On March 9, 2020, staff of the NC Division of Water Resources (DWR) inspected the subject Wastewater
Irrigation System in Durham County. We wish to thank Guido Carrera, the ORC, for his help during the
inspection.
On the day of the inspection, the ORC stated that the septic tank was Iast pumped in October 2018. There
is a riser over the second chamber of the septic tank but not the first. The second chamber was opened.
The filter was found to be in good condition. It was cleaned during the inspection. A sludge judge used to
determine that there is 8 to 12" of solids in the second chamber of the septic tank. It is unknown how much
solids are in the first chamber. It is time to have both chambers of the septic tank pumped.
There are no signs of surfacing water at the sand filter.
There were chlorine tablets in the chlorinator.
The sprayfield pump tank appeared to be in good condition. The timer operated pump was operated and
all sprayheads were in good working order. There was a fence and a sign around the sprayfield and
vegetation is being maintained. The pump was last calibrated with a drawdown test in 2018 and found to
be pumping 14 gpm.
The facility averages 60 to 140 gpd of the 500 gpd permitted (low and irrigates 5 - 7" of the 39" permitted.
Records were reviewed and found to be in good order. Records have been submitted complete and on time,
There are no violations in the BIMS database for data submissions.
ivorlh Car�l'na Uep�utment of E'n:ir�nrnenWl t�ualii� U:visiorr of 41+aicr krsourcc�
R�[t'i91t lteg:und[ Of#ice )800 L'arrcre UtivC Raleigh, North Catulino 2709
910 791 11rin
The following items specify permit conditions and limitations that were in violation during the time of the
inspection. Please also refer to the attached inspection report.
1I. PERFORMANCE STANDARDS
Condition 1 which states, "The subject non -discharge facilities shall be effectively maintained and operated at
all times...
On the day of the inspection, neither the visual or audible alarm were working and the floats used to shut
the pump off to prevent it from burning out in low water conditions was not in working order.
The audible and visual alarms must be repaired and the low Neater cutoff system should be repaired
to protect the pump.
This office requires that the violations, as detailed above, be abated immediately and properly resolved.
Environmental damage and violations of North Carolina Administrative Codes have been documented for
the subject site as stated above. Your efforts to undertake activities to bring the subject site back into
compliance is not an admission, rather it is an action that must be taken in order to begin to resolve ongoing
environmental issues.
You are required to take any necessary action to correct the above violations and to provide a written
response to this Notice on or before December 31, 2018. Please include in your response all corrective
actions already taken and a schedule for completion of any corrective actions not addressed. Failure to
comply with the State's rules, in the manner and time specified, may result in the assessment of civil
penalties and/or the use of other enforcement mechanisms available to the State.
Failure to comply with conditions in a permit may result in a recommendation of enforcement action, to the
Director of the Division of Water Resources, who may issue a civil penalty assessment of not more that
twenty-five thousand ($25,000) dollars against any "person' who violates or fails to act in accordance with
the terms, conditions, or requirements of a permit under authority of G.S. 143-215.6A.
If you have any questions concerning this notice, please contact Ray Milosh or me at (919) 791-
4200.
Sincerely,
cott Vinson
Regional Supervisor — Raleigh Regional Office
Water Quality Regional Operations Section
NCDEQ — Division of Water Resources
Attachment: Inspection Report
cc: RRO-WQROS Files
Water Quality Section Central riles
Compliance Inspection Re ort
Permit:WQ0005134 Effective: 05101f15 Expiration: 44/30/20 Owner: Wake Co Wildlife Club
SOC: Effective: Expiration: Facility: Wake Co Wildlife Club -Coley
County: Durham 1313 Coley Rd
Region: Raleigh
Raleigh NC 27624
Contact Person: Edward C Margeson Title: Phone: 919-783-7406
Directions to Facility:
From Raleigh, NC 50 N. NC 98 W. From 1,1 mi. west of Durham Ca line Left on Coley Rw 0.6 mi. Driveway on left,
System Classifications: SI,
Primary ORC: Guido James Carrara Certification: 25013 Phone: 919427-1786
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 03109?2020 Entry Time 12.001DM Exit Time: 01:30PM
Primary Inspector: Raymond M Milosh Phone: 9119-791-4200
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: ❑ Compliant Not Compliant
Question Areas:
Miscellaneous Questions Treatment Record Keeping
End Use -Irrigation Treatment Disinfection
(See attachment summary)
Page 1 of 5
Permit: W00005134 owner. Facility:Wake Co Wildlife Club
Inspection Date: 03/09/2020 inspection Type :Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
On March 9, 2020, staff of the NC Division of Water Resources (DWR) inspected the subject Wastewater Irrigation System
in Durham County. We wish to thank Guido Carrera, the ORC, for his help during the inspection.
On the day of the inspection, the ORC stated that the septic tank was last pumped in October 2018. There is a riser over
the second chamber of the septic tank but not the first. The second chamber was opened. The filter was found to be in
good condition. It was cleaned during the inspection. A sludge judge used to determine that there is 8 to 12" of solids in the
second chamber of the septic tank. It is unknown how much solids are in the first chamber. It is time to have both
chambers of the septic tank pumped.
There are no signs of surfacing water at the sand filter.
There were chlorine tablets in the chlorinator.
The sprayfield pump tank appeared to be in good condition. The timer operated pump was operated and all sprayheads
were in good working order. There was a fence and a sign around the sprayfield and vegetation is being maintained. The
pump was last calibrated with a drawdown test in 2018 and found to be pumping 14 gpm.
