropped to the sludge storage pad, which plugged the drain system,
flooded the concrete storage area and the supernatant escaped from the building. We estimate
the quantity of supernatant water discharged from the building to be —800 gallons. Due to the
wooded buffer area between the sludge storage building and the stormwater ditch, we do not
expect this entire quantity to have been released directly into the stormwater ditch (estimated at
less than 50 gallons) and there was no evidence of this material being released off -site.
Upon discovery, the facility took immediate corrective actions and placed sand bags,
absorbent pads and bulk sand to stop the flow. The discharge was stopped within a few minutes.
We allowed time for the water to be absorbed and then removed all material from the ground. The
facility also made notification to the NC Emergency Operations Center as this incident happened
outside of normal business hours.
As a corrective action, the facility plans to install additional curbing around the sludge
storage building to prevent recurrence. Please contact me with any questions or comments
regarding this incident at (336) 627-2592 or via e-mail at Lucas.Andrewc@-MillerCoors.com.
Sincerely,
Andrew C. Lucas
EH&S Representative
cc: Mike Van Poots
Bob Rezek
Jim Smith
Audrey Templeton
North Carolina Emergency Management - EM43 Reporting
Page 1 of 3
G ,/t- ..
North Carolina Emergency
Management - EM43 Reporting
Print Return To List
EM Level:
NCEM Edited:
Include in Report:
4
Yes
Yes
Taken by:
Date/Time Reported:
Date/Time Occurred:
CTant
03/27/201012:44:38
03/27/201012:15:38
Reported by:
Agency:
Phone:
Andrew Lucas_-
Miller Corporation Brewing
336-932-2012
County:
City:
Area:
Rockingham
Eden
9
Street Address `"R
;
Zip Code:
863 East Meadow Rd.
EVENT TYPE
Type: Wastewater
Animal Disease Event Type: Bomb Threat Event Type:
Complaint Event Type: Fire Event Type:
FNF Event Type: FNF Class:
HazMat Event Type: HazMat Class:
Homeland Security Event: Non-FNF Event:
Other Event Type: SAR Type:
Transportation Event Type s,r» Wastewater Event Type:
Sewage
Weather Event Type: Weather Event Name:
State Resource Request
HazMat Mode:
Non-FNF Event Type:
WMD Event Type:
Event Description:
Miller Brewing reported less than 300 gallons of treated waster water escaped the sludge press area
and containment area. Crews contained the water by using sandbags. Clean up will be conducted.
Filename:
Deaths: Injuries: Evacuation: Radius:
0 0 0 0
�" :11"
y RResponsible Partes onsiblePart Phone
w
_ ��
Point of Contact: Point of Contact Phone:
Latitude: Longitude:'`
00.000000 00.000000
RRT Request: RRT Approved: RRT Team RRT Mission
Number: Number:
https://www.ncsparta.net/eoc7/boards/board.aspx?tableid=275&viewid=1011 &label=EM-... 3/29/2010
NCDENR
North Carolina Department of Environment and Natura
Division of Water Quality
Beverly Eaves Perdue Coleen H. Sullins
Governor Director
22 February 2010
MillerCoors, LLC
Attn: Mr. Andrew C. Lucas, Environmental, Health & Safety Representative
863 East Meadow Road
Eden, NC 27288-3636
Subject: Compliance Evaluation Inspections
NPDES Individual Wastewater Permit NCO029980 &
NPDES General Industrial Stormwater Permit NCG060112
MillerCoors, LLC
Rockingham County
Dear Mr. Lucas:
Resources
Dee Freeman
Secretary
Ron Boone, of the Winston-Salem Regional Office (WSRO) of the NC Division of Water Quality
(DWQ or the Division), conducted compliance evaluation inspections (CEI) of the subject permits
on 15 February 2010. Your assistance and cooperation, as well as that of Mr. Harry Hudgins,
Wastewater Plant Operator in Responsible Charge (ORC), was greatly appreciated. Inspection
checklists are attached for your records.
NPDES Individual Wastewater Permit NCO029980
Site Review
2. The plant is very well operated and managed; the entire plant was very clean and well maintained.
The following items were noted:
a. The grit chamber is currently down for repairs but is expected to be placed back in service
soon.
b. Two aeration basins are currently in use.
C. One aeration basin is currently in use as an equalization basin.
d. Two of the secondary clarifiers are currently in use.
e. The plant does not have any sludge digestion facilities; however there is a 90K gallon
sludge holding tank that waste sludge is pumped to before being processed in the sludge
presses.
f. The sludge processing facilities are well operated/maintained and produce a high quality
sludge cake.
g. The lagoons are in very good condition. Excessive algae are controlled through application
of Barley Straw.
h. Effluent flow is measured and flow proportional effluent samples are obtained through a
sampler located in the basement of the main treatment building. The flow meter is
calibrated as required.
North Carolina Division of Water Quality, Winston-Salem Regional Office
Location: 585 Waughtown St. Winston-Salem, North Carolina 27107
Phone: 336-771-50001 FAX: 336-77146301 Customer Service: 1-877-623-6748
Internet: www.ncwaterqual4.org
An Equal Opportunity 1 Affirmative Action Employer
NorthCarolina
Natural
1b`
MillerCoors, LLC 11
Attn: Mr. Andrew C. Lucas, Environmental, Health & Safety Representative
Compliance Evaluation Inspections
MillerCoors Eden, NCO029980 & NCGO60112
22 February 2010
Page 2 of 3
i. The actual outfall could not be reached during the inspection due to extremely damp and
muddy conditions. However, a distant visual observation showed the right-of-way to the
outfall to be clear and accessible.
Documentation Review
3. The following documentation was reviewed:
a. Laboratory records, both in-house and contract, were reviewed. All records were complete,
accurate, well organized and available for review. At least five years worth of records are
kept on file. Laboratory records matched discharge monitoring reports and no transcription
or other errors were noted. MillerCoors has a current field laboratory certification for
dissolved oxygen, pH and temperature. All laboratory chains of custody were also
complete, well organized and available for review.
b. Operation and maintenance records were also complete, current well organized and
available for review. Most maintenance of plant equipment is managed through electronic
databases that produce work orders when maintenance is due. Completed work orders are
kept on file. An operational log book is kept. Operators make appropriate daily entries
during their shifts.
C. An operator visitation log is also kept. It is complete and current.
d. No annual compliance report is required.
e. The plant is currently operated 24/7.
f. The assigned ORC, Harry Hudgins, as well as the backup ORC(s), have current appropriate
certifications to enable them to operate the plant.
g. The plant had no limit violations over the previous twelve months.
4. No problems were noted during this inspection. It is noted that Mr. Hudgins will be retiring within
the next few months. Please keep in mind the ORC/BORC requirements and plan ahead to
ensure MillerCoors always maintains ORC/BORC(s) of the required grade in these positions at all
times. Please be sure to copy this office on all ORC designation forms submitted to our Raleigh
office.
NPDES General Industrial Stormwater Permit NCG060112
Site Review
5. The entire manufacturing plant .was quite clean and well maintained. Only one small discrepancy
was noted; the drain for one secondary containment facility was left opened and unlocked. It was
fixed immediately, however. Please ensure all secondary containment facilities are always
maintained in accordance with the permit; i.e. drains always locked in the closed position when not
in use. Also, only designated personnel should be allowed to manage the locks.
