HomeMy WebLinkAboutWQ0010828_Permit (Issuance)_19950508June 19, 1996
ROY L. RAMEY,MAYOR
VASS, TOWN-LINCOLN AVE REVITA
PO BOX 487
VASS, NC 28394
SUBJECT: CERTIFICATE OF COMPLETION
PERMIT NO. WQ0010828
VASS, TOWN-LINCOLN AVE REVITA
MOORE COUNTY
Dear Permittee:
On May 08, 1995 the Division of Environmental Management issued you
the subject permit. One of the conditions of the subject permit read as
follows:
Upon completion of construction and prior to operation of this permitted
facility, a certification must be received from a professional engineer
certifying that the permitted facility has been installed in accordance
with the requirements of this permit and the approved plans and
specifications. Mail certification to the Permits and Engineering Unit,
P.O. Box 29535, Raleigh, N.C., 27626-0535.
To date, our records show tha:.. no certification has been received for the
subject permit. If the permitted facility has been constructed and placed into
operation please submit the required certification immediately. Operation of
the treatment system prior to submission of the required certification is in
violation of your permit and is subject to enforcement action. If you have any
questions, please contact your consulting engineer for this project, HOBBS
UPCHURCH & ASSOC at (910)692-5616. If the facility has not been constructed,
please contact the Fayetteville Regional Office at (919)486-1541, so that they
can update their records.
Thank you for your prompt attention to this matter.
Sincerely,
Carolyn McCaskill, Supervisor
State Engineering Review Group
cc: File
Fayetteville Regional Office
State'of North Carolina
Department of Environment,
Health and Natural Resources
Division of Environmental Management
James B. Hunt, Jr., Governor
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
May 8, 1995
The Honorable Roy L. Ramey, Mayor
Town of Vass
Post Office Box 487
Vass, North Carolina 28394
Dear Mayor Ramey:
09WAA
IT
A&4
- - - - !Ll
EDEHNI=1
Subject: Permit No. WQ0010828
Town of Vass
Lincoln Avenue Revitalization
Sewer Extension
Moore County
In accordance with your application received March 27, 1995, we are forwarding herewith Permit
No. WQ0010828, dated May 8, 1995, to the Town of Vass for the construction and operation of the
subject wastewater collection extension.
This permit shall be effective from the date of issuance until rescinded and shall be subject to the
conditions and limitations as specified therein.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of
this permit. This request must be in the form of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, P.O. Drawer
27447, Raleigh, NC 27611-7447. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact Mr. Michael D. Allen at (919) 733-5083 ext. 547.
cc: Moore County Health Department
Fayetteville Regional Office, Water Quality Section
Hobbs, Upchurch & Associates, P.A.
Sincerely,
z1
Al. Prest Howard, Jr., P.E.
ttECETVEn
MAY 18 "
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-5083 FAX 919-733-9919
An Equal Opportunity Affirmative Action Employer 50% recycled/ 10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT, HEALTH AND NATURAL RESOURCES
RALEIGH
WASTEWATER COLLECTION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO THE
Town of Vass
Moore County
FOR THE
construction and operation of approximately 5,407 linear feet of 8-inch gravity sewer, an 80 GPM pump
station with duplex pumps, high water alarms, emergency generator, and approximately 1,371 linear feet
of 4-inch force main to serve twenty-two (22) 3-bedroom homes in the Lincoln Avenue Revitalization, and
the discharge of 7,920 GPD of collected domestic wastewater into the Moore Water and Sewer Authority's
existing sewerage system, pursuant to the application received March 27, 1995, and in conformity with the
project plan, specifications, and other supporting data subsequently filed and approved by the Department
of Environment, Health and Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until rescinded and shall be subject to the
following specified conditions and limitations:
1. This permit shall become voidable unless the facilities are constructed in accordance with the
conditions of this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. The facilities must be properly maintained and operated at all times.
4. The sewage and wastewater collected by this system shall be treated in the Moore Water and Sewer
Authority Wastewater Treatment Facility prior to being discharged into the receiving stream.
5. This permit is not transferable. In the event there is a desire for the facilities to change ownership,
or there is a name change of the Permittee, a formal permit request must be submitted to the
Division of Environmental Management accompanied by an application fee, documentation from
the parties involved, and other supporting materials as may be appropriate. The approval of this
request will be considered on its merits and may or may not be approved.
6. Construction of the sewers, pump station(s) and force main shall be scheduled so as not to
interrupt service by the existing utilities nor result in an overflow or bypass discharge of
wastewater to the surface waters of the State.
7. Upon completion of construction and prior to operation of this permitted facility, a certification
must be received from a professional engineer certifying that the permitted facility has been
installed in accordance with this permit, the approved plans and specifications, and other
supporting materials. Mail the Certification to the Water Quality Permits and Engineering Unit,
P.O. Box 29535, Raleigh, NC 27626-0535.
8. A copy of the approved plans and specifications shall be maintained on file by the Permittee for a
minimum of five years from the date of the completion of construction.
9. Failure to abide by the conditions and limitations contained in this permit may subject the Permittee
to an enforcement action by the Division of Environmental Management, in accordance with North
Carolina General Statute 143-215.6(a) to 143-215.6(c).
10. The issuance of this permit does not preclude the Permittee from complying with any and all
statutes, rules, regulations, or ordinances which may be imposed by other government agencies
(local, state, and federal) which have jurisdiction.
11. The Permittee shall provide for the pump station and force main the following items:
a. Pump on/off elevations located so that 2-8 pumping cycles may be achieved per hour in the
pump station,
b. An air relief valve located at all high points along the force main,
c. A screened vent for the wet well,
d. Fillets located in the wet well at the intersection of the flooring and sidewalls,
e. Three feet of cover (minimum) over the force main or the use of ferrous material where three
feet cannot be maintained,
f. Sufficient devices which will protect the pump station from vandals, and
g. Flood protection if the pump station is located below the 100-year flood elevation.
12. In the event that the facilities fail to perform satisfactorily, including the creation of nuisance
conditions, the Permittee shall take immediate corrective action, including those as may be required
by this Division, such as the construction of additional or replacement wastewater collection
facilities.
13. NONCOMPLIANCE NOTIFICATION:
The Permittee shall report by telephone to the Fayetteville Regional Office, telephone number (910)
486-1541, as soon as possible, but in no case more than 24 hours or on the next working day
following the occurrence or first knowledge of the occurrence of either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable
of adequate wastewater transport, such as mechanical or electrical failures of pumps, line
blockage or breakage, etc.; or
b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving
waters without treatment of all or any portion of the influent to such station or facility.
Persons reporting such occurrences by telephone shall also file a written report in letter form within
15 days following first knowledge of the occurrence. This report must outline the actions taken or
proposed to be taken to ensure that the problem does not recur.
14. This permit shall become voidable unless the agreement between the Town of Vass and the Moore
Water and Sewer Authority for the collection and final treatment of wastewater is in full force and
effect.
Permit issued this the eighth day of May, 1995
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
A. Preston oward, Jr., P.E., Director
Division of -Environmental Management
By Authority of the Environmental Management Commission
Permit Number WQ0010828
Permit No. WQ0010828
May 8, 1995
♦ •♦
I, , as a duly registered Professional Engineer in the State of North
Carolina, having been authorized to observe (periodically, weekly, full time) the construction of the
project,
Project Name
Location
for the
Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation
of the construction such that the construction was observed to be built within substantial compliance and
intent of this permit, the approved plans and specifications, and other supporting materials.
Signature
Date
Registration No.
