HomeMy WebLinkAboutNC0032867_Inspection_20171220United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO032867 I11 121 17/12/20 I17 18 U 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
1.0 70J 711„ I 72 L.71 74 79 I I I I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
11:15AM 17/12/20
14/01/01
Kings Mountain Travel Plaza
400 Dixon School Rd
Exit Time/Date
Permit Expiration Date
Kings Mountain NC 28086
12:50PM 17/12/20
18/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Ken Deaver,PO Box 63 Rutherfordton NC
281390063/ORC/828-657-1810/8286574664 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Flow Measurement 0 Operations & Maintenar 0 Facility Site Review 0 Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell DWR/MRO WQ/704-663-1699 Ext.2192/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCO032867 I11 12I 17/12/20 117 18 IRI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The wastewater treatment plant was not being properly operated and maintained. The following
observations were noted during the site inspection:
- Untreated wastewater had accumulated on the ground beside the leaking septic tanks;
- No aeration was being provided in one of the aeration basin trains due to inoperable blower/motor
units (2-total). Note: Influent flow was entering both aeration basin trains;
- The wastewater in the inoperable aeration basin train was septic due to lack of aeration;
- The microbial population in the operable aeration basin appeared very low;
- No tablets were in the dechlorination unit;
- Flow meter had not been calibrated in over a year;
- The strip chart recording device on flow meter was not operational;
- The effluent TRC sample (>500 ug/L) exceeded the permit limit;
- The effluent ammonia sample (54 mg/L) exceeded the permit limit;
- The effluent appeared turbid with suspended solids
Page#
Permit: NCO032867
Inspection Date: 12/20/2017
Owner -Facility: Kings Mountain Travel Plaza
Inspection Type: Reconnaissance
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Yes No NA NE
Page#