Documentation Review
6. The Stormwater Pollution Prevention Plan (SP3) was found to meet requirements. All
discrepancies noted during the last inspection had been corrected. Both analytical and qualitative
monitoring has been accomplished as required; no exceedences of permit benchmarks have
occurred. MillerCoors currently has representative outfall status (ROS) that allows them to monitor
only one of four stormwater discharge outfalls (SDO). Mr. Boone found no reason to reconsider
this status and therefore it will remain in effect for the time being.
Wt
oors, LLC
Mr. Andrew C. Lucas, Environmental, Health & Safety Representative
Compliance Evaluation Inspections
MillerCoors Eden, NCO029980 & NCG060112
22 February 2010
Page 3 of 3
7. All other SP3 related records, i.e. training, facility inspections, etc., were reviewed and also found
to be complete, current, well organized and available for review. Please remember to conduct and
document annual SP3 reviews that include updated spill records and SDO certifications.
8. No written reply to this letter is required. Please continue to help the Division to protect waters of
the State through your continued efforts to comply with all conditions of NCO029980 and
NCG060112. If you have any questions or concerns regarding the inspections or this letter, please
contact me or Mr. Boone at 336-771-5000.
Sincerely,
Steve W. Tedder
Water Quality Regional Supervisor
Winston-Salem Region
Division of Water Quality
Attachments:
1. Inspection Checklist NC0029980
2. Inspection Checklist NCG060112
Cc: WSRO/SWP
NPDES West Unit
Central Files
r
Un,ted States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires8-31-98
Section ANational Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 I NI 2 15I 11 ECO029980 Ill 121 10/02/15 117 181 CI 19I SI 20I I
Remarks
2,IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIILill
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA--------Reserved----------- ------8 —
671 169 711 I 711 I 721 v I 73 W 74 711 I I I I I j
Section B Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POT',/V name and NODES permit Number)
09:00 AM 10/02/15
07/08/01
MillerCoors LLC
Exit Time/Date
Permit Expiration Date
863 E Meadow Rd
Eden NC 272883636
12:00 PM 10/02/15
12/04/30
Name(s) of Onsite Representative (s)(Titles(s)/Phone and Fax Number(s)
Other Facility Data
Harry D Hudgins//336-627-2354 /
Harry D Hudgins//336-627-2419 /
Name, Address of Responsible OfficiaUTitle/Phone and Fax Number
Contacted
Andrew C Lucas,863 E Meadow Rd Eden NC 272863636//336-627-2592/
No
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit ® Flow Measurement ® Operations & Maintenance ® Records/Reports
Self -Monitoring Program ® Sludge Handling Disposal ® Facility Site Review Effluent/Receiving Waters
Laboratory ® Storm Water
Section D Summary of Finding/Comments Attach additional sheets of narrative and checklists as necessary
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone WSRO WQ//704-663-1699 Ext.2202/
- gs_
Signature o met A Revie Agency/Offce/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES
yr/mo/day
31 NCO029980 I11 12I 10/02/15 117
Inspection Type
18II
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
Page # 2
Permit: NC0029980
Inspection Date: 02/15/2010
Pump Station - Influent
Is the pump wet well `ree of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Owner - Facility: MillerCcors LLC
Inspection Type: Compliance Evaluation
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry ava fable and operational?
Is audible and visual alarm available and operational?
Comment: Please refer to the attached inspection summary letter.
Type of bar screen
a. Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: Please refer to the attached inspection summary letter.
Type of grit removal
a. Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment: Please refer to the attached inspection summary letter.
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
■❑nn
■nnn
■nnn
■nnn
nnn■
■nnn
■nnn
n
■
■nnn
■nnn
■nnn
■nnn
■nnn
■nnn
■nnn
nn■n
Page # 3
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 02/15/2010 Inspection Type: Compliance Evaluation
Equalization Basins
Yes No NA NE
Are all pumps operable?
n n ■ n
Are float controls operable?
n n n ■
Are audible and visual alarms operable?
n n n ■
# Is basin size/volume adequate?
■ n
Comment: Please refer to the attached inspection summary letter.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
■ n n n
Are surface aerators and mixers operational?
n n ■ n
Are the diffusers operational?
■ n n n
Is the foam the proper color for the treatment process?
■ n n n
Does the foam cover less than 25% of the basin's surface?
■ n n n
Is the DO level acceptable?
n n n ■
Is the DO level acceptable?(1.0 to 3.0 mg/I)
nnn■
Comment: Please refer to the attached inspection summary letter.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
■ n n n
Is the site free of excessive buildup of solids in center well of circular clarifier?
■ n n n
■ n n n
Are weirs level?
Is the site free of weir blockage?
■ n n n
Is the site free of evidence of short-circuiting?
■ n n n
Is scum removal adequate?
■ n n n
Is the site free of excessive floating sludge?
■ n n n
Is the drive unit operational?
■ n n n
Is the return rate acceptable (low turbulence)?
■ n n n
Is the overflow clear of excessive solids/pin floc?
■ n n n
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
■ n n n
Comment: Please refer to the attached inspection summary letter.
Lagoons
Yes No NA NE
Page # 4
FPermit: NC0029980
Inspection Date: 02/15/2010
Lagoons
Type of lagoons?
# Number of lagoons in operation at time of visit?
Are lagoons operated in?
# Is a re -circulation line present?
Is lagoon free of excessive floating materials?
# Are baffles between ponds or effluent baffles adjustable?
Are dike slopes clear of woody vegetation?
Are weeds controlled around the edge of the lagoon?
Are dikes free of seepage?
Are dikes free of erosion?
Owner -Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Are dikes free of burrowing animals?
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations?
# If excessive algae is present, has barley straw been used to help control the growth?
Is the lagoon surface free of weeds?
Is the lagoon free of short circuiting?
Comment: Please refer to the attached inspection summary letter.
Pump Station -Effluent
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment: Please refer to the attached inspection summary letter.
Flow Measurement- Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Facultative
4
Series
n n n ■
■ n n n
nnn■
■ n n n
■ n n n
■ n n n
■ n n n
■nnn
nnn■
■nnn
■nnn
■ n n n
Yes No NA NE
■nnn
■ n n n
■nnn
nnn■
■nnn
nnn■
Yes No NA NE
Page # 5
Permit: NCO029980 Owner -Facility: MillerCoors LLC
Inspection Date: 02/15/2010 Inspection Type: Compliance Evaluation
Flow Measurement - Effluent
Yes No NA NE
Comment: Please refer to the attached inspection summary letter.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
■ n n n
Are the receiving water free of foam other than trace amounts and other debris?
n n n ■
If effluent (diffuser pipes are required) are they operating properly?
n n ■ n
Comment: Please refer to the attached inspection summary letter.
Pumps-RASMAS
Yes No NA NE
Are pumps in place?
■ n n n
Are pumps operational?
■ n n n
Are there adequate spare parts and supplies on site?
■ n n n
Comment: Please refer to the attached inspection summary letter.
Solids Handling Equipment
Yes No NA NE
Is the equipment operational?
■ n n n
Is the chemical feed equipment operational?
■ n n n
Is storage adequate?
