Loading...
HomeMy WebLinkAboutNC0036242_Compliance Evaluation Inspection_20200324ROY COOPER Governor MICHAEL S. REGAN Secretary S. DANIEL SMITH Director Mr. Jadd Brewer Water Quality Utilities, Inc. P.O. Box 1167 Banner Elk, NC 28604-1167 NORTH CAROLINA Environmental Quality March 24, 2020 SUBJECT: Compliance Evaluation Inspection Woodland Hills Apartments WWTP NPDES Permit No. NCO036242 Watauga County Dear Mr. Brewer, On March 19, 2020, Kelli Park, of this office, met with Paul Isenhour, Operator in Responsible Charge (ORC), to perform a Compliance Evaluation Inspection at the Woodland Hills wastewater treatment plant. This type of inspection consists of two basic parts: an in -office file review and an on -site inspection of the treatment facility. The attached EPA inspection form details the areas that were evaluated during this inspection. Concerns noted during the inspection are outlined below: 1) Ms. Park also noted a data transcription error for dissolved oxygen for July 22, 2020. Operators must be more careful when transcribing data from source documentation to DMRs to prevent such reporting errors. If you have any questions regarding the inspection or this report, please contact Kelli Park or me at (336) 776-9800 or by email at kelli.park(a)ncdenr.gov or Ion. snider(cZincdenr.gov. Sincerely, Docu SiTgnedl�by: �- 145B49E225C94EA... Lon Snider Regional Supervisor Water Quality Regional Operations Division of Water Resources Attachments: EPA Water Compliance Inspection Report cc: WSRO North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office [ 450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105 H nahr�cARo1.1Ha � NOp m o-o�ma�r o�.r� /"� 336.776.9800 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 u 3 I NC0036242 111 121 20/03/19 I17 18 LC] I 19 I s I 20L] 21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 67 I 72 I n, I 71 I 74 79 I I I I I I I80 701 I 71 I LL -1 I I LJ Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 11:15AM 20/03/19 17/12/01 Woodland Hills Apartments WWTP NCSR 1107 Exit Time/Date Permit Expiration Date Boone NC 28607 12:OOPM 20/03/19 22/09/30 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Paul E. Isenhour/ORC/828-898-6277/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Heather Sofield,355 Industrial Park Dr Boone NC 28607H828-268-0994/8282623887 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenar 0 Records/Reports Self -Monitoring Progran 0 Facility Site Review Effluent/Receiving Wate Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Kelli A Park Docusigned by: DWR/WSRO WQ/336-776-9689/ tu: PA4 3/24/2020 E B4A41 DCE74C34B9_. Signature of Management Q A Revie cBu4S,gned by: Agency/Office/Phone and Fax Numbers Date Lon Snider L�ti 7 S"je, 3/24/2020 145B49E225C94EA... EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NCO036242 I11 12I 20/03/19 117 18 i c i (Cont.) Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On March 19, 2020, Kelli Park, of this office, met with Paul Isenhour, Operator in Responsible Charge (ORC), to perform a Compliance Evaluation Inspection at the Woodland Hills wastewater treatment plant. This type of inspection consists of two basic parts: an in -office file review and an on -site inspection of the treatment facility. The attached EPA inspection form details the areas that were evaluated during this inspection. Concerns noted during the inspection are outlined below: 1) Ms. Park also noted a data transcription error for dissolved oxygen for July 22, 2020. The lab sheet indicated 6.12 mg/I, while 8.61 mg/1 was entered on the DMR. Operators must be more careful when transcribing data from source documentation to DMRs to prevent such reporting errors. If you have any questions regarding the inspection or this report, please contact Kelli Park or me at (336) 776-9800 or by email at kelli.park@ncdenr.gov or lon.snider@ncdenr.gov. Page# Permit: NCO036242 Inspection Date: 03/19/2020 Operations & Maintenance Is the plant generally clean with acceptable housekeeping? Owner -Facility: Woodland Hills Apartments WWTP Inspection Type: Compliance Evaluation Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Permit (If the present permit expires in 6 months or less). Has the permittee submitted a new application? Is the facility as described in the permit? # Are there any special conditions for the permit? Is access to the plant site restricted to the general public? Is the inspector granted access to all areas for inspection? Comment: Record Keeping Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Is the backup operator certified at one grade less or greater than the facility classification Is a copy of the current NPDES permit available on site? Yes No NA NE ❑ ❑ ❑ ❑ ❑ ❑ Yes No NA NE ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ Yes No NA NE ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Page# 3 Permit: NCO036242 Inspection Date: 03/19/2020 Owner -Facility: Woodland Hills Apartments WWTP Inspection Type: Compliance Evaluation Record Keeping Facility has copy of previous year's Annual Report on file for review? Comment: There was a data transcription error on July 22, 2020 for DO ORC is a grade 4, bORC is a grade 3 Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Yes No NA NE ❑ ❑ ■ ❑ Yes No NA NE ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ Comment: Flow is estimated mathematically by collecting water in a bucket and using a timer. Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? 0 ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/I) 0 ❑ ❑ ❑ Comment: DO maintained around 1.5-2 mg/I Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? 0 ❑ ❑ ❑ Is the site free of weir blockage? 0 ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ 0 ❑ Is the return rate acceptable (low turbulence)? 0 ❑ ❑ ❑ Page# 4 Permit: NCO036242 Inspection Date: 03/19/2020 Owner -Facility: Woodland Hills Apartments WWTP Inspection Type: Compliance Evaluation Secondary Clarifier Yes No NA NE Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) 0 ❑ ❑ ❑ Comment: Sludge blanket estimated to be about 20% of the clarifier depth Pumping records are available. Triple T pumped the plant in Feb 2020. Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? 0 ❑ ❑ ❑ Number of tubes in use? 0 Is the level of chlorine residual acceptable? ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ Comment: Cl tablets are placed in the weirs De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 1 Comment: a plastic gallon container is used to hold to de-cl tabelts in a holding tank under a manhole before being discharged to the stream. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ ❑ Comment: Effluent pipe does not exist. The effluent goes from the plant into a culvert which then is mixed in with stormwater drainaaes before reachina the stream. Effluent Sampling Yes No NA NE Page# 5 Permit: NCO036242 Inspection Date: 03/19/2020 Effluent Sampling Is composite sampling flow proportional? Owner -Facility: Woodland Hills Apartments WWTP Inspection Type: Compliance Evaluation Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: Sample is collected from the manhole after dechlorination Upstream / Downstream Sampling Is the facility sampling performed as required by the permit (frequency, sampling type, an( sampling location)? Comment: Yes No NA NE ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Yes No NA NE ■ ❑ ❑ ❑ Page# 6