HomeMy WebLinkAboutNC0000396_Application_20200415ROY COOPER
Governor
MICHAEL S. REGAN
Secrerary
LINDA CULPEPPER
Pireltor
Duke Energy Progress, LLC.
Attn: Gary Whisnant, Plant Manager
200 CPL Drive
Arden, NC 28704
Subject: Permit Modification
Application No. NC0000396
Asheville Steam Electric Power Plant
Buncombe County
Dear Applicant:
NORTH CAROLINA
Environmental Quality
December 12, 2019
The Water Quality Permitting Section acknowledges the December 11, 2019 receipt of your permit modification
application and supporting documentation. Your application will be assigned to a permit writer within the Section's NPDES
WW permitting branch. Per G.S. 150E-3 your current permit does not expire until permit decision on the application is
made. Continuation of the current permit is contingent on timely and sufficient application for renewal of the current
permit. The permit writer will contact you if additional information is required to complete your permit renewal. Please
respond in a timely manner to requests for additional information necessary to allow a complete review of the application
and renewal of the permit.
Information regarding the status of your renewal application can be found online using the Department of Environmental
Quality's Environmental Application Tracker at:
https: /deg.nc.gov/permits-regulations/permit-guidance/environmental-application-tracker
If you have any additional questions about the permit, please contact the primary reviewer of the application using the
links available within the Application Tracker.
Sincerely,
Wren Thedford
Administrative Assistant
Water Quality Permitting Section
ec: WQPS Laserfiche File w/application
�L Nortt Caro ra Depanrnentof EnvironroeatW Qu*Irty I D+vsion ofl5(ater ResoLroes
D Q' Ashev a Rego na Off oe 1 2090 U.S. 70 }Igh.vay I S iinnenoe, North Caro ra 28778
DUKE
Garry A. Whisnant
ENERGY, Plant General Manager
Asheville Steam Electric Plant
rgy Progress
Certified Mail: 7014 1820 0001 7891 3459Duke SVLPL I200CP&LOr
ASVL PLT � 200 CP&L Dr
Arden, NC 28704
File: 12520B
o: 828-687-5211
f 828-687-5204
garry.whisnant@duke-energy.com
December 4, 2019
Julie Grzyb
Department of Environmental Quality
NPDES Complex Permitting Unit RECEIVED
1617 Mail Service Center
Raleigh, NC 27699-1617 DEC 112019
Subject: Asheville Steam Electric Generating Plant NMEWWRINMES
NPDES Permit NC0000396
Outfall 002 NPDES Permit Modification Request
Dear Ms. Grzyb:
Asheville Steam Electric Generating Plant coal units are retiring soon. These coal units
will then proceed with decommissioning activities. The shutting down of operational
systems and decommissioning activities will warrant the need to modify the NPDES
permit. It is requested that the NPDES permit be modified to reflect the NPDES related
changes. The following and attachments provide the details associated with this permit
modification request.
The Condenser Cooling Water (CCW) system currently discharges through NPDES
Outfall 002 into Lake Julian. When the coal units are retired this system will no longer
discharge into Lake Julian. The current average flow from the CCW system is
approximately 255 mgd.
The cooling water from the evaporator system for the Combustion Turbines currently
discharges into the 64-ash basin, which discharges through NPDES Outfall 001. One
of the initial decommissioning activities is to modify the evaporator system's cooling
water flow path to discharge into the treatment pond that the CCW system currently
discharges into and then exit Outfall 002 into Lake Julian. This treatment pond also
receives storm water.
The evaporator system is used to cool air at ambient temperatures by the water flowing
across filter media into the Combustion Turbine Air Inlet. The cooling of the air
increases the combustion efficiency and maintains megawatt production level in the
warmer months. There are no chemicals added to the evaporator system. The source
of water is service water (raw lake water) from Lake Julian.
Julie Grzyb
Department of Environmental Quality
NPDES Complex Permitting Unit
December 4, 2019
The evaporator system is operated typically from May through October. The average
flowrate from this system is estimated to be 56 gpm (0.08 mgd). The temperature of this
discharge is close to ambient. The evaporator discharge will not begin to discharge to
Outfall 002 until after the CCW flow has stopped. The future flow and heat load from
the evaporator at Outfall 002 will be significantly less in comparison to the current CCW
discharge.
Therefore, it is requested that Outfall 002 be modified to include the discharge from the
evaporator system and to reflect shutting down of the coal station's CCW. Continuous
thermal, flow and chlorine sampling associated with the CCW flows are requested to be
removed with this modification as the addition of chlorine at the intake structure has
ceased.
Attached are sample results from the evaporator cooling water, a process flow diagram
that shows the evaporator, an aerial photo identifying the flow paths for the changes
described in this submittal and a check for $1,030 to process this permit modification
request.
Should you have questions or need additional information please contact Robert Wylie
at 704 382-4669.
Sincerely,
Garry Whisnant, Plant Manager
GM II - Regulated Stations
Attachments:
A. Evaporator Analytical Data
B. Process Flow Diagram
C. Aerial Photos Illustrating Current and Future Flow Paths
D. Check for Modification Fee
cc: Landon Davidson, DEQ, Asheville Regional Office
Teresa Williams, Duke Energy
Robert Wylie, Duke Energy
Attachment A
Evaporator Analytical Data
Asheville Electric Power Plant
NPDES Permit # NC0000396
Evaporator Cooling Water Analytical Results
Item
Parameter
Concentration
1
Chloride
17.2 mg/L
2
Chromium
0.80 ug/L
3
Copper
2.4 ug/L
4
Hardness
26 mg/L
5
Iron
61.9 ug/L
6
Magnesium
3.1 mg/L
7
Manganese
12.8 ug/L
8
Nickel
ND
9
Oil and Grease
ND
10
Sulfate
6.2 mg/L
11
TDS
99.0 mg/L
12
TSS
ND
13
Zinc
ND
ND = Not Detected
Note the temperature should be approximately the same as the ambient
temperature.
Attachment B
Process Flow Diagram
Combined and Simple Cycle Combustion Turbine Plant
Attachment C
Aerial Photos Illustrating Current and Future Flow Paths
e Duke Energt
® Asheville P an
r
Dam is removed —
future industrial
210
KEY
F— Ash Treatment — Sluice lines to Rim Ditch,
Center Pond, Filter Skid, pH building, outfall 001
Plant Drains, Coal Pile Run off RO,
OWS(LVSW)
W WT — FGD Blowdown (currently to PCITW)
1964 Basin Dewatering (Duck Pond)-
LVSW, Ash removal decant, Industrial SW,
Once through Cooling — outfall 002
Industrial SW Permit area (SW1, 3)
River Pump make up to Lake Julian
002
001
Asheville plant current NPDES flows at Coal Plant Shut down/CC start
OOlA
001C
KEY
<— Waste water line to outfall 001
<_ Demo - Plant Drains, Coal Pile Run
off, LVSW, Existing OWS
Ems. W WT — FGD Blowdown (currently to VISD)
1964 Basin Dewatering
LVSW, Ash removal decant, Industrial SW,
.;,Convert Once through Cooling—outfall
002 to CT EVAP Cooler/stormwater
< —Industrial SW area — adding upper back
road, Fuel oil, CC
River Pump make up to Lake Julian
Attachment D
Check for Modification Fee