■ n n n
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
■ n n n
Is the site free of sludge buildup on belts and/or rollers of filter press?
■ n n n
Is the site free of excessive moisture in belt filter press sludge cake?
■ n n n
The facility has an approved sludge management plan?
n n n ■
Comment: Please refer to the attached inspection summary letter.
Chemical Feed
Yes No NA NE
Is containment adequate?
■ n n n
Is storage adequate?
■ n In n
Are backup pumps available?
n n n ■
Is the site free of excessive leaking?
■ n n n
Comment: Please refer to the attached inspection summary letter.
Operations & Maintenance
Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
■ n 00
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ n n n
Judge, and other that are applicable?
Page # 6
Permit: NCO029980
Inspection Date: 02/15/2010
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Operations & Maintenance
Yes No
NA
NE
Comment: Please refer to the attached inspection summary letter.
Permit
Yes No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
n n
■
n
Is the facility as described in the permit?
® n
n
n
# Are there any special conditions for the permit?
■ n
n
n
Is access to the plant site restricted to the general public?
■ n
n
n
Is the inspector granted access to all areas for inspection?
■ n
n
in
Comment: Please refer to the attached inspection summary letter.
Record Keeping
Yes No
NA
NE
Are records kept and maintained as required by the permit?
■ n
n
In
Is all required information readily available, complete and current?
■ n
n
n
Are all records maintained for 3 years (lab. reg. required 5 years)?
■ n
n
n
Are analytical results consistent with data reported on DMRs?
■ n
n
n
Is the chain -of -custody complete?
■ n
n
n
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
® n
n
n
Has the facility submitted its annual compliance report to users and DWQ?
n n
■
n
(If the facility is = or > 5 MGD permitted flow) Do they operate 2417 with a certified operator on each shift?
■ n
n
n
Is the ORC visitation log available and current?
® n
n
n
Is the ORC certified at grade equal to or higher than the facility classification?
® n
n
n
Is the backup operator certified at one grade less or greater than the facility classification?
■ n
n
n
Is a copy of the current NPDES permit available on site?
■ n
n
n
Facility has copy of previous year's Annual Report on file for review?
n n
■
n
Comment: Please refer to the attached inspection summary letter.
Laboratory
Yes No NA NE
Page # 7
Permit: NCO029980
Inspection Date: 02/15/2010
Owner -Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
11
Laboratory
Yes
NO
NA
Nt
Are field parameters performed by certified personnel or laboratory?
■
n
O
0
Are all other parameters(excluding field parameters) performed by a certified lab?
■
n
n
n
# Is the facility using a contract lab?
■
n
n
n
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees Celsius)?
■
n
n
n
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
n
n
n
■
Incubator (BCD) set to 20.0 degrees Celsius +/- 1.0 degrees?
n
n
n
■
Comment: Please refer to the attached inspection summary letter.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling Flow proportional?
■
n
n
n
Is sample collected below all treatment units?
■
n
n
Is proper volume collected?
■
n
n
n
Is the tubing clean?
n
n
■
o
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
■
n
n
n
Is the facility sampling performed as required by the permit (frequency, sampling type representative)?
■
n
n
n
Comment: Please refer to the attached inspection summary letter.
Upstream / Downstream Sampling
Yes
No
NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? ■
n
n
n
Comment: Please refer to the attached inspection summary letter.
Page # 8
Permit: NCG060112
SOC:
County: Rockingham
Region: Winston-Salem
Compliance Inspection Report
Effective: 11/01/07 Expiration: 10/31/12
Effective: Expiration:
Contact Person: Andrew C Lucas
Directions to Facility:
System Classifications:
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
24 hour contact name
On -site representative
Related Permits:
Andrew C Lucas
Andrew C Lucas
Title:
Certification:
Owner: Millercoors LLC
Facility: MillerCoors LLC
863 E Meadow Rd
Eden NC 272883636
Phone: 336-627-2592
Phone:
Phone: 336-627-2592
Phone: 336-627-2592
Inspection Date: 02/1512010 gEntime: 12.00 PM Exit Time: 01 00 PM
Primary Inspector: Ron Boone Phone: 704-663-1699
Ext.2202
Secondary lnspector(s): 6� /°�.� g. t) C
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Food/Tobacco/Soaps/Cosmetics/Public Warehousing
Stormwater Discharge COC
Facility Status: ■ Compliant Q Not Compliant
Question Areas:
■ Storm Water
(See attachment summary)
Page:1
Permit: NCG060112 Owner - Facility: Millercoors LLC
Inspection Date: 02/15/2010 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Please refer to the attached inspection summary letter.
Page:2
i7L
Permit: NCG060112 Owner - Facility: Millercoors LLC
Inspection Date: 02/15/2010 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Stormwater Pollution Prevention Plan Yes No NA NE
Does the site have a Stormwater Pollution Prevention Plan? ■ n n n
# Does the Plan include a General Location (LISGS) map? ■ n n n
# Does the Plan include a "Narrative Description of Practices"? ■ n n n
# Does the Plan include a detailed site map including outfall locations and drainage areas? ■ n n n
# Does the Plan include a list of significant spills occurring during the past 3 years? ■ n n n
# Has the facility evaluated feasible alternatives to current practices? ■ n n n
# Does the facility provide all necessary secondary containment? ■ n n n
# Does the Plan include a BMP summary? ■ n n n
# Does the Plan include a Spill Prevention and Response Plan (SPRP)? ■ n n n
# Does the Plan include a Preventative Maintenance and Good Housekeeping Plan? ■ n n n
# Does the facility provide and document Employee Training? ■ n n n
# Does the Plan include a list of Responsible Party(s)? ■ n n n
# Is the Plan reviewed and updated annually? ®❑
# Does the Plan include a Stcrmwater Facility Inspection Program? ■ n n n
Has the Stormwater Pollution Prevention Plan been implemented? ■ n n n
Comment: Please refer to the attached inspection summary letter
Qualitative Monitoring
Yes
No
NA
NE
Has the facility conducted its Qualitative Monitoring semi-annually'?
■
n
n
n
Comment: Please refer to the attached inspection summary letter.
Analytical Monitoring
Yes
No
NA
NE
Has the facility conducted its Analytical monitoring?
■
n
n
n
# Has the facility conducted its Analytical monitoring from Vehicle Maintenance areas?
■
n
n
n
Comment: Please refer to the attached inspection summary letter.
Permit and Outfalls
Yes
No
NA
NE
# Is a copy of the Permit and the Certificate of Coverage available at the site?
■
n
n
n
# Were all outfalls observed during the inspection?
■
n
n
n
# If the facility has representative outfall status, is it properly documented by the Division?
■
n
n
n
# Has the facility evaluated all illicit (non stormwater) discharges?
■
n
n
n
Comment: Please refer to the attached inspection summary letter
Page3
ppppppp�
Beverly Eaves Perdue
Governor
ALT'T4;_WVWA
__I__
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Coleen H. Sullins
Director
December 22, 2009
5107
Mr. Kurt Cranson
Miller Brewing Company
863 East Meadow Road
Eden, NC 27288-
SUBJECT: North Carolina Wastewater/Groundwater Laboratory Certification Renewal
FIELD PARAMETERS ONLY
Dear Mr. Cranson :
do�-
RECEIVED
N.C. Deott of ENR
i
DEC 2 8 2M
Winston-Salem
Regional Office
Dee Freeman
Secretary
The Department of Environment and Natural Resources, in accordance with the provisions of NC GS 143-
215-.3 (a) (10), 15 NCAC 2H .0800, is pleased to renew certification for your laboratory to perform
specified environmental analyses required by EMC monitoring and reporting regulations 15 NCAC 2B
.0500, 2H .0900 and 2L .0100, .0200, .0300, and 2N .0100 through .0800.
