HomeMy WebLinkAboutNC0023884_Email_20200420Scheller, Roberto
From: Robert Loper <rlope@salisburync.gov>
Sent: Thursday, November 7, 2019 11:48 AM
To: Scheller, Roberto
Subject: [External] September
Mr, Roberto Scheller,
YE had a pH violation of 5.92 on Monday, September 23, 2019. The violation was discovered 9/27/2019, 1 called in the
violation to Andrew Pitner, DEQ/DWR/MRO, 9/27/2019 at 3:42 pm.
Below is a summary of the pH investigation
On Tuesday, September 24th, 2019 around 1230 Brian Waller SPO noticed that the GE pH sample was a 5.85 at 0800 and
5.97 at 1200. He had the operator pull another GE sample while he calibrated the backup meter. He compared the two
meters at that time and our Hach meter read 5.97 compared to our VWR meter at 6.97. At that time, he replaced the
probe on our Hach meter. He attempted to perform the calibrations, but the meter would not calibrate. At that time,
he put the VWR, spare meter in service. On Wednesday, September 25th, Brian contacted Hach technical support, and
we were able to get the new probe working. We ran tests on the original probe, however, they determined that the
probe was not in range on the millivolt scale. The probe would not read a sample, continued to stay out of range. The
technician had him reinstall the new probe, he had Andrew Maysan run the calibration and everything ran through with
correct calibration. He then spoke with Toni, our Hach sales representative, and she is going to replace the bad probe
for us.
Thank You
Robert (Bob) Loper
WWTP Operations/ Bio-Solids Supervisor-ORC
COM- = ���
Salisbury -Rowan Utilities I 1 Waste Water Treatment Plants Bio-Solids Program
1915 Grubb Ferry Rd. Salisbury, North Carolina, 28144
Ph: (704) 216-2728 Celt: (704) 762-0521
t