2
Wi
MEMO TO: State Review Group
FROM: Ricky Revels P L3 g,
Environmental Technician IV
SUBJECT: Procedure Four (4)
WQ0010828
Lincoln Ave. Revitalization
Sewer Extension - Private
MOWASA/Town of Vass
Moore County
Division of Environmental
Management
Fayetteville Regional
Office
4/27/95
Date
State Review Group Review
Engineer Buzz Crosby
Regional Office
Contact Ricky Revels
1) Name of wastewater treatment plant to receive the wastewater:
Town of Vass Wastewater Treatment Plant
2) WWTP design capacity 0.060 MGD
3) NPDES Permit No.: NC0074373 Expiration Date: 5 31 96
4) Compliance Information:
Present treatment plant performance
for previous 12 months - beginning 3194
(See attached self -monitoring data)
5) Quantity and type of wastewater from proposed sewers:
7,920 GPD
domestic 100% industrial other
6) Volume from previously approved projects not yet tributary to
WWTP 28,400 GPD
7) Regional Recommendations: Approval X Denial
RR/rr
Enclosure
GKEXBB/MF:'
COMPLIANCE EVALUATION
ANALYSIS
REPORT
O4/26/95
PAGE i
PERMIT--NCO074373
PIPE--00i
REPORT
PERIOD,
9403-9502
LOC---
E
FACILITY--MOORE
WATER
AND
SEWER AUTH.
DESIGN FLOW--
.0600
CLASS--2
LOCATION--VASS
REGION/COUNTY--06
MOORE
50050
803i0
00530
006i0
316i6
50060
000i8
0040O
MONTH
Q/MGD
BOD
RE%/T%% NH3+NH4-
FEC COLI
CHLORINE
TEMP
PH
LIMIT F
.0600
F 30.00
F 30.0
NOL
F 200.0
NOL
NOL
9.0 6.0
94/03
.0033
3.78
3.0
.15
40.3
.386
13.69
7.7-6.3
94/04
.0025
6.07
4.8
is
4i.3
.327
i9.04
7.5-6.8
/05
.0027
3.20
2.6
1.03
ii.9
.375
2i.45
7.8-6.7
/06
.0022
3.60
3.2
.i4
10.O
25.66
7.2-6.5
94/07
.00i8
2.75
2.0
.16
i0.0
26.50
7.i-7.0
94/08
.0022
3.26
2.4
.i5
ii.6
25.00
7.1-6.4
94/89
.003i
2.75
2.8
.15
i9.0
06.666
22.75
7.3-6.8
/10
.0023
2.25
4.4
.29
9.5
388.46i
18.25
7.2-6.7
/ii
.0046
4.86
6.0
1.08
26.6
346.153
17.60
7.i-6.7
02
.0042
4.20
4.2
.34
i5.3
363.636
14.80
7.3-7.1
5/01
.0046
7.15
4.5
i.39
28.i
393.333
12.25
7.3-7.1
5/02
.0045
8.i0
7.9
i.25
9}.7
09.230
iO.25
7.1-7.0
AVERAGE
.803i
4.33
3.9
.52
26.2
247.6i8
i8.88
--_
MAXIMUM
.0241
ii.30
ii.6
2.7i
i2800.0
700.000
26.00
7.800
INIMUM
.0086
1.40
2.0
.i0
3.8
.150
8.00
6.300
UNIT'
MGD
MG/L
MG/L
MG/L
0/100ML
UG/L
DEG.0
%U
GKEX88/MP
, 04/26/95
COMPLIANCE EVALUATION ANALYSIS REPORT PAIE 2
PERMIT--NC0074373 PIPE--00i REPORT PERIOD: 9403-9502 LOC--- E
FACILITY--MOORE WATER AND SEWER AUTH. DESIGN FLOW-- .0600 CLASS--2
| LOCATION --VASE REGION/COUNTY--06 MOORE
00600 0866�
MONTH TOTAL N PHO%-TOT
NOL NOL
� 94/03 36.000 2.8000
� 94/O4
94/05
94/06 51.400 3.9000
94/07
� 94/08
� 94/09 4i.500 3.9000
� 94/i0
| 94/12 9.900 i.800O
� 95/0i
�95/02
AVERAGE 34.475 3.i000
MAXIMUM 51.400 3.9000
MINIMUM 9.000 i.8000
UNIT MG/L MG/L