Enclosed for your use is a certificate describing the requirements and limits of your certification. Please
review this certificate to insure that your laboratory is certified for all parameters required to properly meet
your certification needs.
Please contact us at 919-733-3908 if you have questions or need additional information.
Sincerely,
EN Z /1 11-11
Pat Donnelly
Certification Branch Manager
Laboratory Section
Enclosure
cc: Ramon L. Cook
Dana Satterwhite
Winston-Salem Regional Office
DENR DWQ Laboratory Section NC Wastewater/Groundwater Laboratory Certification Branch
1623 Mail Service Center, Raleigh, North Carolina 27699-1623 One
Location: 4405 Reedy Creek Road. Raleigh, North Carolina 27607-6445 NorthCarolina
Phone: 919-733-39081 FAX: 919-733-6241
Internet: www.dwglab.org aturall
An Equal Opportunity\ Affirmative Action Employer Customer Service:1-877-623-6748 www.ncwaterquality.org
STATE OF NORTH CAROLINA DEPARTMENT OF THE
ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
LABORATORY CERTIFICATION PROGRAM
In accordance with the provisions ofN.C.G.S. 143-215.3 (a) (1), 143-215.3 (a)(10) and NCAC 2H.0800:
2010
MILLER BREWING COMPANY
Is hereby certified to perform environmental analysis as listed on Attachment I and report monitoring data to DWQ for
compliance with NPDES effluent, surface water, groundwater, and pretreatment regulations.
By reference 15A NCAC 2H .0800 is made a part of this certificate.
This certificate does not guarantee validity of data generated, but indicates the methodology, equipment, quality control procedures,
records, and proficiency of the laboratory have been examined and found to be acceptable.
This certificate shall be valid until December 31, 2010
Certificate No 5107
Pat Donnelly
ppppp,p-
Attachment I
North Carolina Wastewater/Groundwater Laboratory Certification
Certified Parameters Listing
Lab Name: Miller Brewing Company Certificate Number: 5107
Address: 863 East Meadow Road Effective Date: 01/01/2010
Eden, NC 27288- Expiration Date: 12/31/2010
Date of Last Amendment:
The above named laboratory, having duly met the requirements of 15A NCAC 2H.0800, is hereby certified for the measurement of the parameters listed below.
I CERTIFIED PARAMETERS
INORGANICS
DISSOLVED OXYGEN
Std Method 4500 O G
pH
Std Method 4500 H B
TEMPERATURE
Std Method 2550E
This certification requires maintance of an acceptable quality assurance program, use of approved methodology, and satisfactory performance on evaluation samples. Laboratories are
subject to civil penalties and/or decertification for infractions as set forth in 15A NCAC 2H.0807.
PPPPFP'
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Coleen H. Sullins Dee Freeman
Governor Director Secretary
September 8, 2009
Mr. Kurt Cranson, Environmental Coordinator
MillerCoors, LLC
863 East Meadow Road
Eden, NC 27288
SUBJECT: Chronic Effluent Toxicity Test Results
Miller Brewing Company
Wastewater Treatment Facilities
NPDES Permit NCO029980/001
Rockingham County
Dear Mr. Cranson,
The attached memorandum summarizes the test results of a bioassay performed by Miller Brewing
Company staff and picked up by Ms. Jenifer Carter of the Winston-Salem Regional Office during the
week of August 11, 2009.
The test used Ceriodaphnia dubia as the test organism. The test result was a pass in 2.1% effluent
concentration. The test information is found in the memorandum.
Should you have any questions, please contact Jenifer Carter in our office at (336) 771-4957.
Cc: &WSRO Files
SWP Central Files
Mr. Harry D. Hudgins (same address)
Joni Carolina Division of Water Quaiity, VVinston-Salem Regional Office
Location: 585 Itdaughicwn St. >rJinston-Salem, North Carolina 27107
?hone: 336-771 500J! FAX: 336-771-4630 i Customer Smice 1-877-623-6748
Internet: w,am.nmaterquaiity.org
Sincerely,
tom®
Steve W. Tedder
Surface Water Regional Supervisor
Winston-Salem Regional Office
Division of Water Quality
North Carolina
Naturally
�al0- * uF!!p' A9linlatv2Acri,n c.rnjf r
Division of Water Quality
September 1, 2009
MEMORANDUM
To: Steve Tedder
Regional Supervisor, Surface Water Protection, WSRO
Through: Cindy A. Moore C
Supervisor, Aquatic Toxicology Unit
From: Carol Hollenkamp ('(
Quality Assurance Officer, Aquatic Toxicology Unit
Subject: Whole effluent toxicity test results
Miller Brewing Company
NPDES Permit # NC0029980/001
Rockingham County
The aquatic toxicity test using flow -proportional 24-hour composite samples of effluent discharged from
Miller Brewing Company has been completed. Miller Brewing Co. has a permitted effluent discharge of
5.2 MGD entering the Dan River (7Q 10 of 313.0 CFS). Whole effluent samples were collected on August
11 and August 16 by a Miller Brewing Co. facility representative and then picked up by Jenifer Carter for
use in a chronic Ceriodaphnia dubia pass/fail toxicity test. The test using these samples resulted in a pass.
Toxicity information follows.
Test Type
Test Concentrations
Test Result
Control Survival
Control Mean Reproduction
Test Treatment Survival
Treatment Mean Reproduction
First Sample pH
First Sample Conductivity
First Sample Total Residual Chlorine
Second Sample pH
Second Sample Conductivity
Second Sample Total Residual Chlorine
3-Brood Ceriodaphnia dubia pass/fail
2.1 % sample
Pass
100%
31.8
100%
32.0
8.58 SU
1667 micromhos/cm
<0.1 mg/L
8.55 SU
1636 micromhos/cm
<0.1 mg/L
Test results for the above samples indicate that the effluent would not be predicted to have water quality
impacts on receiving water. These samples were split and sent to Meritech, the contract laboratory used by
Miller Brewing Co. The chronic Ceriodaphnia dubia pass/fail toxicity test run by Meritech also resulted in
a pass. Please contact us if further effluent toxicity monitoring is desired. We may be reached at (919)
743-8401.
Basin: ROA 03
cc: Central Files
Jenifer Carter, WSRO
Aquatic Toxicology Unit Environmental Sciences Section
2a�
0 MillerCoors
January 13, 2009
NCDENR Division of Water Quality
585 Waughtown Street
Winston Salem, NC 27107
Attn: Mr. Steve Tedder
Re: Response to NPDES Inspection on December 3, 2008
MillerCoors Facility, 863 E. Meadow Rd. Eden, NC 27288
Mr. Tedder:
RECEIVED
a " Dept. of ENR
JAN1y2a
nston.galem
regional pryy�
As requested, I am responding to your Compliance Evaluation Inspection letter dated December
15, 2008, with the compliance schedule for items 8(a) through 8(c).
Item 8(a) - MillerCoors will update the Stormwater Pollution Prevention Plan (SP3) general location
map to include longitude and latitudes for each outfall, names of receiving streams, and whether or not
any of the receiving waters are present on the 303(d) list of impaired waters by 2/15/09.
Item 8(b) - Details will be added to the site drawing to delineate separate drainage areas on the
site and estimates will be made as to what percent of the site is impervious by 2/15/09.
Item 8(c) - MillerCoors will maintain the SP3 review/update log and significant spill listing
specified in the letter and will recertify the Stormwater Discharge Outfalls as part of the annual
review. These items will be completed by 2/15/09.
In addition, I will follow up on the other items noted in the inspection by the appropriate due
dates.
• MillerCoors will update plant description for the next NPDES permit cycle to include the
process details as requested (expires April 30, 20012).
• MillerCoors is currently seeking a wastewater ORC to replace Harry Hudgins who will
be retired effective February 01, 2009. Back Up ORC, Bobby Jones will fill in
temporarily while we seek a permanent replacement. Once that position has been filled
we will submit a completed operator designation form within the required 120 days with
the required information.
If you have any questions regarding this implementation schedule, please contact me at 336-627-2592.
Sincerely,
"U
Kurt Cranson, CHMM
Environmental Coordinator
MillerCoors - Eden, NC
0
�0� wa0
r
� Y
CERTIFIED MAIL
RETURN RECEIPT REQUESTED
7008-0150-0002-7876-9352
Michael F. Easley, Governor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
15 December 2008
Mr. Kurt Cranson, Environmental Coordinator
MillerCoors, LLC
863 East Meadow Road
Eden, NC 27288
Subject: Compliance Evaluation Inspections
Individual NPDES Wastewater Discharge Permit NCO029980 &
General NPDES Stormwater Discharge Permit NCG060112
MillerCoors, LLC
Rockingham County
Dear Mr. Cranson:
Coleen H. Sullins, Director
Division of Water Quality
1. Mr. Ron Boone of the Winston-Salem Regional Office of the Division of Water Quality (DWQ)
conducted wastewater and stormwater compliance evaluation inspections (CEI) of the
MillerCoors, LLC facility located at 863 East Meadow Road, in Eden, Rockingham County, North
Carolina, on 3 December 2008. Your assistance and cooperation, as well as that of Mr. Harry
Hudgins, Operator in Responsible Charge (ORC) of the wastewater treatment plant, were greatly
appreciated. Inspection findings are summarized below and inspection reports are attached for
your records.
Individual NPDES Wastewater Discharge Permit NCO029980
2. The MillerCoors wastewater treatment plant (WWTP) discharges into receiving waters known as
the Dan River, this section of which is currently classified as Class C waters in the Roanoke River
basin. The plant consists of influent screw lift pumps, a bar screen, a grit chamber, neutralization,
flow equalization, extended aeration basins, secondary clarifiers, nutrient addition, polishing
lagoons and aerobic digestion. Some of these components/processes, such as neutralization and
equalization, are only used on an as needed basis, as flows from the manufacturing facility
change. The plant also has an effluent flow meter, which is used for flow reporting, and a sludge
press along with lime and ferric chloride addition for sludge dewatering before it is land applied.
Neither the flow meter nor the press and chemical process is included in the plant description of
the permit. Please ensure these components are added to the plant description during the next
permit renewal cycle, along with any other plant components that should be added to the
description.
Documentation Review
3. Mr. Boone evaluated laboratory data and all required records were available and complete.
Comparison of lab reports with discharge monitoring reports (DMR) revealed no transcription
errors and chains of custody were also complete. All lab records were well organized. The plant
lab's certification for field laboratory tests is current. The plant has had no limit violations over the
12 months previous to the inspection.
North Carolina Division of Water Quality 585 Waughtown Street; Winston-Salem, NC 27107 Phone (336) 771-5000
Customer Service: 1-877-623-6748 Internet: www.ncwaterquality.org Fax (336) 7714630
An Equal Opportunity/Affirmative Action Employer — 50% Recycled/10% Post Consumer Paper
r�
`r
t
Mr. Kurt Cranson
15 December 2008
Page 2 of 3
4. Daily operator visitation records were complete and current. Records of plant operations and
maintenance were also available, complete and current. All records must be maintained for a
period of three years, with the exception of laboratory records, which must be kept on file for a
minimum of five years.
Site Review
5. Most plant components were operational during the inspection except for two of the clarifiers,
which were down for maintenance/repair. Several of the aeration basins were also shut down.
None of these units are needed to meet permit limits; only a portion of the plant's capacity is
currently required to treat the influent flow. One aeration basin is actually used as an aerobic
digester and others are used for flow equalization and/or neutralization as needed. The plant is
well operated and maintained. No discrepancies were noted.
6. It was discussed during the inspection that Mr. Hudgins will soon be retiring from service. Please
note that MillerCoors must designate a new ORC for the plant within 120 calendar days following
Mr. Hudgins vacating the position. You must do so by submitting a properly filled out and signed
operator designation form to the Division's Technical Assistance and Certification Unit (TACU).
Additionally, Mr. Hudgins must personally notify the TACU and the appropriate regional office
within 14 calendar days of vacating the position.
General NPDES Stormwater Discharae Permit NCG060112
7. Stormwater related to industrial activity is discharged from this site to an unnamed tributary to Dry
Creek, which is currently classified as Class C waters in the Roanoke River Basin. The site
currently has four stormwater discharge outfalls (SDO), only one of which is currently monitored
analytically due to MillerCoors being granted representative outfall status (ROS) in March 1994.
Consequently, MillerCoors analytically monitors only SDO 004. Furthermore, no conditions were
noted during the inspection that brought into question the validity of ROS for this site. The entire
site was clean and well maintained. All four SDOs were inspected and the receiving waters
exhibited no adverse effects from stormwater discharges.
Documentation Review
8. The Stormwater Pollution Prevention Plan (SP3) was reviewed and the following discrepancies
were noted:
a. The general location map (GLM) does not show accurate latitudes/longitudes for each of the
SDOs, the receiving stream is not labeled and the map does not indicate the whether the
receiving stream is impaired according to the state's 303(d) list of impaired waters. Please
refer to Part II, Section A, Paragraph 1(a) for further details on these requirements.
b. The site map does not delineate separate drainage areas for the site and does not indicate
the percentage of each drainage area that is impervious.
c. The SP3 was originally written in November 1997 and reviews/updates have not been
properly recorded. The SP3 should include a review/update log on which the required
annual reviews and associated updates are annotated. In addition, the permit now requires
that you update the list of significant spills or make an annotation that no spills have
occurred and recertify the SDOs in accordance with Part II, Section A, Paragraph 1(e), as
part of the annual review. Please note that the certification of the outfalls is a requirement
V
rt Cranson
cember 2008
3 of 3
separate from analytical monitoring, although nothing precludes you from performing the
tasks simultaneously, as long as all documentation requirements are met.
All other components of the SP3 were found to be compliant.
9. Analytical and qualitative monitoring records for 2008 were reviewed. No discrepancies were
noted and no benchmarks were exceeded. It is again noted that the facility has ROS and
analytically monitors only SDO 004, but still qualitatively monitors all four SDOs, as required by
the permit. No vehicle maintenance is performed at the site.
10. We greatly appreciate your cooperation in the inspection process and your efforts to meet the
requirements of both the wastewater and stormwater permits. Please reply to this letter in writing
within 30 days of receiving it. Your response should include a corrective action plan with
implementation schedule for each of the discrepancies noted above in paragraphs 8(a) through
8(c). If you have any questions regarding the inspection or this letter, please do not hesitate to
contact Mr. Boone or me at (336) 771-5000.
Sincerely,
Steve W. Tedder
Water Quality Regional Supervisor
Winston-Salem Region
Division of Water Quality
Attachments:
1. BIMS Inspection Report NCO029980
2. BIMS Inspection Report NCG060112
cc: WSRO — SWP w/ atch
Central Files w/ atch
NPDES West Unit
Stormwater Permitting Unit w/ atch
71
United States Environmental Protection Agency
Form Approved.
EPAWashington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 11 NI 2 15I 31 N00029980 111 121 08/12/03 117 18LCI 19I� 20I II
Remarks
2111111111Jill Jill 11111111111111111111111111111116
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 CIA --------------------------- Reserved ----------------------
67I 169 701 I 711 I 72I N I 73 W 74 751 I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
Mi1lerCoors LLC
11:00 AM 08/12/03
07/08/01
Exit Time/Date
Permit Expiration Date
863 E Meadow Rd
Eden NC 27288
05:00 PM 08/12/03
12/04/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Kurt Cranson,863 E Meadow Rd Eden NC 27288//336-627-2592/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone WSRO WQ//704-663-1699 Ext.2202/
Signature of Mana ement Q A Revie r Agency/Office/Phone and Fax Numbers Date
p
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES yr/mo/day Inspection Type
3I NCO029980 I11 12I 08/12/03 I17 18ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Please refer to attached inspection summary letter.
Page # 2
Permit: NCO029980 Owner -Facility: MillerCoors LLC
Inspection Date: 12/03/2008 Inspection Type: Compliance Evaluation
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit? ■ ❑ ❑ ❑
Is all required information readily available, complete and current? ■ ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
❑
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
❑
■
❑
❑
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
■
❑
❑
❑
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
■
❑
Comment: Permittee has exemption from the 24/7 ops requirement in the permit.
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
■
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
■
❑
❑
❑
# Is the facility using a contract lab?
■
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
■
❑
❑
❑
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
■
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
■
❑
Comment:
Permit
Yes
No
NA
NE
Page # 3
Permit: NC0029980 Owner - Facility: MillerCoors LLC
Inspection Date: 12/03/2008 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application? ❑ ❑ ■ Cl
Is the facility as described in the permit? ❑ ■ ❑ ❑
# Are there any special conditions for the permit? ❑ ■ ❑ ❑
Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? ■ ❑ ❑ ❑
Comment: Plant description needs to be updated as specified in the inspection
summary letter.
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Yes No NA NE
Permit: NCO029980
Inspection Date: 12/03/2008
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment:
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Owner - Facility: MillerCoors LLC
Inspection Type: Compliance Evaluation
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/. of the sidewall depth)
Comment:
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Yes No NA NE
■ ❑ ❑ ❑
In ❑ ❑ ❑
Yes No NA NE
Ext. Air
Diffused
■ ❑ ❑ ❑
■❑❑❑
Page # 5
,11
Permit: NC0029980 Owner - Facility: MillerCoors LLC
Inspection Date: 12/03/2008 Inspection Type: Compliance Evaluation
Pumps-RAS-WAS Yes No NA NE
Are there adequate spare parts and supplies on site? ■ C3 0 ❑
Comment:
Lagoons
Yes
No
NA
NE
Type of lagoons?
Aerated
# Number of lagoons in operation at time of visit?
2
Are lagoons operated in?
Series
# Is a re -circulation line present?
Q
❑
■
Is lagoon free of excessive floating materials?
■
❑
n
# Are baffles between ponds or effluent baffles adjustable?
0
Q
■
Q
Are dike slopes clear of woody vegetation?
■
O
0
Q
Are weeds controlled around the edge of the lagoon?
■
n
0
O
Are dikes free of seepage?
■
❑
Q
Q
Are dikes free of erosion?
■
Q
❑
Are dikes free of burrowing animals?
■
0
11
❑
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple locations?
❑
Q
■
# If excessive algae is present, has barley straw been used to help control the growth?
■13
O
Q
Is the lagoon surface free of weeds?
■
O
Q
Q
Is the lagoon free of short circuiting?
■
Q
Q
0
Comment: Barley straw has been in use for quite some time and is controlling algae
very effectively.
Pump Station - Effluent
Yes
No
NA
NE
Is the pump wet well free of bypass lines or structures?
■
n
n
n
Are all pumps present?
■
Q
Q
Are all pumps operable?
■
Q
❑
Q
Are float controls operable?
■
O
Q
Is SCADA telemetry available and operational?
Cl
❑
■
Is audible and visual alarm available and operational?
❑
Q
■
0
Comment:
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
■
Q
Q
Q
Page # 6
C
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 12/03/2008 Inspection Type: Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Is flow meter calibrated annually? ■ ❑ ❑ ❑
Is the flow meter operational?
■
❑ ❑
❑
(If units are separated) Does the chart recorder match the flow meter?
■
❑
❑
❑
Comment:
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
■
❑
❑
❑
Is sample collected below all treatment units?
■
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
■
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
MOOO
Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ❑ ❑ ❑
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? ■ ❑ ❑ ❑
Comment:
Aerobic Digester
.es
no
NA
nt
Is the capacity adequate?
■
❑
❑
❑
Is the mixing adequate?
■
❑
❑
❑
Is the site free of excessive foaming in the tank?
■
❑
❑
❑
# Is the odor acceptable?
■
❑
❑
❑
# Is tankage available for properly waste sludge?
■
❑
❑
❑
Comment:
Chemical Feed
Yes
No
NA
NE
Is containment adequate?
■
❑
❑
❑
Is storage adequate?
■
❑
❑
❑
Are backup pumps available?
■
❑
❑
❑
Is the site free of excessive leaking?
■
❑
❑
❑
Comment:
Solids Handling Equipment
Yes
No
NA
NE
Is the equipment operational?
■
❑
❑
❑
Page # 7
Permit: NCO029980 Owner - Facility: MillerCoors LLC
Inspection Date: 12/03/2008 Inspection Type: Compliance Evaluation
Solids Handling Equipment Yes No NA NE
Is the chemical feed equipment operational? ■ ❑ ❑ ❑
Is storage adequate?
■
❑
❑
❑
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
■
❑
❑
❑
Is the site free of sludge buildup on belts and/or rollers of filter press?
■
❑
❑
❑
Is the site free of excessive moisture in belt filter press sludge cake?
■
❑
❑
❑
The facility has an approved sludge management plan?
❑
❑
❑
■
Comment:
Operations & Maintenance
Yes
No
NA
NE
Is the plant generally clean with acceptable housekeeping?
■
❑
❑
❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ ❑ ❑ ❑
Judge, and other that are applicable?