The facility averages 60 to 140 gpd of the 500 gpd permitted flow and irrigates 5 — 7" of the 39" permitted.
Records were reviewed and found to be in good order. Records have been submitted complete and on time. There are no
violations in the RIMS database for data submissions.
The following items specify permit conditions and limitations that were in violation during the time of the inspection. Please
also refer to the attached inspection report.
11. PERFORMANCE STANDARDS
Condition 1 which states, "The subject non -discharge facilities shall be effectively maintained and operated at all times...
On the day of the inspection, neither the visual or audible alarm were working and the floats used to shut the pump off to
prevent it from burning out in low water conditions was not in working order.
The audible and visual alarms must be repaired and the low water cutoff system should be repaired to protect the pump.
This office requires that the violations, as detailed above, be abated immediately and properly resolved. Environmental
damage and violations of North Carolina Administrative Codes have been documented for the subject site as stated above
Your efforts to undertake activities to bring the subject site back into compliance is not an admission, rather it is an action
that must be taken in order to begin to resolve ongoing environmental issues.
You are required to take any necessary action to correct the above violations and to provide a written response to this Notice
on or before December 31, 2018. Please include in your response all corrective actions already taken and a schedule for
completion of any corrective actions not addressed. Failure to comply with the State's rules, in the manner and time
specified, may result in the assessment of civil penalties and/or the use of other enforcement mechanisms available to the
State.
Failure to comply with conditions in a permit may result in a recommendation of enforcement action, to the Director of the
Division of Water Resources, who may issue a civil penalty assessment of not more that twenty-five thousand ($25,000)
dollars against any "person" who violates or fails to act in accordance with the terms, conditions, or requirements of a permit
under authority of G.S. 143-215.6A.
Page 2 of 5
Permit: W00005134 owner - Facility: Wake Co Wildlife Club
Inspection hate: 03/09/2020 Inspection Type :Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Infiltration System
Lagoon Spray, LR
Single Family Spray, LR
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Recycle/Reuse
Activated Sludge Drip, LR
Single Family Drip
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0
Do all treatment units appear to be operational? (if no, note below.) ❑ 0 E30
Comment: The audible and visual alarm and the low water cut off at the s ra field dosing panel are not
working. Both chambers of the septic tank needs to bew um ed out.
Treatment Disinfection
Yes No NA NE
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (-30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
E El
Is the fan in the chlorine feed room and storage area operable?
■ 11
Is the chlorinator accessible?
0
If tablets, are tablets present?
Are the tablets the proper size and type?
❑ ❑
Is contact chamber free of sludge, solids and growth?
❑ El
If UV, are extra UV bulbs available?
0
If UV, is the UV intensity adequate?
El El 0
# Is it a dual feed system?
❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No, 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
El El N El
If yes, then what is the EPA twelve digit ID Number? (1000- -_)
If yes, then when was the RMP last updated?
Comment:
Record Keeping
Yes No NA NE
Page 3 of 5
Permit: W00005134 owner - Facility: Wake Co Wildlife Club
Inspection Date: 03109/2020 Inspection Type : Compl ante Evaluation Reason for Visit: Routine
is a copy of current permit available?
N ❑ ❑ ❑
Are monitoring reports present: NDMR?
0 ❑ ❑ ❑
NDAR?
0 ❑ ❑ ❑
Are flow rates less than of permitted flow?
E ❑ ❑ ❑
Are flow rates less than of permitted flow?
E ❑ ❑ ❑
Are application rates adhered to?
E ❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ E ❑
Are all samples analyzed for all required parameters?
N ❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ E ❑
is GW 59A certification form completed for facility?
❑ ❑ E ❑
Is effluent sampled for same parameters as GW?
❑ ❑ 0 ❑
Do effluent concentrations exceed GW standards?
❑ ❑ ❑
Are annual soil reports available?
❑ ❑ ❑
# Are PAN records required?
N ❑ ❑ ❑
# Did last soil report indicate a need for lime?
E ❑ ❑ ❑
If so, has it been applied?
E ❑ ❑ ❑
Are operational logs present?
0 ❑ ❑ ❑
Are lab sheets available for review?
E ❑ ❑ ❑
Do lab sheets support data reported on NDMR?
■ ❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
0 ❑ ❑ ❑
Are Operational and Maintenance records present?
N ❑ ❑ ❑
Were Operational and Ma'ntenance records complete?
0 ❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
0 ❑ ❑ ❑
Is a copy of the SOC readily available?
0 Cl ❑ ❑
No treatment units bypassed since last inspection?
0 ❑ ❑ ❑
Comment:
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
0 ❑ ❑ ❑
Is the cover crop type specified in permit?
❑ ❑ ❑
Is the crop cover acceptable?
❑ ❑ ❑
Is the site condition adequate?
■ ❑ ❑ ❑
1s the site free of runoff / ponding?
■ ❑ ❑ ❑
Is the acreage specified in the permit being utilized?
0 ❑ Cl ❑
Is the application equipment present?
E ❑ ❑ ❑
Is the applicat;0n equipment operational?
❑ ❑ ❑
Is the disposal Feld free of limiting slopes?
❑ ❑ ❑
Page 4 of 5
Permit: WO0005134 Owner - Facility: Wake Co Wildlife Club
Inspection Date: 03/0912020 Inspection Type : Compl ance Evaluation Reason for Visit: Routine
Is access restricted and/or signs posted during act,ve site use? 0❑
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well? El E3 N El
Is municipal water available in the area?
# Info only. Does the permit call for monitoring wells? ❑ M
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed. including screened interval? M
Are monitoring wells damaged? El 13■
Comment: