HomeMy WebLinkAboutNC0040355_Compliance Evaluation Inspection_20090630 Er1LE CCTV
•
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Coleen H. Sullins Dee Freeman
Governor Director Secretary
June 30, 2009
Fred Tingle, General Manager
Royal Oaks, Inc. — Springdale Country Club
200 Golfwatch Road
Canton, NC 28716
SUBJECT: Compliance Evaluation Inspection
Springdale Country Club WWTP
•
Permit No. NC0040355
Haywood County
Dear Mr. Tingle:
Enclosed please find a copy of the Compliance Evaluation Inspection form from the
inspection conducted on June 26, 2009. The facility was found to be in compliance with permit
NC0040355.
Please refer to the enclosed inspection report for additional observations and comments.
If you or your staff have any questions, please call me at 828-296-4500 ext.4662.
Sincerely,
Wanda P. Frazier
Environmental Specialist
Enclosure
cc: Central Files
shevitle File. , „
SURFACE WATER PROTECTION—ASHEVILLE REGIONAL OFFICE One
Nort arohCar• Fn
a
Location: 2090 U.S. Highway 70,Swannanoa, NC 28778 Naturally
Phone: (828)296-45001FAX: 828 299-70431Customer Service: 1-877-623-6748
Internet:www.ncwaterqualitv.orq
United States Environmental Protection Agency Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day • Inspection Type Inspector Fac Type
1 I N1 2 15I 31 NC0040355 111 121 09/06/26 1 17 181 cl 191 sl 201 I
Remarks
21I111111I IIII III •1IIII111111II111111IIIIII IIIIII166
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA - -----------Reserved-----------
671 1.0 1 69 .701 31 711 I 721 N I "1 1 1 74 75I 1 1 1 1 1 1 1 80
Section B: Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number)
03:00 PM 09/06/26 06/04/01
Springdale Country Club WWTP
Springdale Country Club Exit Time/Date Permit Expiration Date
Canton NC 28716 03:30 PM 09/06/26 11/01/31
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Gifford C Raulerson,200 Golfwatch Rd Canton NC 28716//828-235-8451/ No
Section C: Areas Evaluated During Inspection(Check only those areas evaluated)
®Permit • ®Operations&Maintenance ®Records/Reports ®Facility Site Review
IN Effluent/Receiving Waters
Section D: Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date •
Wanda P Frazier ARO WQ//828-296-4500 Ext.4662/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
F
NPDES yr/mo/day Inspection Type
i
3I NC0040355 I11 121 09/06/26 I17 181C1
Section D: Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Mr. Henry Dyer& Mr. Gifford Raulerson assisted with the inspection.
The effluent appeared clear, indicating compliance with permit limits.
The surface of the plant is in need of attention. It is very corroded and rusted.
The weeds need to be removed.
Page# 2
Permit: NC0040355 Owner-Facility: Springdale Country Club wWfP
Inspection Date: 06/26/2009 • Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application? n n S n
Is the facility as described in the permit? N n n n
#Are there any special conditions for the permit? n ® n n
Is access to the plant site restricted to the general public? ® n n n
Is the inspector granted access to all areas for inspection? ® n n n
Comment: •
Bar Screens Yes No NA NE
Type of bar screen
a.Manual !�
b.Mechanical • n
Are the bars adequately screening debris? - n n n
Is the screen'free of excessive debris? fignnn
Is disposal of screening in compliance? Einnn
Is the unit in good condition? , n n n
Comment: • •
Equalization Basins Yes No NA NE
Is the basin aerated? n ® n n
Is the basin free of bypass lines or structures to the natural environment? AN n n n
Is the basin free of excessive grease? E ❑ n n
Are all pumps present? ® n n n
Are all pumps operable? ® n n n
Are float controls operable? ® .n n n
Are audible and visual alarms operable? ❑ its n n
#Is basin size/volume adequate? •
Comment: Due to low flow, the EQ basin is aerated only one day, every two weeks.
There is a visual alarm, but no audible alarm.
Aeration Basins Yes No NA NE
Mode of operation Ext.Air
•
Type of aeration system Diffused
Is the basin free of dead spots? ® n n n
•
Page# 3
• 111
Permit: NC0040355 Owner-Facility: Springdale Country Club VVWTP
Inspection Date: 06/26/2009 Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Are surface aerators and mixers operational? n n ® n
Are the diffusers operational? ® n n n
Is the foam the proper color for the treatment process? ® n n n
Does the foam cover less than 25%of the basin's surface? ® n n n
Is the DO level acceptable? ® n n n
Is the DO level acceptable?(1.0 to 3.0 mg/I) ® n n n
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? ® n n n
Is the site free of excessive buildup of solids in center well of circular clarifier? n n ® n
Are weirs level? ® n n n
Is the site free of weir blockage? ® n n n
Is the site free of evidence of short-circuiting? ® n n n
Is scum removal adequate? ® n n n
Is the site free of excessive floating sludge? ® n n n
Is the drive unit operational? n n ■ n
Is the return rate acceptable(low turbulence)? ® n n n
Is the overflow clear of excessive solids/pin floc? la n n n
Is the sludge blanket level acceptable?(Approximately'/of the sidewall depth) s n n n
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? ® n n n
Are the tablets the proper size and type? ® n n n
Number of tubes in use? 2
Is the level of chlorine residual acceptable? n n n
Is the contact chamber free of growth,or sludge buildup? tr, n n n
Is there chlorine residual prior to de-chlorination? *? n n n
Comment:
De-chlorination Yes No NA NE
Type of system? Tablet
Page# 4
r
Permit: NC0040355 Owner-Facility: Springdale Country Club VWVTP
Inspection Date: 06/26/2009 Inspection Type: Compliance Evaluation
De-chlorination Yes No NA NE
Is the feed ratio proportional to chlorine amount(1 to 1)? 0 0 ■ 0
Is storage appropriate for cylinders? n n ■ ❑
#Is de-chlorination substance stored away from chlorine containers? ® ❑ n n
•
Comment:
Are the tablets the proper size and type? • ® ❑ ❑ ❑
Are tablet de-chlorinators operational? ® ❑ ❑ ❑
Number of tubes in use? 2
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ ® ❑ n
Does the facility analyze process control parameters,for ex: MLSS, MCRT,Settleable Solids, pH, DO,Sludge El ❑ 0
Judge, and other that are applicable?
Comment: There were waist high weeds all around the plant. More attention to
housekeeping is needed. •
Page# 5