Comment:
Page # 8
Compliance Inspection Report
Permit: NCG060112 Effective: 11/01/07 Expiration: 10/31/12 Owner: Millercoors LLC
SOC: Effective: Expiration: Facility: MillerCoors LLC
County: Rockingham 863 E Meadow Rd
Region: Winston-Salem
Eden NC 27288
Contact Person: Deon Van AS Title: Phone: 336-627-2592
Directions to Facility:
System Classifications:
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 12/03/2008 UEnime: 11:00 AM
Primary Inspector: Ron Boone
Secondary Inspector(s):
Certification: Phone:
Exit Time: 01:30 PM
Phone:704-663-1699
Ext.2202
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Food/Tobacco/Soaps/Cosmetics/Public Warehousing
Stormwater Discharge COC
Facility Status: ❑ Compliant ■ Not Compliant
Question Areas:
0 Storm Water
(See attachment summary)
C
Page: 1
Permit: NCG060112 Owner - Facility: Millercoors LLC
Inspection Date: 12/03/2008 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Please see attached inspection summary letter.
Page: 2
Permit: NCG060112 Owner - Facility: Millercoors LLC
Inspection Date: 12/03/2008 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Stormwater Pollution Prevention Plan Yes No NA NE
Does the site have a Stormwater Pollution Prevention Plan?
■ ❑ ❑
❑
# Does the Plan include a General Location (USGS) map?
■
❑
❑
❑
# Does the Plan include a "Narrative Description of Practices"?
■
❑
❑
❑
# Does the Plan include a detailed site map including outfall locations and drainage areas?
■
❑
❑
❑
# Does the Plan include a list of significant spills occurring during the past 3 years?
■
❑
❑
❑
# Has the facility evaluated feasible alternatives to current practices?
■
❑
❑
❑
# Does the facility provide all necessary secondary containment?
■
n
n
n
# Does the Plan include a BMP summary?
■
❑
❑
❑
# Does the Plan include a Spill Prevention and Response Plan (SPRP)?
■
❑
❑
❑
# Does the Plan include a Preventative Maintenance and Good Housekeeping Plan?
■
❑
❑
❑
# Does the facility provide and document Employee Training?
■
n
❑
❑
# Does the Plan include a list of Responsible Party(s)?
■
❑
❑
n
# Is the Plan reviewed and updated annually?
■
❑
❑
❑
# Does the Plan include a Stormwater Facility Inspection Program?
■
❑
❑
❑
Has the Stormwater Pollution Prevention Plan been implemented?
■
❑
❑
❑
Comment: Some minor discrepancies were noted with the general location map, site
map and the annual reviews as noted in the attached inspection summary letter.
Qualitative Monitoring
Yes
No
NA
NE
Has the facility conducted its Qualitative Monitoring semi-annually?
■
❑
❑
❑
Comment:
Analytical Monitoring
Yes
No NA
NE
Has the facility conducted its Analytical monitoring?
■
❑ ❑
❑
# Has the facility conducted its Analytical monitoring from Vehicle Maintenance areas?
❑
❑ ■
❑
Comment:
Permit and Outfalls
Yes
No NA
NE
# Is a copy of the Permit and the Certificate of Coverage available at the site?
■
❑ ❑
n
# Were all outfalls observed during the inspection?
■
❑ ❑
❑
# If the facility has representative outfall status, is it properly documented by the Division?
■
❑ ❑
❑
# Has the facility evaluated all illicit (non stormwater) discharges?
■
n n
n
Comment:
'IN
Page: 3
Harry D. Hudgins
4958 Morgan Ford Road
Ridgeway, VA 24148
(276) 956-4813
Technical Assistance & Certification Unit
1618 Mail Service Center
Raleigh, NC 27699-1618
RECEIVED
N.C. Deot. of ENR
JAN 1 2 !!0
9Winston-Sa
Regional Office
i
Due to my retirement, effective immediately I will no longer be Operator in
Responsible Charge of the Wastewater Treatment Plant at MillerCoors located at 863 E
Meadow Road in Eden, NC. (NPDES # NC0029980)
Thank you.
Harry 4HIH-luns
Ron Boone
585 town Street
mston Salem, NC 27107
December 19, 2008
5107
Mr. Kurt Cranson
Miller Brewing Company
863 East Meadow Road
Eden, NC 27288-
/197—
Michael F. Easley, Governor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
SUBJECT: Wastewater/Groundwater Laboratory Certification Renewal
FIELD PARAMETERS ONLY
Dear: Mr. Cranson
Coleen H. Sullins, Director
Division of Water Quality
REC1
JAN G ? �,,,4
h i n. tun-4wern
Regional Of e
The Department of Environment and Natural Resources, in accordance with the provisions of NC GS 143-215-.3
(a) (10), 15 NCAC 2H .0800, is pleased to renew certification for your laboratory to perform specified
environmental analyses required by EMC monitoring and reporting regulations 15 NCAC 2B .0500, 2H .0900 and
2L .0100, .0200, .0300, and 2N .0100 through .0800.
Enclosed for your use is a certificate describing the requirements and limits of your certification. Please review
this certificate to insure that your laboratory is certified for all parameters required to properly meet your
certification needs.
Please contact us at 919-733-3908 if you have questions or need additional information.
Sincerely,
Pat Donnelly
Certification Branch Manager
Laboratory Section
Enclosure
cc: Ramon L. Cook
Dana Satterwhite
Winston-Salem Regional Office
NNo hcarolina
aturally
Laboratory Section 1623 Mail Service Center; Raleigh, NC 27699-1623 Phone (919) 733-3908
Location: 4405 Reedy Creek Road; Raleigh, NC 27607 FAX (919) 733-6241
Internet: www.dwgfab.org Customer Service 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer — 50% Recycled110% Post Consumer Paper
STATE OF NORTH CAROLINA DEPARTMENT OF THE
ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
LABORATORY CERTIFICATION PROGRAM
In accordance with the provisions of N.C.G.S. 143-215.3 (a) (1), 143-215.3 (a)(10) and NCAC 2H.0800:
Field Parameter Only
00
0
MILLER BREWING COMPANY
Is hereby certified to perform environmental analysis as listed on Attachment I and report monitoring data to DWQ for
compliance with NPDES effluent, surface water, groundwater, and pretreatment regulations.
By reference 15A NCAC 2H .0800 is made a part of this certificate.
This certificate does not guarantee validity of data generated, but indicates the methodology, equipment, quality control procedures,
records, and proficiency of the laboratory have been examined and found to be acceptable.
This certificate shall be valid until December 3311, 2009
Certificate No. 5107 �. J
l/
Pat Donnelly
Attachment
PPPPPPP' North Carolina Wastewater/Groundwater Laboratory Certification
Certified Parameters Listing
FIELD PARAMETERS ONLY
Lab Name: Miller Brewing Company Certificate Number: 5107
Address: 863 East Meadow Road Effective Date: 01/01/2009
Eden, NC 27288- Expiration Date: 12/31/2009
Date of Last Amendment:
The above named laboratory, having duly met the requirements of 15A NCAC 21-1.0800, is hereby certified for the measurement of the parameters listed below.
CERTIFIED PARAMETERS
INORGANICS
DISSOLVED OXYGEN
Std Method 4500 O G
pH
Std Method 4500 H B
TEMPERATURE
Sid Method 2550E
This certification requires maintance of an acceptable quality assurance program, use of approved methodology, and satisfactory performance on evaluation samples. Laboratories are
subject to civil penalties and/or decertification for infractions as set forth in 15A NCAC 2H.0807.
\NArF9
P
--I
)aM'_
Michael F. Easley, Governor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Coleen H. Sullins, Director
Division of Water Quality
July 28, 2008
u�
5107 !Mr.L 2 Kurt Cranson winston Salem
Miller Brewing Company LRegional pff�
863 East Meadow Road
Eden, NC 27288-
SUBJECT: North Carolina Wastewater/Groundwater Laboratory Certification (NC WW/GW LC)
Laboratory Certification Maintenance Inspection
Dear Mr. Cranson :
Enclosed is a report for the inspection performed on July 8, 2008 by Mr. Ramon Cook.
Where finding(s) are cited in this report, a response is required. Within thirty days of receipt,
please supply this office with a written item for item description of how these finding(s) were
corrected. If the finding(s) cited in the enclosed report are not corrected, enforcement actions
may be recommended. For certification maintenance, your laboratory must continue to carry
out the requirements set forth in 15A NCAC 2H .0800.
Copies of the checklists completed during the inspection may be requested from this
office. Thank you for your cooperation during the inspection. If you wish to obtain an electronic
copy of this report by email or if you have questions or need additional information, please
contact us at 919-733-3908.
Sincerely,
D J
(Yana S erwhite
Certification Unit Supervisor
Laboratory Section
Enclosure
cc: Ramon Cook
Winston-Salem Regional Office
Nose Carolina
hrra!!y
North Carolina Division of Water Quality 1623 Mail Service Center Raleigh, NC 27699-1623 Phone (919) 733-3908
Internet: www.dwqlab.org Location: 4405 Reedy Creek Rd Raleigh, NC 27607 Fax (919) 733-6241
An Equal Opportunity/Affirmative Action Employer — 50% Recycled/10% Post Consumer Paper
Customer Service
1-877-623-6748
LABORATORY NAME:
NPDES PERMIT #:
ADDRESS:
CERTIFICATE #:
DATE OF INSPECTION:
TYPE OF INSPECTION:
AUDITOR(S):
On -Site Inspection Report
Miller Brewing Company
NCO029980
863 East Meadow Road
Eden, NC 27728
5107
July 8, 2008
Field Maintenance
Ramon Cook
LOCAL PERSON(S) CONTACTED: Kurt Cranson
I. INTRODUCTION:
IV.
This laboratory was inspected to verify its compliance with the requirements of 15A NCAC 2H .0800 for the
analysis of environmental samples.
GENERAL COMMENTS:
The laboratory is spacious and well equipped. All facilities and instrumentation are well maintained.
Comment: Finding A is a new policy that has been implemented by our program since the last inspection.
FINDINGS, REQUIREMENTS, COMMENTS AND RECOMMENDATIONS:
Temperature — Standard Methods, 20"' Edition, 2550 B
A. Finding: The temperature correction factors were not documented on any of the
thermometers/meters in use.
Requirement: All thermometers and temperature measuring devices must be checked every
12 months against a NIST certified or NIST traceable thermometer and the process
documented. To check a thermometer or the temperature sensor of a meter, read the
temperature of the thermometer/meter against a NIST certified or NIST traceable thermometer
and record the two temperatures. The thermometer/meter readings must be less than or equal
to 10C from the NIST certified or NIST traceable thermometer reading. (NC
Wastewater/Groundwater Laboratory Certification Policy). The documentation must include the
serial number of the NIST certified thermometer or NIST traceable thermometer that was used
in the comparison. Also document any correction that applies on both the
thermometer/meter and on a separate sheet to be filed.
PAPER TRAIL INVESTIGATION:
The paper trail consisted of comparing field testing records and contract lab reports to Discharge
Monitoring Reports (DMRs) submitted to the North Carolina Division of Water Quality. Data were
reviewed for the following months: March, April and May, 2008. No transcription errors were detected.
The facility appears to be doing a good job of accurately transcribing data.
a
11er Brewing Company
CONCLUSIONS:
Correcting the above cited finding and implementing the recommendations will help this lab to produce
quality data and meet certification requirements. The inspector would like to thank the staff for its
assistance during the inspection and data review process. Please respond to all findings.
Report prepared by: Ramon L. Cook Date: July 11, 2008
Report reviewed by: Todd Crawford Date: July 15, 2008
RECEIVED
N.C. Dept, of ENR
JAN 0 7 2008
i
Winston-Salem
i Regicnal CIffice
January 4, 2008
NCDEHNR
Winston Salem Regional Office
585 Waughtown St.
Winsto - 241
r. David Russel
Re: oaming incident. December 31, 2007
Miller Brewing Company
Eden, NC 27288
Dear Mr. Russel:
On December 31, 2007 at approximately Sam Miller Brewing's ORC Harry Hudgins
notified Miller Management of a foaming issue that was observed at the influent screw
lift basin.
MBCO notified DQW Winston-Salem Regional Office at approximately 10 AM by
phone, and left you a message detailing the incident and that clean up had begun.
Most of the foam was on the pavement around the bar screen, grit box & grit chamber.
On the west side of bar screen the foam was on the grass about 15' down the hill,
however did not impact any surface waters or migrate off site.
The cause of this foaming was due to routine drain cleaning that was performed over the
holiday shutdown. The debris and built-up grime that was loosened during the cleaning
contained solidified conveyor lubricant that when agitated caused excessive foaming.
Corrective actions are being developed and put in place to minimize this occurrence in
the future. If you have any questions regarding this incident or more specific information
on corrective actions feel free to contact me at 336-627-2592 or by email at
cranson.kurt@mbco.com.
Sincerely
Kurt R. Cranson, CHMM
Environmental Coordinator
Miller Brewing Company
■ complete items 1, 2, and 3. Also complete
item 4 if Restricted Delivery is desired.
■ Print your name and address on the reverse
so that we can return the card to you.
■ Attach this card to the back of the mailpiece,
or on the front if space permits.
Article Addressed to:
Mr. Kurt Cranson
Miller -Coors, LLC
863 East Meadow Road
Eden, NC 27288
A. Signature
X P24"
B. Received by (Printed Name) I C.
❑ Agent
❑ Addresse(
D. Is delivery address different from item 1? ❑ Yes
If YES, enter delivery address below: ❑ No
3. Service Type
Certified Mail ❑ Express Mail
egistered ❑ Return Receipt for Merchandise
❑ Insured Mail ❑ C.O.D.
4. Restricted Delivery? (Extra Fee) ❑ Yes
2. An 7008 0150 0002 7876 �/
(Tr ---- 9352
l �i:� C"T
DS Form 3811, February 2004 Domestic Return Receipt / ^ , Ad& 102595-02-M-1541
Ak
UNITED S Tff
IT
0 Sender: Please print your name, address, and ZIP+4 in this box 0
NCDENR- Water Quality Section
6wile-
585 Waughtown Street
Winston-Salem, NC 27107
If I I I I If I I I I I I HII I I I I I If I I I It If I If I I I I I 1! 1 1 1 1 1 11 If III I I 1! 11 1I